Network Working Group                            M. Chandramouli 
     Internet-Draft                               Cisco Systems, Inc. 
     Intended Status: Standards Track                    B. Schoening 
     Expires: April 31 2012                    Independent Consultant 
                                                           J. Quittek 
                                                             T. Dietz 
                                                      NEC Europe Ltd. 
                                                            B. Claise 
                                                  Cisco Systems, Inc. 
                                                     October 31, 2011 
                                                                      
      
                        Power and Energy Monitoring MIB 
                      draft-ietf-eman-energy-monitoring-mib-01

     Status of this Memo 

        This Internet-Draft is submitted to IETF in full conformance 
        with the provisions of BCP 78 and BCP 79.   
           
        Internet-Drafts are working documents of the Internet 
        Engineering Task Force (IETF), its areas, and its working 
        groups.  Note that other groups may also distribute working 
        documents as Internet-Drafts.  
         
        Internet-Drafts are draft documents valid for a maximum of six 
        months and may be updated, replaced, or obsoleted by other 
        documents at any time.  It is inappropriate to use Internet-
        Drafts as reference material or to cite them other than as  
        "work in progress."  
         
        The list of current Internet-Drafts can be accessed at 
        http://www.ietf.org/ietf/1id-abstracts.txt  
         
        The list of Internet-Draft Shadow Directories can be accessed  
        at http://www.ietf.org/shadow.html  
         
        This Internet-Draft will expire on February 2012.                     


      
     <Claise, et. Al>        Expires April 15  2012            [Page 1] 

     Internet-Draft <Power and Energy Monitoring MIB>   October 2011 
      
      
     Copyright Notice 
      
        Copyright (c) 2011 IETF Trust and the persons identified as the 
        document authors.  All rights reserved. 
         
        This document is subject to BCP 78 and the IETF Trust's Legal 
        Provisions Relating to IETF Documents 
        (http://trustee.ietf.org/license-info) in effect on the date of 
        publication of this document.  Please review these documents 
        carefully, as they describe your rights and restrictions with 
        respect to this document.  Code Components extracted from this 
        document must include Simplified BSD License text as described 
        in Section 4.e of the Trust Legal Provisions and are provided 
        without warranty as described in the Simplified BSD License. 
         
         
     Abstract 

        This document defines a subset of the Management Information 
        Base (MIB) for power and energy monitoring of devices.  
         
     Conventions used in this document 

        The key words "MUST", "MUST NOT", "REQUIRED", "SHALL", "SHALL 
        NOT", "SHOULD", "SHOULD NOT", "RECOMMENDED", "NOT RECOMMENDED", 
        "MAY", and "OPTIONAL" in this document are to be interpreted as 
        described in RFC 2119 [RFC2119]. 
         
         
         
        Table of Contents 
         
        1. Introduction............................................. 3 
        2. The Internet-Standard Management Framework............... 4 
        3. Use Cases................................................ 4 
        4. Terminology.............................................. 5 
        5. Architecture Concepts Applied to the MIB Module.......... 5 
        5.1. Energy Object Information............................. 12 
        5.2. Power State........................................... 12 
              5.2.1. Power State Set................................13 
              5.2.2. IEEE1621 Power State Set.......................13 
              5.2.3. DMTF Power State Set...........................14 
              5.2.4. EMAN Power State Set...........................15 
        5.3. Energy Object Usage Information....................... 18 
        5.4. Optional Power Usage Quality.......................... 18 
        5.5. Optional Energy Measurement........................... 19 
      
      
     <Claise, et. Al>        Expires April 31, 2012            [Page 2] 
         

     Internet-Draft <Power and Energy Monitoring MIB>   October 2011 
      
        5.6. Fault Management...................................... 23 
        6. Discovery............................................... 23 
        6.1. ENERGY-AWARE-MIB Module Implemented................... 23 
        6.2. ENERGY-AWARE-MIB Module Not Implemented, ENTITY-MIB 
        Implemented................................................ 24 
        6.3. ENERGY-AWARE-MIB Module and ENTITY-MIB Not Implemented.25 
        7. Link with the other IETF MIBs........................... 25 
           7.1. Link with the ENTITY MIB and the ENTITY-SENSOR MIB..25 
           7.2. Link with the ENTITY-STATE MIB......................26 
           7.3. Link with the POWER-OVER-ETHERNET MIB...............27 
           7.4. Link with the UPS MIB...............................28 
           7.5. Link with the LLDP and LLDP-MED MIBs................29 
        8. Implementation Scenario................................. 29 
        9. Structure of the MIB.................................... 32 
        10. MIB Definitions........................................ 32 
        11. Security Considerations................................ 69 
        12. IANA Considerations.................................... 70 
        12.1. IANA Considerations for the MIB Modules.............. 70 
        12.2. IANA Registration of new Power State Set............. 71 
         12.2.1. IANA Registration of the IEEE1621 Power State Set..71 
         12.2.2. IANA Registration of the DMTF Power State Set......71 
         12.2.3. IANA Registration of the EMAN Power State Set......72 
        12. Contributors........................................... 72 
        13. Acknowledgment......................................... 72 
        14. Open Issues............................................ 73 
        15. References............................................. 74 
           15.2. Normative References...............................74 
           15.3. Informative References.............................74 
      

              
         
         
     1. Introduction 

        This document defines a subset of the Management Information 
        Base (MIB) for use in energy management of devices within or 
        connected to communication networks.  The MIB modules in this 
        document are designed to provide a model for energy management, 
        which includes monitoring for power state and energy consumption 
        of networked elements.  This MIB takes into account the Energy 
        Management Framework  [EMAN-FRAMEWORK], which in turn, is based 
        on the Requirements for Energy Management[EMAN-REQ]. 
         
        Energy management is applicable to devices in communication 
        networks.  Target devices for this specification include (but 
        are not limited to): routers, switches, Power over Ethernet 
        (PoE) endpoints, protocol gateways for building management 
      
      
     <Claise, et. Al>        Expires April 31, 2012            [Page 3] 
         

     Internet-Draft <Power and Energy Monitoring MIB>   October 2011 
      
        systems, intelligent meters, home energy gateways, hosts and 
        servers, sensor proxies, etc. Target devices and the use cases 
        for Energy Management are discussed in Energy Management 
        Applicability Statement [EMAN-AS]. 
         
        Where applicable, device monitoring extends to the individual 
        components of the device and to any attached dependent devices. 
        For example: A device can contain components that are 
        independent from a power-state point of view, such as line 
        cards, processor cards, hard drives.  A device can also have 
        dependent attached devices, such as a switch with PoE endpoints 
        or a power distribution unit with attached endpoints. 
         
        Devices and their sub-components may be characterized by the 
        power-related attributes of a physical entity present in the 
        ENTITY MIB, even though the ENTITY MIB compliance is not a 
        requirement due to the variety and broad base of devices 
        concerned with energy management. 
         
         
     2. The Internet-Standard Management Framework 

        For a detailed overview of the documents that describe the 
        current Internet-Standard Management Framework, please refer to 
        section 7 of RFC 3410 [RFC3410]. 
         
        Managed objects are accessed via a virtual information store, 
        termed the Management Information Base or MIB. MIB objects are 
        generally accessed through the Simple Network Management 
        Protocol (SNMP).  Objects in the MIB are defined using the 
        mechanisms defined in the Structure of Management Information 
        (SMI).  This memo specifies MIB modules that are compliant to 
        SMIv2, which is described in STD 58, RFC 2578 [RFC2578], STD 58, 
        RFC 2579 [RFC2579] and STD 58, RFC 2580 [RFC2580]. 
         
         
     3. Use Cases 

        Requirements for power and energy monitoring for networking 
        devices are specified in [EMAN-REQ].  The requirements in [EMAN-
        REQ] cover devices typically found in communications networks, 
        such as switches, routers, and various connected endpoints.  For 
        a power monitoring architecture to be useful, it should also 
        apply to facility meters, power distribution units, gateway 
        proxies for commercial building control, home automation 
        devices, and devices that interface with the utility and/or 
        smart grid.  Accordingly, the scope of the MIB modules in this 
        document is broader than that specified in [EMAN-REQ].  Several 
      
      
     <Claise, et. Al>        Expires April 31, 2012            [Page 4] 
         

     Internet-Draft <Power and Energy Monitoring MIB>   October 2011 
      
        use cases for Energy Management have been identified in the 
        "Energy Management (EMAN) Applicability Statement" [EMAN-AS]. An 
        illustrative example scenario is presented in Section 8.  
         
         
     4. Terminology 

          The definitions of basic terms such as  Energy Object, Energy 
          Object Parent, Energy Object Child, Energy Object Meter 
          Domain, Power State can be found in the terminology draft 
          draft-parello-eman-definitions.  
         
      
        Power State Set 
         
          A Power State Set is defined as a sequence of incremental 
          energy saving modes of a device.  The elements of this set can 
          be viewed as an interface for the underlying device-
          implemented power settings of a device.  Examples of Power 
          State Sets include DTMF [DMTF], IEEE1621 [IEEE1621], ACPI 
          [ACPI] and EMAN.  
           
          EDITOR NOTE: Use the latest definition from draft-parello-
          eman-definitions 
         
        Power State 
         
          A Power State is defined as a specific power setting for an  
          Energy Object (e.g., shut, hibernate, sleep, high). Within the 
          context of a Power State Set, the Power State of a device is 
          one of the power saving modes in that Power State Set.  
           
          EDITOR NOTE: Use the latest definition from draft-parello-
          eman-definitions 
      
      
      
         
         
     5. Architecture Concepts Applied to the MIB Module 

        This section describes the concepts specified in the Energy 
        Management Framework [EMAN-FRAMEWORK] that pertain to power 
        usage, with specific information related to the MIB module 
        specified in this document.  This subsection maps to the section 
        "Architecture High Level Concepts" in the Power Monitoring 
        Architecture [EMAN-FRAMEWORK]. 
         
      
      
     <Claise, et. Al>        Expires April 31, 2012            [Page 5] 
         

     Internet-Draft <Power and Energy Monitoring MIB>   October 2011 
      
        The Energy Monitoring MIB has 2 independent MIB modules. The 
        first MIB module energyObjectMib is focused on measurement of 
        power and energy. The second MIB module powerQualityMIB is 
        focused on Power Quality measurements.  
         
        The energyObjectMib MIB module consists of four tables.  The 
        first table eoPowerTable is indexed by eoPowerIndex. The second 
        table eoPowerStateTable indexed by eoPowerIndex,and 
        eoPowerStateIndex. . The eoEnergyParametersTable and 
        eoEnergyTable are indexed by eoPowerIndex.  
         
         eoPowerTable(1) 
          | 
          +---eoPowerEntry(1) [eoPowerIndex] 
          |   |  
          |   +-- --- Integer32         eoPowerIndex(1) 
          |   +---r-n Integer32         eoPower(2) 
          |   +-- r-n Integer32         eoPowerNamePlate(3) 
          |   +-- r-n UnitMultiplier    eoPowerUnitMultiplier(4) 
          |   +-- r-n Integer32         eoPowerAccuracy(5) 
          |   +-- r-n INTEGER           eoMeasurementCaliber(6) 
          |   +-- r-n INTEGER           eoPowerCurrentType(7) 
          |   +-- r-n INTEGER           eoPowerOrigin(8) 
          |   +-- rwn Integer32         eoPowerAdminState(9) 
          |   +-- r-n Integer32         eoPowerOperState(10) 
          |   +-- r-n OwnerString       eoPowerStateEnterReason(11) 
          |   | 
          |   | 
          +---eoPowerStateTable(2) 
          |      +--eoPowerStateEntry(1) 
          |      |     [eoPowerIndex,  
          |      |      eoPowerStateIndex]  
          |      | 
          |      +-- --- IANAPowerStateSet  eoPowerStateIndex(1) 
          |      +-- r-n Interger32         eoPowerStateMaxPower (2) 
          |      +-- r-n UnitMultiplier  
          |                  eoPowerStatePowerUnitMultiplier (3) 
          |      +-- r-n TimeTicks          eoPowerStateTotalTime(4) 
          |      +-- r-n Counter64          eoPowerStateEnterCount(5) 
          | 
      
          +eoEnergyParametersTable(1) 
          +---eoEnergyParametersEntry(1) [eoPowerIndex] 
          |    
          |   +-- r-n TimeInterval  
          |               eoEnergyParametersIntervalLength (1) 
          |   +-- r-n Integer32     
          |               eoEnergyParametersIntervalNumber (2) 
      
      
     <Claise, et. Al>        Expires April 31, 2012            [Page 6] 
         

     Internet-Draft <Power and Energy Monitoring MIB>   October 2011 
      
          |   +-- r-n Integer32     
          |               eoEnergyParametersIntervalMode (3) 
          |   +-- r-n TimeInterval  
          |               eoEnergyParametersIntervalWindow (4) 
          |   +-- r-n Integer32     
          |               eoEnergyParametersSampleRate (5) 
          |   +-- r-n RowStatus  eoEnergyParametersStatus (6) 
          |       
          +eoEnergyTable(1) 
          +---eoEnergyEntry(1) [eoPowerIndex] 
          |      
          |   +-- r-n TimeInterval  eoEnergyIntervalStartTime (1) 
          |   +-- r-n Integer32     eoEnergyIntervalEnergyConsumed (2) 
          |   +-- r-n Integer32     eoEnergyIntervalEnergyProduced (3)   
          |   +-- r-n Integer32     eoEnergyIntervalEnergyNet (4) 
          |   +-- r-n UnitMultiplier 
          |                eoEnergyIntervalEnergyUnitMultiplier (5) 
          |   +-- r-n Integer32     eoEnergyIntervalEnergyAccuracy(6) 
          |   +-- r-n Integer32     eoEnergyIntervalMaxConsumed (7) 
          |   +-- r-n Integer32     eoEnergyIntervalMaxProduced (8) 
          |   +-- r-n TimeTicks 
          |                   eoEnergyIntervalDiscontinuityTime(9) 
          |   +-- r-n RowStatus     eoEnergyParametersStatus (10) 
          
              
        The powerQualityMIB consists of four tables. eoACPwrQualityTable 
        is indexed by eoPowerIndex. eoACPwrQualityPhaseTable is indexed 
        by eoPowerIndex and eoPhaseIndex. eoACPwrQualityWyePhaseTable 
        and eoACPwrQualityDelPhaseTable are indexed by eoPowerIndex and 
        eoPhaseIndex. 
         
        eoPowerTable(1) 
          | 
          +---eoACPwrQualityEntry (1) [eoPowerIndex] 
          |   | 
          |   | 
          |   +----- INTEGER      eoACPwrQualityConfiguration (1) 
          |   +-- r-n Interger32  eoACPwrQualityAvgVoltage (2) 
          |   +-- r-n Integer32   eoACPwrQualityAvgCurrent (3) 
          |   +-- r-n Integer32   eoACPwrQualityFrequency  (4) 
          |   +-- r-n UnitMultiplier  
          |             eoACPwrQualityPowerUnitMultiplier (5) 
          |   +-- r-n Integer32   eoACPwrQualityPowerAccuracy (6) 
          |   +-- r-n Interger32  eoACPwrQualityTotalActivePower (7) 
          |   +-- r-n Integer32   
          |            eoACPwrQualityTotalReactivePower (8) 
          |   +-- r-n Integer32   eoACPwrQualityTotalApparentPower (9) 
          |   +-- r-n Integer32   eoACPwrQualityTotalPowerFactor(10) 
      
      
     <Claise, et. Al>        Expires April 31, 2012            [Page 7] 
         

     Internet-Draft <Power and Energy Monitoring MIB>   October 2011 
      
          |   +-- r-n Integer32   eoACPwrQualityThdAmpheres (11) 
          |      
          +eoACPwrQualityPhaseTable (1) 
          +---EoACPwrQualityPhaseEntry(1)[eoPowerIndex,  
          |     |                          eoPhaseIndex] 
          |     | 
          |     +-- r-n Integer32  eoPhaseIndex  (1) 
          |     +-- r-n Integer32   
          |     |          eoACPwrQualityPhaseAvgCurrent (2) 
          |     +-- r-n Integer32   
          |     |          eoACPwrQualityPhaseActivePower (3) 
          |     +-- r-n Integer32   
          |     |          eoACPwrQualityPhaseReactivePower (4) 
          |     +-- r-n Integer32   
          |     |          eoACPwrQualityPhaseApparentPower (5) 
          |     +-- r-n Integer32  
          |     |          eoACPwrQualityPhasePowerFactor (6) 
          |     +-- r-n Integer32   
          |     |          eoACPwrQualityPhaseImpedance (7) 
          |     | 
          +eoACPwrQualityDelPhaseTable (1) 
          +-- eoACPwrQualityDelPhaseEntry(1)  
          |     |                            [eoPowerIndex, 
          |     |                             eoPhaseIndex] 
          |     +-- r-n Integer32 
          |     |    eoACPwrQualityDelPhaseToNextPhaseVoltage (1) 
          |     +-- r-n Integer32  
          |     |    eoACPwrQualityDelThdPhaseToNextPhaseVoltage (2) 
          |     +-- r-n Integer32  eoACPwrQualityDelThdCurrent (3) 
          |     | 
          +eoACPwrQualityWyePhaseTable (1) 
          +-- eoACPwrQualityWyePhaseEntry (1)  
          |     |                              [eoPowerIndex,  
          |     |                               eoPhaseIndex] 
          |     +-- r-n Integer32  
          |     |    eoACPwrQualityWyePhaseToNeutralVoltage (1) 
          |     +-- r-n Integer32   
          |     |     eoACPwrQualityWyePhaseCurrent (2) 
          |     +-- r-n Integer32 
          |     |    eoACPwrQualityWyeThdPhaseToNeutralVoltage (3) 
          |     . 
                
           
                            
        A UML representation of the MIB objects in the two MIB modules 
        are energyObjectMib and powerQualityMIB are presented.  
         
         
      
      
     <Claise, et. Al>        Expires April 31, 2012            [Page 8] 
         

     Internet-Draft <Power and Energy Monitoring MIB>   October 2011 
      
         
         
         
         
         
         
         
         
                                                                         
        +--------------------------+                           
        |    Energy Object ID      |            
        |                          |                       
        |  Energy-aware-MIB  (*)   |
        |                          | +---------------------------+      
        |                          | |                           | 
        | eoPowerIndex             | |_ EnergyObject Attributes  | 
        |                          | |                           | 
        +--------------------------+ | eoPowerNamePlate          | 
                  |                | | eoPowerMeasurementCaliber |  
                  |                | | eoPowerOrigin             | 
                  |                | | eoPowerCurrentType        |    
                  |                | +---------------------------+      
                  |                |       | 
                  |                |       |  
                  v                |       v   
        +-----------------------------------------+ 
        |  EnergyObjec Measurement                | 
        |                                         | 
        | eoPower                                 | 
        | eoPowerUnitMultiplier                   | 
        | eoPowerAccuracy                         | 
        +-----------------------------------------+ 
                  ^                 |      ^  
                  |                 |      |                         
        +-------------------------+ |      |                          
        |    EnergyObject State   | |  +------------------------+   
        |                         | |  | EnergyObject   State   |   
        | eoPowerAdminState       | |  |    Statistics          | 
        | eoPowerOperState        | |  |                        | 
        | eoPowerStateEnterReason | |  | eoPowerStateMaxPower   |   
        +-------------------------+ |  | eoPowerStateTotalTime  |      
                                    |  | eoPowerStateEnterCount |    
                                    |  +------------------------+     
                                    | 
                                    | 
                                    | 
                                    | 
         
      
      
     <Claise, et. Al>        Expires April 31, 2012            [Page 9] 
         

     Internet-Draft <Power and Energy Monitoring MIB>   October 2011 
      
              Figure 1:UML diagram for powerMonitor MIB  
                               
             (*)   Link with the ENERGY-AWARE-MIB 
         
         
         
                                   | 
                                   |  
                                   | 
                                   V        
               +----------------------------------------+           
               |    Energy Table                        |                          
               |                                        |                          
               |  eoEnergyIntervalStartTime             |                        
               |  eoEnergyIntervalEnergyConsumed        | 
               |  eoEnergyIntervalEnergyProduced        | 
               |  eoEnergyIntervalEnergyNet             | 
               |  eoEnergyIntervalEnergyUnitMultiplier  | 
               |  eoEnergyIntervalEnergyAccuracy        |           
               |  eoEnergyIntervalMaxConsumed           | 
               |  eoEnergyIntervalMaxProduced           |    
               |  eoEnergyIntervalDiscontinuityTime     |    
               +----------------------------------------+         
                                                  
                        
         
         
                +--------------------------+                           
                |    EnergyObject ID       |            
                |                          |                       
                |  Energy-aware-MIB  (*)   |
                |                          |        
                | eoPowerIndex             |  
                |                          |          
                +--------------------------+ 
                               | 
                               v 
                   +-------------------------------------+  
                   |  Power Quality                      | 
                   |                                     |   
                   | eoACPwrQualityConfiguration         | 
                   | eoACPwrQualityAvgVoltage            | 
                   | eoACPwrQualityAvgCurrent 
                   | eoACPwrQualityFrequency             | 
                   | eoACPwrQualityPowerUnitMultiplier   | 
                   | eoACPwrQualityPowerAccuracy         | 
                   | eoACPwrQualityTotalActivePower      | 
                   | eoACPwrQualityTotalReactivePower    | 
      
      
     <Claise, et. Al>        Expires April 31, 2012           [Page 10] 
         

     Internet-Draft <Power and Energy Monitoring MIB>   October 2011 
      
                   | eoACPwrQualityTotalApparentPower    | 
                   | eoACPwrQualityTotalPowerFactor      |    
                   | eoACPwrQualityThdAmpheres           | 
                   +-------------------------------------+ ^       
                                    ^                   ^  |      
                                    |                   |  -------     
                                    |                   ----     |   
                                    |                       |    | 
                                    |                       |    | 
                  +-------------------------------------+   |    | 
                  |  Power Phase Quality                |   |    |  
                  |                                     |   |    | 
                  | eoPhaseIndex                        |   |    | 
                  | eoACPwrQualityPhaseAvgCurrent       |   |    | 
                  | eoACPwrQualityAvgCurrent            |   |    | 
                  | eoACPwrQualityFrequency             |   |    |  
                  | eoACPwrQualityPowerUnitMultiplier   |   |    |  
                  | eoACPwrQualityPowerAccuracy         |   |    | 
                  | eoACPwrQualityPhaseActivePower      |   |    | 
                  | eoACPwrQualityPhaseReactivePower    |   |    | 
                  | eoACPwrQualityPhaselApparentPower   |   |    | 
                  | eoACPwrQualityPhaseImpedance        |   |    | 
                  +-------------------------------------+   |    |   
                                                            |    | 
                                                            |    | 
                +---------------------------------------------+  | 
                |  Power Quality DEL Configuration            |  | 
                |                                             |  | 
                | eoACPwrQualityDelPhaseToNextPhaseVoltage    |  | 
                | eoACPwrQualityDelThdPhaseToNextPhaseVoltage |  | 
                | eoACPwrQualityDelThdCurrent                 |  | 
                +---------------------------------------------+  |   
                                                                 | 
                                                                 | 
                    +---------------------------------------------+  
                    |  Power Quality WYE Configuration            | 
                    |                                             |   
                    | eoACPwrQualityWyePhaseToNeutralVoltage      | 
                    | eoACPwrQualityWyePhaseCurrent               | 
                    | eoACPwrQualityWyeThdPhaseToNeutralVoltage   | 
                    +---------------------------------------------+   
         
                 Figure 2: UML diagram for the powerQualityMIB  
      
      

      
      
     <Claise, et. Al>        Expires April 31, 2012           [Page 11] 
         

     Internet-Draft <Power and Energy Monitoring MIB>   October 2011 
      
     5.1. Energy Object Information 

        Refer to the "Energy Object Information" section in [EMAN-
        FRAMEWORK] for background information.  An energy aware device 
        is considered as an instance of a Energy Object as defined in 
        the [EMAN-FRAMEWORK]. 
         
        The Energy Object identity information is specified in the MIB 
        ENERGY-AWARE-MIB module [EMAN-AWARE-MIB] primary table, i.e. the 
        eoTable. In this table, every Energy Object SHOULD have a 
        printable name eoName, and MUST HAVE a unique Energy Object 
        index eoIndex.  The ENERGY-AWARE-MIB module returns the 
        relationship (parent/child) between Energy Objects . 
         
        EDITOR'S NOTE: this last sentence will have to be updated with 
        terms such as Aggregator, Proxy, etc... when the [EMAN-
        FRAMEWORK] will stabilize. 
      

     5.2. Power State 

        Refer to the "Power States" section in [EMAN-FRAMEWORK] for 
        background information. 
         
        An Energy Object may have energy conservation modes called Power 
        States.  Between the ON and OFF states of a device, there can be 
        several intermediate energy saving modes.  Those energy saving 
        modes are called as Power States.  
         
        Power States, which represent universal states of power 
        management of  an Energy Object, are specified by the 
        eoPowerState MIB object.  The actual Power State is specified by 
        the eoPowerOperState MIB object, while the eoPowerAdminState MIB 
        object specifies the Power State requested for the Energy 
        Object.  The difference between the values of eoPowerOperState 
        and eoPowerAdminState  can be attributed that the Energy Object 
        is busy transitioning from eoPowerAdminState into the 
        eoPowerOperState, at which point it will update the content of 
        eoPowerOperState.  In addition, the possible reason for change 
        in Power State is reported in eoPowerStateEnterReason.  
        Regarding eoPowerStateEnterReason, management stations and 
        Energy Objects should support any format of the owner string 
        dictated by the local policy of the organization.  It is 
        suggested that this name contain at least the reason for the 
        transition change, and one or more of the following: IP address, 
        management station name, network manager's name, location, or 
        phone number. 
         
      
      
     <Claise, et. Al>        Expires April 31, 2012           [Page 12] 
         

     Internet-Draft <Power and Energy Monitoring MIB>   October 2011 
      
        The MIB objects eoPowerOperState, eoPowerAdminState , and 
        eoPowerStateEnterReason are contained in the eoPowerTable MIB 
        table. 
            
        The eoPowerStateTable table enumerates the maximum power usage 
        in watts, for every single supported Power State of each Power 
        State Set supported by the Energy Object. In addition, 
        PowerStateTable provides additional statistics: 
        eoPowerStateEnterCount, the number of times an entity has 
        visited a particular Power State, and eoPowerStateTotalTime, the 
        total time spent in a particular Power State of an Energy 
        Object.  
         
         
     5.2.1. Power State Set 

        There are several standards and implementations of Power State 
        Sets.  A Energy Object can support one or multiple Power State 
        Set implementation(s) concurrently.  
         
        There are currently three Power State Sets advocated:   
         
          unknown(0) 
          IEEE1621(256) - [IEEE1621] 
          DMTF(512)     - [DMTF] 
          EMAN(1024)     - [EMAN-MONITORING-MIB] 
        
       The respective specific states related to each Power State Set 
        are specified in the following sections. The guidelines for 
        addition of new Power State Sets have been specified in the IANA 
        Considerations Section.  
        
         
     5.2.2. IEEE1621 Power State Set 

        The IEEE1621 Power State Set [IEEE1621] consists of 3 
        rudimentary states : on, off or sleep. 
          on(0)    - The device is fully On and all features of the 
        device are in working mode.  
          off(1)   - The device is mechanically switched off and does 
        not consume energy.  
          sleep(2) - The device is in a power saving mode, and some 
        features may not be available immediately. 
         
        The Textual Convention IANAPowerStateSet provides the proposed 
        numbering of the Power States within the IEEE1621 Power State 
        Set.  
      
      
      
     <Claise, et. Al>        Expires April 31, 2012           [Page 13] 
         

     Internet-Draft <Power and Energy Monitoring MIB>   October 2011 
      
         
     5.2.3. DMTF Power State Set 

        DMTF [DMTF] standards organization has defined a power profile 
        standard based on the CIM (Common Information Model) model that 
        consists of 15 power states ON (2), SleepLight (3), SleepDeep 
        (4), Off-Hard (5), Off-Soft (6), Hibernate(7), PowerCycle Off-
        Soft (8), PowerCycle Off-Hard (9), MasterBus reset (10), 
        Diagnostic Interrupt (11), Off-Soft-Graceful (12), Off-Hard 
        Graceful (13), MasterBus reset Graceful (14), Power-Cycle Off-
        Soft Graceful (15), PowerCycle-Hard Graceful (16).  DMTF 
        standard is targeted for hosts and computers.  Details of the 
        semantics of each Power State within the DMTF Power State Set 
        can be obtained from the DMTF Power State Management Profile 
        specification [DMTF]. 
         
        DMTF power profile extends ACPI power states.  The following 
        table provides a mapping between DMTF and ACPI Power State Set: 
         
              --------------------------------------------------- 
              |  DMTF                             | ACPI        | 
              |  Power State                      | Power State | 
              --------------------------------------------------- 
              | Reserved(0)                       |             | 
              --------------------------------------------------- 
              | Reserved(1)                       |             | 
              --------------------------------------------------- 
              | ON (2)                            | G0-S0       | 
              -------------------------------------------------- 
              | Sleep-Light (3)                   | G1-S1 G1-S2 | 
              -------------------------------------------------- 
              | Sleep-Deep (4)                    | G1-S3       | 
              -------------------------------------------------- 
              | Power Cycle (Off-Soft) (5)        | G2-S5       | 
              --------------------------------------------------- 
              | Off-hard (6)                      | G3          | 
              --------------------------------------------------- 
              | Hibernate (Off-Soft) (7)          | G1-S4       | 
              --------------------------------------------------- 
              | Off-Soft (8)                      | G2-S5       | 
              --------------------------------------------------- 
              | Power Cycle (Off-Hard) (9)        | G3          | 
              --------------------------------------------------- 
              | Master Bus Reset (10)             | G2-S5       | 
              --------------------------------------------------- 
              | Diagnostic Interrupt (11)         | G2-S5       | 
              --------------------------------------------------- 
              | Off-Soft Graceful (12)            | G2-S5       | 
      
      
     <Claise, et. Al>        Expires April 31, 2012           [Page 14] 
         

     Internet-Draft <Power and Energy Monitoring MIB>   October 2011 
      
              --------------------------------------------------- 
              | Off-Hard Graceful (13)            | G3          | 
              --------------------------------------------------- 
              | MasterBus Reset Graceful (14)     | G2-S5       | 
              --------------------------------------------------- 
              | Power Cycle off-soft Graceful (15)| G2-S5       | 
              --------------------------------------------------- 
              | Power Cycle off-hard Graceful (16)| G3          | 
              --------------------------------------------------- 
           Figure 3: DMTF and ACPI Powe State Set Mapping 
            
         
        The Textual Convention IANAPowerStateSet contains the proposed 
        numbering of the Power States within the DMTF Power State Set. 
            
            
     5.2.4. EMAN Power State Set 

        The EMAN Power State Set represents an attempt for a uniform 
        standard approach to model the different levels of power 
        consumption of a device.  The EMAN Power States are an expansion 
        of the basic Power States as defined in IEEE1621 that also 
        incorporate the Power States defined in ACPI and DMTF.  
        Therefore, in addition to the non-operational states as defined 
        in ACPI and DMTF standards, several intermediate operational 
        states have been defined.  
         
        There are twelve Power States, that expand on IEEE1621 on,sleep 
        and off.  The expanded list of Power States are divided into six  
        operational states, and six non-operational states.  The lowest 
        non-operational state is 1 and the highest is 6.  Each non-
        operational state corresponds to an ACPI state [ACPI] 
        corresponding to Global and System states between G3 (hard-off) 
        and G1 (sleeping). For Each operational state represent a 
        performance state, and may be mapped to ACPI states P0 (maximum 
        performance power) through P5 (minimum performance and minimum 
        power).  
         
        An Energy Object may have fewer Power States than twelve and 
        would then map several policy states to the same power state. 
        Energy Object with more than twelve states, would choose which 
        twelve to represent as power policy states. 
         
        In each of the non-operational states (from mechoff(1) to 
        ready(6)), the Power State preceding it is expected to have a 
        lower power consumption and a longer delay in returning to an 
        operational state:  
      
      
     <Claise, et. Al>        Expires April 31, 2012           [Page 15] 
         

     Internet-Draft <Power and Energy Monitoring MIB>   October 2011 
      
         
        IEEE1621 Power(off): 
         
                 mechoff(1)  : An off state where no entity features are 
                               available.  The entity is unavailable. 
                               No energy is being consumed and the power 
                               connector can be removed.  This  
                               corresponds to ACPI state G3.      
                      
                 softoff(2)  : Similar to mechoff(1), but some  
                               components remain powered or receive 
                               trace power so that the entity  
                               can be awakened from its off state.  In  
                               softoff(2), no context is saved and the  
                               device typically requires a complete boot  
                               when awakened.  This corresponds to ACPI  
                               state G2. 
         
        IEEE1621 Power(sleep) 
         
                 hibernate(3): No entity features are available.  The 
                               entity may be awakened without requiring  
                               a complete boot, but the time for  
                               availability is longer than sleep(4). An  
                               example for state hibernate(3) is a save 
                               to-disk state where DRAM context is not  
                               maintained. Typically, energy consumption  
                               is zero or close to zero.  This  
                               corresponds to state G1, S4 in ACPI. 
         
                 sleep(4)    : No entity features are available, except  
                               for out-of-band management, for example   
                               wake-up mechanisms. The time for  
                               availability is longer than standby(5).  
                               An example for state sleep(4) is a save- 
                               to-RAM state, where DRAM context is  
                               maintained.  Typically, energy  
                               consumption is close to zero. This  
                               corresponds to state G1, S3 in ACPI. 
         
                 standby(5) : No entity features are available, except  
                              for out-of-band management, for example  
                              wake-up mechanisms. This mode is analogous   
                              to cold-standy.  The time for availability  
                              is longer than ready(6).  For example, the  
                              processor context is not maintained.  
                              Typically, energy consumption is close to  

      
      
     <Claise, et. Al>        Expires April 31, 2012           [Page 16] 
         

     Internet-Draft <Power and Energy Monitoring MIB>   October 2011 
      
                              zero. This corresponds to state G1, S2 in  
                              ACPI. 
         
                 ready(6)    : No entity features are available, except  
                               for out-of-band management, for example  
                               wake-up mechanisms. This mode is  
                               analogous to hot-standby.  The entity can  
                               be quickly transitioned into an  
                               operational state.  For example,  
                               processors are not executing, but  
                               processor context is maintained. This  
                               corresponds to state G1, S1 in ACPI. 
         
        IEEE1621 Power(on): 
         
                 lowMinus(7) : Indicates some entity features may not be     
                               available and the entity has selected  
                               measures/options to provide less than  
                               low(8) usage.  This corresponds to  
                               ACPI State G0. This includes operational  
                               states lowMinus(7) to full(12). 
         
                 low(8)      : Indicates some features may not be  
                               available and the entity has taken  
                               measures or selected options to provide 
                               less than mediumMinus(9) usage. 
         
                 mediumMinus(9): Indicates all entity features are  
                               available but the entity has taken  
                               measures or selected options to provide  
                               less than medium(10) usage. 
         
                 medium(10)  : Indicates all entity features are  
                               available but the entity has taken  
                               measures or selected options to provide   
                               less than highMinus(11) usage. 
         
                 highMinus(11): Indicates all entity features are  
                                available and power usage is less  
                                than high(12). 
         
                 high(12)    : Indicates all entity features are  
                               available and the entity is consuming the  
                               highest power. 
         
        The Textual Convention IANAPowerStateSet contains the proposed 
        numbering of the Power States within the EMAN Power State Set. 
         
      
      
     <Claise, et. Al>        Expires April 31, 2012           [Page 17] 
         

     Internet-Draft <Power and Energy Monitoring MIB>   October 2011 
      
         
      

     5.3. Energy Object Usage Information 

        Refer to the "Energy Object Usage Measurement" section in [EMAN-
        FRAMEWORK] for background information. 
         
        For an Energy Object, power usage is reported using eoPower.  
        The magnitude of measurement is based on the 
        eoPowerUnitMultiplier MIB variable, based on the UnitMultiplier 
        Textual Convention (TC). Power measurement magnitude should 
        conform to the IEC 62053-21 [IEC.62053-21] and IEC 62053-22 
        [IEC.62053-22]  definition of unit multiplier for the SI (System 
        International) units of measure.  Measured values are 
        represented in SI units obtained by BaseValue * 10 raised to the 
        power of the scale.   
           
        For example, if current power usage of an Energy Object is 3, it 
        could be 3 W, 3 mW, 3 KW, or 3 MW, depending on the value of 
        eoPowerUnitMultiplier.  Note that other measurements throughout 
        the two MIB modules in this document use the same mechanism, 
        including eoPowerStatePowerUnitMultiplier, 
        eoEnergyIntervalEnergyUnitMultiplier, and 
        eoACPwrQualityPowerUnitMultiplier. 
         
        In addition to knowing the usage and magnitude, it is useful to 
        know how a eoPower measurement was obtained.  An NMS can use 
        this to account for the accuracy and nature of the reading 
        between different implementations.  For this eoPowerOrigin 
        describes whether the measurements were made at the device 
        itself or from a remote source.  The eoPowerMeasurementCaliber 
        describes the method that was used to measure the power and can 
        distinguish actual or estimated values.  There may be devices in 
        the network, which may not be able to measure or report power 
        consumption. For those devices, the object 
        eoPowerMeasurementCaliber shall report that measurement 
        mechanism is "unavailable" and the eoPower measurement shall be 
        "0".  
         
        The nameplate power rating of an Energy Object is specified in 
        eoPowerNameplate MIB object. 
         
         
     5.4. Optional Power Usage Quality 

        Refer to the "Optional Power Usage Quality" section in [EMAN-
        FRAMEWORK] for background information. 
      
      
     <Claise, et. Al>        Expires April 31, 2012           [Page 18] 
         

     Internet-Draft <Power and Energy Monitoring MIB>   October 2011 
      
         
        The optional powerQualityMIB MIB module can be implemented to 
        further describe power usage quality measurement.  The 
        powerQualityMIB MIB module adheres closely to the IEC 61850 7-2 
        standard to describe AC measurements.   
         
        The powerQualityMIB MIB module contains a primary table, the 
        eoACPwrQualityTable table, that defines power quality 
        measurements for supported  eoPowerIndex entities, as a sparse 
        extension of the eoPowerTable (with eoPowerIndex as primary 
        index).  This eoACPwrQualityTable table contains such 
        information as the configuration (single phase, DEL 3 phases, 
        WYE 3 phases), voltage, frequency, power accuracy, total 
        active/reactive power/apparent power, amperage, and voltage.  
         
        In case of 3-phase power, the eoACPwrQualityPhaseTable 
        additional table is populated with power quality measurements 
        per phase (so double indexed by the eoPowerIndex and 
        eoPhaseIndex).  This table, which describes attributes common to 
        both WYE and DEL configurations, contains the average current, 
        active/reactive/apparent power, power factor, and impedance. 
         
        In case of 3-phase power with a DEL configuration, the 
        eoACPwrQualityDelPhaseTable table describes the phase-to-phase 
        power quality measurements, i.e., voltage and current. 
         
        In case of 3-phase power with a Wye configuration, the 
        eoACPwrQualityWyePhaseTable table describes the phase-to-neutral 
        power quality measurements, i.e., voltage and current. 
         
         
     5.5. Optional Energy Measurement 

        Refer to the "Optional Energy and demand Measurement" section in 
        [EMAN-FRAMEWORK] for the definition and terminology information. 
         
        It is relevant to measure energy when there are actual power 
        measurements from an Energy Object, and not when the power 
        measurement is assumed or predicted as specified in the 
        description clause of the object eoPowerMeasurementCaliber.    
         
        Two tables are introduced to characterize energy measurement of 
        an  Energy Object:  eoEnergyTable and eoEnergyParametersTable.  
        Both energy and demand information can be represented via the 
        eoEnergyTable.  Energy information will be an accumulation with 
        no interval.  Demand information can be represented as an 
        average accumulation per interval of time.  
         
      
      
     <Claise, et. Al>        Expires April 31, 2012           [Page 19] 
         

     Internet-Draft <Power and Energy Monitoring MIB>   October 2011 
      
        The eoEnergyParametersTable consists of the parameters defining 
        the duration of measurement intervals in seconds, 
        (eoEnergyParametersIntervalLength), the number of successive 
        intervals to be stored in the eoEnergyTable, 
        (eoEnergyParametersIntervalNumber), the type of measurement 
        technique (eoEnergyParametersIntervalMode), and a sample rate 
        used to calculate the average (eoEnergyParametersSampleRate).  
        Judicious choice of the sampling rate will ensure accurate 
        measurement of energy while not imposing an excessive polling 
        burden. 
           
        There are three eoEnergyParametersIntervalMode types used for 
        energy measurement collection: period, sliding, and total. The 
        choices of the the three different modes of collection are based 
        on IEC standard 61850-7-4.  Note that multiple 
        eoEnergyParametersIntervalMode types MAY be configured 
        simultaneously.   
         
        These three eoEnergyParametersIntervalMode types are illustrated 
        by the following three figures, for which: 
         
        - The horizontal axis represents the current time, with the 
        symbol <--- L ---> expressing the 
        eoEnergyParametersIntervalLength, and the 
        eoEnergyIntervalStartTime is represented by S1, S2, S3, S4, ..., 
        Sx where x is the value of eoEnergyParametersIntervalNumber. 
         
        - The vertical axis represents the time interval of sampling and 
        the value of eoEnergyIntervalEnergyUsed can be obtained at the 
        end of the sampling period.  The symbol =========== denotes the 
        duration of the sampling period.  
         
         
         
              |             |             | =========== |     
              |============ |             |             |   
              |             |             |             | 
              |             |============ |             | 
              |             |             |             | 
              | <--- L ---> | <--- L ---> | <--- L ---> | 
              |             |             |             | 
             S1            S2            S3             S4 
         
                Figure 4 : Period eoEnergyParametersIntervalMode 
         
        A eoEnergyParametersIntervalMode type of 'period' specifies non-
        overlapping periodic measurements.  Therefore, the next 
        eoEnergyIntervalStartTime is equal to the previous 
      
      
     <Claise, et. Al>        Expires April 31, 2012           [Page 20] 
         

     Internet-Draft <Power and Energy Monitoring MIB>   October 2011 
      
        eoEnergyIntervalStartTime plus eoEnergyParametersIntervalLength. 
        S2=S1+L; S3=S2+L, ... 
         
         
                       |============ |            
                       |             |           
                       | <--- L ---> |        
                       |             |         
                       |   |============ |      
                       |   |             | 
                       |   | <--- L ---> |     
                       |   |             |           
                       |   |   |============ |  
                       |   |   |             |              
                       |   |   | <--- L ---> |  
                       |   |   |             |      
                       |   |   |   |============ |  
                       |   |   |   |             |    
                       |   |   |   | <--- L ---> | 
                      S1   |   |   |             | 
                           |   |   |             | 
                           |   |   |             | 
                          S2   |   |             | 
                               |   |             | 
                               |   |             | 
                              S3   |             | 
                                   |             | 
                                   |             | 
                                  S4 
         
               Figure 5 : Sliding eoEnergyParametersIntervalMode 
         
        A eoEnergyParametersIntervalMode type of 'sliding' specifies 
        overlapping periodic measurements. 
         
         
        |                          | 
        |========================= | 
        |                          | 
        |                          | 
        |                          | 
        |  <--- Total length --->  | 
        |                          | 
                         S1             
         
                Figure 4 : Total eoEnergyParametersIntervalMode 
         

      
      
     <Claise, et. Al>        Expires April 31, 2012           [Page 21] 
         

     Internet-Draft <Power and Energy Monitoring MIB>   October 2011 
      
        A eoEnergyParametersIntervalMode type of 'total' specifies a 
        continuous measurement since the last reset.  The value of 
        eoEnergyParametersIntervalNumber should be (1) one and 
        eoEnergyParametersIntervalLength is ignored. 
         
        The eoEnergyParametersStatus is used to start and stop energy 
        usage logging.  The status of this variable is "active"  when 
        all the objects in eoEnergyParametersTable are appropriate which 
        in turn indicates if eoEnergyTable entries exist or not. 
         
        The eoEnergyTable consists of energy measurements in 
        eoEnergyIntervalEnergyUsed , the units of the measured energy 
        eoEnergyIntervalEnergyUnitMultiplier, and the maximum observed 
        energy within a window - eoEnergyIntervalMax.    
         
        Measurements of the total energy consumed by an Energy Object 
        may suffer from interruptions in the continuous measurement of 
        energy consumption.  In order to indicate such interruptions, 
        the object eoEnergyIntervalDiscontinuityTime is provided for 
        indicating the time of the last interruption of total energy 
        measurement.  eoEnergyIntervalDiscontinuityTime shall indicate 
        the sysUpTime [RFC3418] when the device was reset.  
         
        The following example illustrates the eoEnergyTable and 
        eoEnergyParametersTable: 
         
        First, in order to estimate energy, a time interval to sample 
        energy should be specified, i.e. 
        eoEnergyParametersIntervalLength can be set to "900 seconds" or 
        15 minutes and the number of consecutive intervals over which 
        the maximum energy is calculated 
        (eoEnergyParametersIntervalNumber) as "10".  The sampling rate 
        internal to the Energy Object for measurement of power usage 
        (eoEnergyParametersSampleRate) can be "1000 milliseconds", as 
        set by the Energy Object as a reasonable value.  Then, the 
        eoEnergyParametersStatus is set to active (value 1) to indicate 
        that the Energy Object should start monitoring the usage per the 
        eoEnergyTable. 
         
        The indices for  the eoEnergyTable are eoPowerIndex, which 
        identifies the  Energy Object, and eoEnergyIntervalStartTime, 
        which denotes the start time of the energy measurement interval 
        based on sysUpTime [RFC3418].  The value of 
        eoEnergyIntervalEnergyUsed is the measured energy consumption 
        over the time interval specified 
        (eoEnergyParametersIntervalLength) based on the Energy Object 
        internal sampling rate (eoEnergyParametersSampleRate).  While 
        choosing the values for the eoEnergyParametersIntervalLength and 
      
      
     <Claise, et. Al>        Expires April 31, 2012           [Page 22] 
         

     Internet-Draft <Power and Energy Monitoring MIB>   October 2011 
      
        eoEnergyParametersSampleRate, it is recommended to take into 
        consideration either the network element resources adequate to 
        process and store the sample values, and the mechanism used to 
        calculate the eoEnergyIntervalEnergyUsed.  The units are derived 
        from eoEnergyIntervalPowerUnitMultiplier.  For example, 
        eoEnergyIntervalPowerUsed can be "100" with 
        eoEnergyIntervalPowerUnits equal to 0, the measured energy 
        consumption of the Energy Object is 100 watt-hours.  The 
        eoEnergyIntervalMax is the maximum energy observed and that can 
        be "150 watt-hours". 
         
        The eoEnergyTable has a buffer to retain a certain number of 
        intervals, as defined by eoEnergyParametersIntervalNumber.  If 
        the default value of "10" is kept, then the eoEnergyTable 
        contains 10 energy measurements, including the maximum.   
         
        Here is a brief explanation of how the maximum energy can be 
        calculated.  The first observed energy measurement value is 
        taken to be the initial maximum.  With each subsequent 
        measurement, based on numerical comparison, maximum energy may 
        be updated.  The maximum value is retained as long as the 
        measurements are taking place.  Based on periodic polling of 
        this table, an NMS could compute the maximum over a longer 
        period, i.e. a month, 3 months, or a year. 
      

     5.6. Fault Management 

        [EMAN-REQ] specifies requirements about Power States such as 
        "the current power state" , "the time of the last state change", 
        "the total time spent in each state", "the number of transitions 
        to each state" etc. Some of these requirements are fulfilled 
        explicitly by MIB objects such as eoPowerOperState, 
        eoPowerStateTotalTime and eoPowerStateEnterCount.  Some of the 
        other requirements are met via the SNMP NOTIFICATION mechanism.  
        eoPowerStateChange SNMP notification which is generated when the 
        value(s) of ,eoPowerStateIndex, eoPowerOperState, 
        eoPowerAdminState have changed.  
         
          
     6. Discovery 

     6.1. ENERGY-AWARE-MIB Module Implemented 

        The NMS must first poll the ENERGY-AWARE-MIB module [EMAN-AWARE-
        MIB], if available, in order to discover all the Energy Objects 
        and the relationships between those (notion of Parent/Child).  

      
      
     <Claise, et. Al>        Expires April 31, 2012           [Page 23] 
         

     Internet-Draft <Power and Energy Monitoring MIB>   October 2011 
      
        In the ENERGY-AWARE-MIB module tables, the Energy Objects are 
        indexed by the eoIndex.   

        If an implementation of the ENERGY-AWARE-MIB module is available 
        in the local SNMP context, for the same Energy Object , the 
        eoIndex value (EMAN-AWARE-MIB) MUST be assigned to the 
        eoPowerIndex. The eoPowerIndex characterizes the  Energy Object 
        in the energyObjectMib and powerQualityMIB MIB modules (this 
        document). 

        From there, the NMS must poll the eoPowerStateTable (specified 
        in the energyObjectMib module in this document), which 
        enumerates, amongst other things, the maximum power usage.  As 
        the entries in eoPowerStateTable table are indexed by the  
        Energy Object (eoPowerIndex), by the Power State Set 
        (eoPowerStateIndex), the maximum power usage is discovered per  
        Energy Object, per Power State Set, and per Power Usage.  In 
        other words, polling the eoPowerStateTable allows the discovery 
        of each Power State within every Power State Set supported by 
        the  Energy Object.               

        If the  Energy Object is an Aggregator or a Proxy, the MIB 
        module would be populated with the  Energy Object Parent and 
        Children information, which have their own  Energy Object index 
        value (eoPowerIndex).  However, the parent/child relationship 
        must be discovered thanks to the ENERGY-AWARE-MIB module. 

        Finally, the NMS can monitor the Power Quality thanks to the 
        powerQualityMIB MIB module, which reuses the eoPowerIndex to 
        index the  Energy Object. 

     6.2. ENERGY-AWARE-MIB Module Not Implemented, ENTITY-MIB 
        Implemented 

        When the ENERGY-AWARE-MIB module [EMAN-AWARE-MIB] is not 
        implemented, the NMS must poll the ENTITY-MIB [RFC4133] in order 
        to discover some more information about the Energy Objects.  
        Indeed, the index for the Energy Objects in the MIB modules 
        specified in this document is the eoPowerIndex, which specifies: 
        "If there is no implementation of the ENERGY-AWARE-MIB module 
        but one of the ENTITY MIB module is available in the local SNMP 
        context, then the same index of an entity MUST be chosen as 
        assigned to the entity by object entPhysicalIndex in the ENTITY 
        MIB module." 
      
        As described in Section 6.1.  the NMS must then poll the 
        eoPowerStateTable (specified in the energyObjectMib module in 
        this document), indexed by the Energy Object (eoPowerIndex that 
      
      
     <Claise, et. Al>        Expires April 31, 2012           [Page 24] 
         

     Internet-Draft <Power and Energy Monitoring MIB>   October 2011 
      
        inherited the entPhysicalIndex value),  by the Power State 
        (eoPowerStateIndex).  Then the NMS has discovered every Power 
        State within each Power State Set supported by the Energy 
        Object.  
         
        Note that, without the ENERGY-AWARE-MIB module, the Energy 
        Object acts as an standalone device, i.e. the notion of 
        parent/child can't be specified. 
                      
      

     6.3. ENERGY-AWARE-MIB Module and ENTITY-MIB Not Implemented 

        If neither the ENERGY-AWARE-MIB module [EMAN-AWARE-MIB] nor of 
        the ENTITY MIB module [RFC4133] are available in the local SNMP 
        context, then this MIB module may choose identity values from a 
        further MIB module providing entity identities.  
         
        Note that, without the ENERGY-AWARE-MIB module, the Energy 
        Object acts as a standalone device, i.e. the notion of 
        parent/child can't be specified. 
      
                                      
     7. Link with the other IETF MIBs 

         
     7.1. Link with the ENTITY MIB and the ENTITY-SENSOR MIB  

        RFC 4133 [RFC4133] defines the ENTITY MIB module that lists the 
        physical entities of a networking device (router, switch, etc.) 
        and those physical entities indexed by entPhysicalIndex.  From 
        an energy-management standpoint, the physical entities that 
        consume or produce energy are of interest. 
         
        RFC 3433 [RFC3433] defines the ENTITY-SENSOR MIB module that 
        provides a standardized way of obtaining information (current 
        value of the sensor, operational status of the sensor, and the 
        data units precision) from sensors embedded in networking 
        devices.  Sensors are associated with each index of 
        entPhysicalIndex of the ENTITY MIB [RFC4133].  While the focus 
        of the Power and Energy Monitoring MIB is on measurement of 
        power usage of networking equieoent indexed by the ENTITY MIB, 
        this MIB proposes a customized power scale for power measurement 
        and different power state states of networking equipment, and 
        functionality to configure the power state states. 
         
        When this MIB module is used to monitor the power usage of 
        devices like routers and switches, the ENTITY MIB and ENTITY-
      
      
     <Claise, et. Al>        Expires April 31, 2012           [Page 25] 
         

     Internet-Draft <Power and Energy Monitoring MIB>   October 2011 
      
        SENSOR MIB SHOULD be implemented.  In such cases, the Energy 
        Objects are modeled by the entPhysicalIndex through the 
        entPhysicalEntity MIB object specified in the eoTable in the 
        ENERGY-AWARE-MIB MIB module [EMAN-AWARE-MIB].   

        However, the ENTITY-SENSOR MIB [RFC3433] does not have the ANSI 
        C12.x accuracy classes required for electricity (i.e., 1%, 2%, 
        0.5% accuracy classes). Indeed, entPhySensorPrecision [RFC3433] 
        represents "The number of decimal places of precision in fixed-
        point sensor values returned by the associated entPhySensorValue 
        object".  The ANSI and IEC Standards are used for power 
        measurement and these standards require that we use an accuracy 
        class, not the scientific-number precision model specified in 
        RFC3433.  The eoPowerAccuracy MIB object models this accuracy.  
        Note that eoPowerUnitMultipler represents the scale factor per 
        IEC 62053-21 [IEC.62053-21] and IEC 62053-22 [IEC.62053-22], 
        which is a more logical representation for power measurements 
        (compared to entPhySensorScale), with the mantissa and the 
        exponent values X * 10 ^ Y. 

        Power measurements specifying the qualifier 'UNITS' for each 
        measured value in watts are used in the LLDP-EXT-MED-MIB, POE 
        [RFC3621], and UPS [RFC1628] MIBs.  The same 'UNITS' qualifier 
        is used for the power measurement values.    
         
        One cannot assume that the ENTITY MIB and ENTITY-SENSOR MIB are 
        implemented for all Energy Objects that need to be monitored.  A 
        typical example is a converged building gateway, monitoring 
        several other devices in the building, doing the proxy between 
        SNMP and a protocol like BACNET.  Another example is the home 
        energy controller.  In such cases, the eoPhysicalEntity value 
        contains the zero value, thanks to PhysicalIndexOrZero textual 
        convention. 
         
        The eoPowerIndex MIB object has been kept as the unique index of 
        the Energy Object. The eoPower is similar to entPhySensorValue 
        [RFC3433] and the eoPowerUnitMultipler is similar to 
        entPhySensorScale. 
         
         
     7.2. Link with the ENTITY-STATE MIB  

        For each entity in the ENTITY-MIB [RFC4133], the ENTITY-STATE 
        MIB [RFC4268] specifies the operational states (entStateOper: 
        unknown, enabled, disabled, testing), the alarm (entStateAlarm: 
        unknown, underRepair, critical, major, minor, warning, 
        indeterminate) and the possible values of standby states  

      
      
     <Claise, et. Al>        Expires April 31, 2012           [Page 26] 
         

     Internet-Draft <Power and Energy Monitoring MIB>   October 2011 
      
        (entStateStandby: unknown, hotStandby, coldStandby, 
        providingService). 
         
        From a power monitoring point of view, in contrast to the entity 
        operational states of entities, Power States are required, as 
        proposed in the Power and Energy Monitoring MIB module.  Those 
        Power States can be mapped to the different operational states 
        in the ENTITY-STATE MIB, if a formal mapping is required.  For 
        example, the entStateStandby "unknown", "hotStandby", 
        "coldStandby", states could map to the Power State "unknown", 
        "ready", "standby", respectively, while the entStateStandby 
        "providingService" could map to any "low" to "high" Power State. 
         
         
     7.3. Link with the POWER-OVER-ETHERNET MIB 

        Power-over-Ethernet MIB [RFC3621] provides an energy monitoring 
        and configuration framework for power over Ethernet devices.  
        The RFC introduces a concept of a port group on a switch to 
        define power monitoring and management policy and does not use 
        the entPhysicalIndex as the index.  Indeed, the  
        pethMainPseConsumptionPower is indexed by the 
        pethMainPseGroupIndex, which has no mapping with the 
        entPhysicalIndex.  
         
        One cannot assume that the Power-over-Ethernet MIB is 
        implemented for all Energy Objects that need to be monitored.  A 
        typical example is a converged building gateway, monitoring 
        several other devices in the building, doing the proxy between 
        SNMP and a protocol like BACNET.  Another example is the home 
        energy controller.  In such cases, the eoethPortIndex and 
        eoethPortGrpIndex values contain the zero value, thanks to new 
        PethPsePortIndexOrZero and textual PethPsePortGroupIndexOrZero 
        conventions. 
         
        However, if the Power-over-Ethernet MIB [RFC3621] is supported, 
        the Energy Object eoethPortIndex and eoethPortGrpIndex contain 
        the pethPsePortIndex and pethPsePortGroupIndex, respectively. 
         
        As a consequence, the eoIndex MIB object has been kept as the 
        unique Energy Object index. 
         
        Note that, even though the Power-over-Ethernet MIB [RFC3621] was 
        created after the ENTITY-SENSOR MIB [RFC3433], it does not reuse 
        the precision notion from the ENTITY-SENSOR MIB, i.e. the 
        entPhySensorPrecision MIB object. 
         
          
      
      
     <Claise, et. Al>        Expires April 31, 2012           [Page 27] 
         

     Internet-Draft <Power and Energy Monitoring MIB>   October 2011 
      
     7.4. Link with the UPS MIB 

        To protect against unexpected power disruption, data centers and 
        buildings make use of Uninterruptible Power Supplies (UPS).  To 
        protect critical assets, a UPS can be restricted to a particular 
        subset or domain of the network.  UPS usage typically lasts only 
        for a finite period of time, until normal power supply is 
        restored.  Planning is required to decide on the capacity of the 
        UPS based on output power and duration of probable power outage.  
        To properly provision UPS power in a data center or building, it 
        is important to first understand the total demand required to 
        support all the entities in the site.  This demand can be 
        assessed and monitored via the Power and Energy Monitoring MIB.  

        UPS MIB [RFC1628] provides information on the state of the UPS 
        network.  Implementation of the UPS MIB is useful at the 
        aggregate level of a data center or a building.  The MIB module 
        contains several groups of variables: 

        - upsIdent: Identifies the UPS entity (name, model, etc.).  

        - upsBattery group: Indicates the battery state 
        (upsbatteryStatus, upsEstimatedMinutesRemaining, etc.) 

        - upsInput group: Characterizes the input load to the UPS 
        (number of input lines, voltage, current, etc.). 

        - upsOutput: Characterizes the output from the UPS (number of 
        output lines, voltage, current, etc.) 

        - upsAlarms: Indicates the various alarm events.   

        The measurement of power in the UPS MIB is in Volts, Amperes and 
        Watts.  The units of power measurement are RMS volts and RMS 
        Amperes. They are not based on the EntitySensorDataScale and 
        EntitySensorDataPrecision of Entity-Sensor MIB. 

        Both the Power and Energy Monitoring MIB and the UPS MIB may be 
        implemented on the same UPS SNMP agent, without conflict.  In 
        this case, the UPS device itself is the Energy Object Parent and 
        any of the UPS meters or submeters are the Energy Object 
        Children. 
         
         

      
      
     <Claise, et. Al>        Expires April 31, 2012           [Page 28] 
         

     Internet-Draft <Power and Energy Monitoring MIB>   October 2011 
      
     7.5. Link with the LLDP and LLDP-MED MIBs 

        The LLDP Protocol is a Data Link Layer protocol used by network 
        devices to advertise their identities, capabilities, and 
        interconnections on a LAN network.  
         
        The Media Endpoint Discovery is an enhancement of LLDP, known as 
        LLDP-MED.  The LLDP-MED enhancements specifically address voice 
        applications.  LLDP-MED covers 6 basic areas: capability 
        discovery, LAN speed and duplex discovery, network policy 
        discovery, location identification discovery, inventory 
        discovery, and power discovery.   
         
        Of particular interest to the current MIB module is the power 
        discovery, which allows the endpoint device (such as a PoE 
        phone) to convey power requirements to the switch.  In power 
        discovery, LLDP-MED has four Type Length Values (TLVs): power 
        type, power source, power priority and power value.  
        Respectively, those TLVs provide information related to the type 
        of power (power sourcing entity versus powered device), how the 
        device is powered (from the line, from a backup source, from 
        external power source, etc.), the power priority (how important 
        is it that this device has power?), and how much power the 
        device needs. 
          
        The power priority specified in the LLDP-MED MIB [LLDP-MED-MIB] 
        actually comes from the Power-over-Ethernet MIB [RFC3621]. If 
        the Power-over-Ethernet MIB [RFC3621] is supported, the exact 
        value from the pethPsePortPowerPriority [RFC3621] is copied over 
        in the lldpXMedRemXPoEPDPowerPriority [LLDP-MED-MIB]; otherwise 
        the value in lldpXMedRemXPoEPDPowerPriority is "unknown". From 
        the Power and Energy Monitoring MIB, it is possible to identify 
        the pethPsePortPowerPriority [RFC3621], thanks to the 
        eoethPortIndex and eoethPortGrpIndex. 
         
        The lldpXMedLocXPoEPDPowerSource [LLDP-MED-MIB] is similar to 
        eoPowerOrigin in indicating if the power for an attached device 
        is local or from a remote device. If the LLDP-MED MIB is 
        supported, the following mapping can be applied to the 
        eoPowerOrigin: lldpXMedLocXPoEPDPowerSource fromPSE(2) and 
        local(3) can be mapped to remote(2) and self(1), respectively. 
      

     8. Implementation Scenario 

         

      
      
     <Claise, et. Al>        Expires April 31, 2012           [Page 29] 
         

     Internet-Draft <Power and Energy Monitoring MIB>   October 2011 
      
        This section provides an illustrative example scenario for the 
        implementation of the Energy Object, including Energy Object 
        Parent and Energy Object Child relationships.  
         
        Example Scenario of a campus network: Switch with PoE Endpoints 
        with further connected Devices  
         
        The campus network consists of switches that provide LAN 
        connectivity.  The switch with PoE ports is located in wiring 
        closet.  PoE IP phones are connected to the switch.  The IP 
        phones draw power from the PoE ports of the switch.  In 
        addition, a PC is daisy-chained from the IP phone for LAN 
        connectivity.   
         
        The IP phone consumes power from the PoE switch, while the PC 
        consumes power from the wall outlet.  
         
        The switch has implementations of Entity MIB [RFC4133] and 
        energy-aware MIB [EMAN-AWARE-MIB] while the PC does not have 
        implementation of the Entity MIB, but has an implementation of 
        energy-aware MIB.  The switch has the following attributes, 
        eoPowerIndex "1", eoPhysicalEntity "2", and eoUUID "UUID 1000".  
        The power usage of the switch is "440 Watts".  The switch does 
        not have an Energy Object Parent. 
         
        The PoE switch port has the following attributes: The switch 
        port has eoPowerIndex "3", eoPhysicalEntity is "12" and eoUUID 
        is "UUID 1000:3".  The power metered at the POE switch port is 
        "12 watts".  In this example, the POE switch port has the switch 
        as the Energy Object Parent, with its eoParentID of "1000". 
      
        The attributes of the PC are given below.  The PC does not 
        implementation of Entity MIB, and thus does not have 
        eoPhysicalEntity.  The eoPowerIndex (eoIndex) of the PC is "57", 
        the eoUUID is "UUID 1000:57 ".  The PC has an Energy Object 
        Parent, i.e. the switch port whose eoUUID is "UUID 1000:3".  The 
        power usage of the PC is "120 Watts" and is communicated to the 
        switch port.  
         
        This example illustrates the important distinction between the 
        Energy Object Children: The IP phone draws power from the 
        switch, while the PC has LAN connectivity from the phone, but is 
        powered from the wall outlet.  However, the Energy Object Parent 
        sends power control messages to both the Energy Object Children 
        (IP phone and PC) and the Children react to those messages. 
         
         

      
      
     <Claise, et. Al>        Expires April 31, 2012           [Page 30] 
         

     Internet-Draft <Power and Energy Monitoring MIB>   October 2011 
      
        |--------------------------------------------------------------| 
        |                            Switch                            | 
        |==============================================================| 
        |  Switch  | Switch   | Switch       | Switch     | Switch     | 
        | eoIndex | eoPhyIdx  | eoUUID        |eoParentId  | eoPower   | 
        | ============================================================ | 
        |     1    |    2     | UUID 1000    |    null    |   440      | 
        | ============================================================ | 
        |                                                              | 
        |                           SWITCH PORT                        | 
        | ============================================================ | 
        | | Switch  | Switch   | Switch       | Switch     | Switch    | 
        | | Port    | Port     | Port         | Port       | Port    | | 
        | | eoIndex| eoPhyIdx | eoUUID        | eoParentId | eoPower | | 
        | ============================================================ | 
        | |    3    |    12    | UUID 1000:3  | UUID 1000  |    12   | | 
        | ============================================================ | 
        |                                   ^                          | 
        |                                   |                          | 
        |-----------------------------------|--------------------------| 
                                            | 
                                            | 
                          POE IP PHONE      | 
                                            | 
                                            | 
        ============================================================= 
        | IP phone | IP phone |IP phone     | IP phone   |IP phone|    
        | eoIndex  | eoPhyIdx |eoUUID       |eoParentID  |eoPower | 
        ===========================================================          
        |  31       |     0   |UUID 1000:31 | UUID 1000:3 |  12   | 
        ============================================================ 
                                             | 
                                             | 
        PC connected to switch via IP phone  | 
                                             | 
        ============================================================= 
        | PC     | PC      |PC           |PC          | PC         | 
        |eoIndex| eoPhyIdx |eoUUID       |eoParentID  | eoPower    | 
        ============================================================ 
        | 57      |    0   | UUID 1000:57| UUID 1000:3| 120        |   
        ============================================================= 
                               

                               Figure 1:  Example scenario  

         
      

      
      
     <Claise, et. Al>        Expires April 31, 2012           [Page 31] 
         

     Internet-Draft <Power and Energy Monitoring MIB>   October 2011 
      
     9. Structure of the MIB 

        The primary MIB object in this MIB module is the 
        energyObjectMibObject.  The eoPowerTable table of 
        energyObjectMibObject describes the power measurement attributes 
        of an Energy Object entity. The notion of identity of the device 
        in terms of uniquely identification of the Energy Object and its 
        relationship to other entities in the network are addressed in 
        [EMAN-AWARE-MIB].   
          
         
        The power measurement of an Energy Object contains information 
        describing its power usage (eoPower) and its current power state 
        (eoPowerOperState). In addition to power usage, additional 
        information describing the units of measurement 
        (eoPowerAccuracy, eoPowerUnitMultiplier), how power usage 
        measurement was obtained  (eoPowerMeasurementCaliber),  the 
        source of power  (eoPowerOrigin) and the type of power 
        (eoPowerCurrentTtype) are described. 
         
         
        An Energy Object may contain an optional eoPowerQuality table 
        that describes the electrical characteristics associated with 
        the current power state and usage. 
         
        An Energy Object may contain an optional eoEnergyTable to 
        describe energy measurement information over time. 
         
        An Energy Object may also contain optional battery information 
        associated with this entity.  
         
         
     10. MIB Definitions 

         
        -- ************************************************************ 
        --  
        --    
        -- This MIB is used to monitor power usage of network 
        -- devices 
        --    
        -- ************************************************************* 
         
        ENERGY-OBJECT-MIB DEFINITIONS ::= BEGIN 
         
        IMPORTS 
            MODULE-IDENTITY, 
            OBJECT-TYPE, 
      
      
     <Claise, et. Al>        Expires April 31, 2012           [Page 32] 
         

     Internet-Draft <Power and Energy Monitoring MIB>   October 2011 
      
            NOTIFICATION-TYPE, 
            mib-2, 
            Integer32, Counter64, TimeTicks    
                FROM SNMPv2-SMI 
            TEXTUAL-CONVENTION, DisplayString, RowStatus, TimeInterval            
                FROM SNMPv2-TC     
            MODULE-COMPLIANCE, NOTIFICATION-GROUP, OBJECT-GROUP 
                FROM SNMPv2-CONF 
            OwnerString 
                FROM RMON-MIB;    
         
        energyObjectMib MODULE-IDENTITY 
            LAST-UPDATED    "201110310000Z"     -- 31 October 2011 
         
            ORGANIZATION    "IETF EMAN Working Group" 
            CONTACT-INFO 
                    "WG charter: 
                    http://datatracker.ietf.org/wg/eman/charter/ 
         
                  Mailing Lists: 
                     General Discussion: eman@ietf.org 

                     To Subscribe:  
                     https://www.ietf.org/mailman/listinfo/eman 

                     Archive:  
                     http://www.ietf.org/mail-archive/web/eman 

                  Editors: 
                     Mouli Chandramouli 
                     Cisco Systems, Inc. 
                     Sarjapur Outer Ring Road 
                     Bangalore, 
                     IN 
                     Phone: +91 80 4426 3947 
                     Email: moulchan@cisco.com 

                     Brad Schoening 
                     44 Rivers Edge Drive 
                     Little Silver, NJ 07739 
                     US 
                     Email: brad@bradschoening.com 

                     Juergen Quittek 
                     NEC Europe Ltd. 
                     NEC Laboratories Europe 
                     Network Research Division 
                     Kurfuersten-Anlage 36 
      
      
     <Claise, et. Al>        Expires April 31, 2012           [Page 33] 
         

     Internet-Draft <Power and Energy Monitoring MIB>   October 2011 
      
                     Heidelberg  69115 
                     DE 
                     Phone: +49 6221 4342-115 
                     Email: quittek@neclab.eu 

                     Thomas Dietz 
                     NEC Europe Ltd. 
                     NEC Laboratories Europe 
                     Network Research Division 
                     Kurfuersten-Anlage 36 
                     69115 Heidelberg 
                     DE 
                     Phone: +49 6221 4342-128 
                     Email: Thomas.Dietz@nw.neclab.eu 

                     Benoit Claise 
                     Cisco Systems, Inc. 
                     De Kleetlaan 6a b1 
                     Degem 1831 
                     Belgium 
                     Phone:  +32 2 704 5622 
                     Email: bclaise@cisco.com" 

            DESCRIPTION 
               "This MIB is used to monitor power and energy in  
               devices." 
            REVISION 
                "201110310000Z"     -- 31 October 2011 
         
            DESCRIPTION 
               "Initial version, published as RFC XXXX." 
         
           ::= { mib-2 xxx } 
         
         
        energyObjectMibNotifs OBJECT IDENTIFIER 
            ::= { energyObjectMib 0 } 
         
        energyObjectMibObjects OBJECT IDENTIFIER 
            ::= { energyObjectMib 1 } 
      
        energyObjectMibConform  OBJECT IDENTIFIER 
            ::= { energyObjectMib 2 } 
         
                                    
        -- Textual Conventions 
         
         
      
      
     <Claise, et. Al>        Expires April 31, 2012           [Page 34] 
         

     Internet-Draft <Power and Energy Monitoring MIB>   October 2011 
      
      
         
         
                 
        IANAPowerStateSet ::= TEXTUAL-CONVENTION  
            STATUS  current  
            DESCRIPTION  
         
               "IANAPowerStateSet is a textual convention that describes 
        Power State Sets and Power State Set Values an Energy Object  
        supports. IANA has created a registry of Power State supported 
        by an Energy Object and IANA shall administer the list of Power 
        State Sets and Power States. 
         
          The textual convention assumes that power states in a power 
          state set are limited to 255 distinct values. For a Power 
          State Set S, the named number with the value S * 256 is 
          allocated to indicate the power state set. For a Power State X 
          in the Power State S, the named number with the value S * 256 
          + X + 1 is allocated to represent the power state." 
                         
            REFERENCE  
               "http://www.iana.org/assignments/eman  
          RFC EDITOR NOTE: please change the previous URL if this is  
          not the correct one after IANA assigned it."  
                       
            SYNTAX      INTEGER { 
                           other(0),        -- indicates other set 
                           unknown(255),    -- unknown power state 
         
                           ieee1621(256), -- indicates IEEE1621 set 
                           ieee1621On(257), 
                           ieee1621Off(258), 
                           ieee1621Sleep(259), 
          
                           dmtf(512),   -- indicates DMTF set 
                           dmtfOn(513), 
                           dmtfSleepLight(514), 
                           dmtfSleepDeep(515), 
                           dmtfOffHard(516), 
                           dmtfOffSoft(517), 
                           dmtfHibernate(518), 
                           dmtfPowerOffSoft(519), 
                           dmtfPowerOffHard(520), 
                           dmtfMasterBusReset(521), 
                           dmtfDiagnosticInterrapt(522), 
                           dmtfOffSoftGraceful(523), 

      
      
     <Claise, et. Al>        Expires April 31, 2012           [Page 35] 
         

     Internet-Draft <Power and Energy Monitoring MIB>   October 2011 
      
                           dmtfOffHardGraceful(524), 
                           dmtfMasterBusResetGraceful(525), 
                           dmtfPowerCycleOffSoftGraceful(526), 
                           dmtfPowerCycleHardGraceful(527), 
         
                           eman(1024),       -- indicates EMAN set 
                           emanmechoff(1025), 
                           emansoftoff(1026),      
                           emanhibernate(1027),    
                           emansleep(1028), 
                           emanstandby(1029), 
                           emanready(1030),   
                           emanlowMinus(1031),     
                           emanlow(1032), 
                           emanmediumMinus(1033), 
                           emanmedium(1034),  
                           emanhighMinus(1035),    
                           emanhigh(1036)                         
                       } 
         
        UnitMultiplier ::= TEXTUAL-CONVENTION 
            STATUS          current 
            DESCRIPTION  
               "The Unit Multiplier is an integer value that represents 
               the IEEE 61850 Annex A units multiplier associated with 
               the integer units used to measure the power or energy.  
                 
               For example, when used with eoPowerUnitMultiplier, -3 
               represents 10^-3 or milliwatts." 
            REFERENCE 
                    "The International System of Units (SI), 
                    National Institute of Standards and Technology, 
                    Spec. Publ. 330, August 1991." 
            SYNTAX INTEGER { 
                yocto(-24),   -- 10^-24 
                zepto(-21),   -- 10^-21 
                atto(-18),    -- 10^-18 
                femto(-15),   -- 10^-15 
                pico(-12),    -- 10^-12 
                nano(-9),     -- 10^-9 
                micro(-6),    -- 10^-6 
                milli(-3),    -- 10^-3 
                units(0),     -- 10^0 
                kilo(3),      -- 10^3 
                mega(6),      -- 10^6 
                giga(9),      -- 10^9 
                tera(12),     -- 10^12 
                peta(15),     -- 10^15 
      
      
     <Claise, et. Al>        Expires April 31, 2012           [Page 36] 
         

     Internet-Draft <Power and Energy Monitoring MIB>   October 2011 
      
                exa(18),      -- 10^18 
                zetta(21),    -- 10^21 
                yotta(24)     -- 10^24 
            } 
          
        -- Objects 
         
         
        eoPowerTable OBJECT-TYPE 
            SYNTAX          SEQUENCE OF EoPowerEntry  
            MAX-ACCESS      not-accessible 
            STATUS          current 
            DESCRIPTION 
               "This table lists Energy Objects." 
            ::= { energyObjectMibObjects 1 } 
         
         
        eoPowerEntry OBJECT-TYPE 
            SYNTAX          EoPowerEntry 
            MAX-ACCESS      not-accessible 
            STATUS          current 
            DESCRIPTION 
               "An entry describes the power usage of an Energy Object." 
            INDEX           { eoPowerIndex} 
            ::= { eoPowerTable  1 } 
         
        EoPowerEntry ::= SEQUENCE { 
                eoPowerIndex                    Integer32,    
                eoPower                         Integer32, 
                eoPowerNameplate                Integer32, 
                eoPowerUnitMultiplier           UnitMultiplier, 
                eoPowerAccuracy                 Integer32,                   
                eoPowerMeasurementCaliber       INTEGER, 
                eoPowerCurrentType              INTEGER, 
                eoPowerOrigin                   INTEGER, 
                eoPowerAdminState               IANAPowerStateSet,  
                eoPowerOperState                IANAPowerStateSet,  
                eoPowerStateEnterReason         OwnerString 
          } 
         
        eoPowerIndex OBJECT-TYPE 
            SYNTAX          Integer32 (0..2147483647) 
            MAX-ACCESS      not-accessible 
            STATUS          current 
            DESCRIPTION 
              "A unique value, for each  Energy Object.  

      
      
     <Claise, et. Al>        Expires April 31, 2012           [Page 37] 
         

     Internet-Draft <Power and Energy Monitoring MIB>   October 2011 
      
              If an implementation of the ENERGY-AWARE-MIB module is 
              available in the local SNMP context, then the same index, 
              eoIndex, as the one in the ENERGY-AWARE-MIB MUST be 
              assigned for the identical Energy Object. In this case, 
              entities without an assigned value for eoIndex cannot be 
              indexed by the eoPowerStateTable. 

              If there is no implementation of the ENERGY-AWARE-MIB 
              module but one of the ENTITY MIB module is available in 
              the local SNMP context, then the same index of an entity 
              MUST be chosen as assigned to the entity by object 
              entPhysicalIndex in the ENTITY MIB module. In this case, 
              entities without an assigned value for entPhysicalIndex 
              cannot be indexed by the eoPowerStateTable. 

              If neither the ENERGY-AWARE-MIB module nor of the ENTITY 
              MIB module are available in the local SNMP context, then 
              this MIB module may choose identity values from a further 
              MIB module providing entity identities.  In this case the 
              value for each eoPowerIndex must remain constant at least 
              from one re-initialization of the entity's network 
              management system to the next re-initialization. 

              In case that no other MIB modules have been chosen for 
              providing entity identities, Power States can be reported 
              exclusively for the local device on which this table is 
              instantiated.  Then this table will have a single entry 
              only and an index value of 0 MUST be used." 

            ::= { eoPowerEntry 1 } 
         
         
         
        eoPower OBJECT-TYPE 
            SYNTAX          Integer32 
            UNITS           "Watts" 
            MAX-ACCESS      read-only 
            STATUS          current 
            DESCRIPTION 
               "This object indicates the power measured for the Energy 
               Object. For alternating current, this value is obtained 
               as an average over fixed number of AC cycles.  .  This 
               value is specified in SI units of watts with the 
               magnitude of watts (milliwatts, kilowatts, etc.) 
               indicated separately in eoPowerUnitMultiplier. The 
               accuracy of the measurement is specfied in 
               eoPowerAccuracy. The direction of power flow is indicated 
               by the sign on eoPower. If the Energy Object is consuming 
      
      
     <Claise, et. Al>        Expires April 31, 2012           [Page 38] 
         

     Internet-Draft <Power and Energy Monitoring MIB>   October 2011 
      
               power, the eoPower value will be positive. If the Energy 
               Object is producing power, the eoPower value will be 
               negative.   
           
               The eoPower MUST be less than or equal to the maximum 
               power that can be consumed at the power state specified 
               by eoPowerState. 
           
               The eoPowerMeasurementCaliber object specifies how the 
               usage value reported by eoPower was obtained. The eoPower 
               value must report 0 if the eoPowerMeasurementCaliber is 
               'unavailable'.  For devices that can not measure or 
               report power, this option can be used."  
            ::= { eoPowerEntry 2 } 
         
         
        eoPowerNameplate OBJECT-TYPE 
            SYNTAX          Integer32 
            UNITS           "Watts" 
            MAX-ACCESS      read-only 
            STATUS          current 
            DESCRIPTION 
               "This object indicates the rated maximum consumption for 
               the fully populated Energy Object.  The nameplate power 
               requirements are the maximum power numbers and, in almost 
               all cases, are well above the expected operational 
               consumption.  The eoPowerNameplate is widely used for 
               power provisioning.  This value is specified in either 
               units of watts or voltage and current.  The units are 
               therefore SI watts or equivalent Volt-Amperes with the 
               magnitude (milliwatts, kilowatts, etc.) indicated 
               separately in eoPowerUnitMultiplier."  
            ::= { eoPowerEntry 3 } 
         
        eoPowerUnitMultiplier OBJECT-TYPE 
            SYNTAX          UnitMultiplier 
            MAX-ACCESS      read-only 
            STATUS          current 
            DESCRIPTION 
               "The magnitude of watts for the usage value in eoPower 
               and eoPowerNameplate."  
            ::= { eoPowerEntry 4 } 
         
        eoPowerAccuracy OBJECT-TYPE 
            SYNTAX          Integer32 (0..10000) 
            UNITS           "hundredths of percent" 
            MAX-ACCESS      read-only 
            STATUS          current 
      
      
     <Claise, et. Al>        Expires April 31, 2012           [Page 39] 
         

     Internet-Draft <Power and Energy Monitoring MIB>   October 2011 
      
            DESCRIPTION 
               "This object indicates a percentage value, in 100ths of a 
               percent, representing the assumed accuracy of the usage 
               reported by eoPower. For example: The value 1010 means 
               the reported usage is accurate to +/- 10.1 percent.  This 
               value is zero if the accuracy is unknown or not 
               applicable based upon the measurement method. 
                
               ANSI and IEC define the following accuracy classes for 
               power measurement: 
                    IEC 62053-22  60044-1 class 0.1, 0.2, 0.5, 1  3. 
                    ANSI C12.20 class 0.2, 0.5" 
            ::= { eoPowerEntry 5 } 
         
         
        eoPowerMeasurementCaliber   OBJECT-TYPE 
            SYNTAX          INTEGER  { 
                                unavailable(1) ,          
                                unknown(2),  
                                actual(3) , 
                                estimated(4),   
                                presumed(5)                    } 
            MAX-ACCESS      read-only 
            STATUS          current 
            DESCRIPTION 
               "This object specifies how the usage value reported by 
               eoPower was obtained: 
                
               - unavailable(1): Indicates that the usage is not 
               available. In such a case, the eoPower value must be 0 
               For devices that can not measure or report power this 
               option can be used. 
                
               - unknown(2): Indicates that the way the usage was 
               determined is unknown. In some cases, entities report 
               aggregate power on behalf of another device. In such 
               cases it is not known whether the usage reported is 
               actual(2), estimated(3) or presumed (4). 
                 
               - actual(3):  Indicates that the reported usage was 
               measured by the entity through some hardware or direct 
               physical means. The usage data reported is not presumed 
               (4) or estimated (3) but the real apparent current energy 
               consumption rate. 

               - estimated(4): Indicates that the usage was not 
               determined by physical measurement. The value is a 
               derivation based upon the device type, state, and/or 
      
      
     <Claise, et. Al>        Expires April 31, 2012           [Page 40] 
         

     Internet-Draft <Power and Energy Monitoring MIB>   October 2011 
      
               current utilization using some algorithm or heuristic. It 
               is presumed that the entity's state and current 
               configuration were used to compute the value.   
               
              - presumed(5): Indicates that the usage was not 
              determined by physical measurement, algorithm or 
              derivation. The usage was reported based upon external 
              tables, specifications, and/or model information.  For 
              example, a PC Model X draws 200W, while a PC Model Y 
              draws 210W" 
               
         ::= { eoPowerEntry 6 } 
      
        eoPowerCurrentType OBJECT-TYPE 
              SYNTAX      INTEGER  { 
                               ac(1), 
                               dc(2), 
                               unknown(3) 
                           } 
               MAX-ACCESS  read-only 
               STATUS      current 
            DESCRIPTION 
               "This object indicates whether the eoUsage for the  
               Energy Object reports alternative current AC(1), direct 
               current DC(2), or that the current type is unknown(3)."  
         ::= { eoPowerEntry 7 } 
      
        eoPowerOrigin  OBJECT-TYPE 
            SYNTAX          INTEGER  { 
                                self (1),  
                                remote (2)                     
                            } 
            MAX-ACCESS      read-only 
            STATUS          current 
            DESCRIPTION 
               "This object indicates the source of power measurement 
               and can be useful when modeling the power usage of 
               attached devices. The power measurement can be performed 
               by the entity itself or the power measurement of the 
               entity can be reported by another trusted entity using a 
               protocol extension.  A value of self(1) indicates the 
               measurement is performed by the entity, whereas remote(2) 
               indicates that the measurement was performed by another 
               entity."  
            ::= { eoPowerEntry 8 } 
         
        eoPowerAdminState OBJECT-TYPE 
            SYNTAX          IANAPowerStateSet  
      
      
     <Claise, et. Al>        Expires April 31, 2012           [Page 41] 
         

     Internet-Draft <Power and Energy Monitoring MIB>   October 2011 
      
            MAX-ACCESS      read-write 
            STATUS          current 
            DESCRIPTION 
             
                "This object specifies the desired Power State and the 
                Power State Set for the Energy Object. Note that 
                other(0) is not a Power State Set and unknown(255) is 
                not a Power State as such, but simply an indication that 
                the Power State of the Energy Object is unknown. 
                Possible values of eoPowerAdminState within the Power 
                State Set are registered at IANA.   
                A current list of assignments can be found at 
                <http://www.iana.org/assignments/eman> 
                RFC-EDITOR: please check the location after IANA" 
            ::= { eoPowerEntry 9  } 
           
        eoPowerOperState OBJECT-TYPE 
            SYNTAX          IANAPowerStateSet  
            MAX-ACCESS      read-only 
            STATUS          current 
            DESCRIPTION 
                 
                "This object specifies the current operational Power 
                State and the Power State Set for the Energy Object. 
                other(0) is not a Power State Set and unknown(255) is 
                not a Power State as such, but simply an indication that 
                the Power State of the Energy Object is unknown. 
                 
                Possible values of eoPowerAdminState within the Power 
                State Set are registered at IANA.   
                A current list of assignments can be found at 
                <http://www.iana.org/assignments/eman> 
                RFC-EDITOR: please check the location after IANA" 
                 
            ::= { eoPowerEntry 10   } 
      
        eoPowerStateEnterReason OBJECT-TYPE 
             SYNTAX     OwnerString 
             MAX-ACCESS read-create 
             STATUS     current 
             DESCRIPTION 
                "This string object describes the reason for the 
                eoPowerAdminState  
                transition Alternatively, this string may contain with 
                the entity that configured this Energy Object to this 
                Power State."  
      
      
     <Claise, et. Al>        Expires April 31, 2012           [Page 42] 
         

     Internet-Draft <Power and Energy Monitoring MIB>   October 2011 
      
             DEFVAL { "" } 
             ::= { eoPowerEntry 11  } 
      
        eoPowerStateTable OBJECT-TYPE 
            SYNTAX          SEQUENCE OF EoPowerStateEntry  
            MAX-ACCESS      not-accessible 
            STATUS          current 
            DESCRIPTION 
               "This table enumerates the maximum power usage, in watts, 
               for every single supported Power State of each Energy 
               Object. 
                
               This table has an expansion-dependent relationship on the 
               eoPowerTable, containing rows describing each Power State 
               for the corresponding Energy Object. For every  Energy 
               Object in the eoPowerTable, there is a corresponding 
               entry in this table." 
            ::= { energyObjectMibObjects 2 } 
      
        eoPowerStateEntry OBJECT-TYPE 
            SYNTAX          EoPowerStateEntry 
            MAX-ACCESS      not-accessible 
            STATUS          current 
            DESCRIPTION 
               "A eoPowerStateEntry extends a corresponding 
               eoPowerEntry.  This entry displays max usage values at 
               every single possible Power State supported by the Energy 
               Object.  
               For example, given the values of a Energy Object  
               corresponding to a maximum usage of 11W at the  
               state 1 (mechoff), 6 (ready), 8 (mediumMinus), 12 (High): 
                
                    State         MaxUsage Units 
                     1 (mechoff       0       W            
                     2 (softoff)      0       W            
                     3 (hibernate)    0       W            
                     4 (sleep)        0       W            
                     5 (standby)      0       W            
                     6 (ready)        8       W           
                     7 (lowMinus)     8       W           
                     8 (low)         11       W   
                     9 (medimMinus)  11       W 
                    10 (medium)      11       W    
                    11 (highMinus)   11       W 
                    12 (high)        11       W                 
                

      
      
     <Claise, et. Al>        Expires April 31, 2012           [Page 43] 
         

     Internet-Draft <Power and Energy Monitoring MIB>   October 2011 
      
               Furthermore, this table extends to return the total time 
               in each Power State, along with the number of times a 
               particular Power State was entered." 
                
                        INDEX   { eoPowerIndex,                                 
                                 eoPowerStateIndex                    
                                }  
            ::= { eoPowerStateTable 1 } 
         
        EoPowerStateEntry ::= SEQUENCE { 
                eoPowerStateIndex                 IANAPowerStateSet,  
                eoPowerStateMaxPower              Integer32, 
                eoPowerStatePowerUnitMultiplier   UnitMultiplier,        
                eoPowerStateTotalTime             TimeTicks, 
                eoPowerStateEnterCount            Counter64 
        } 
         
        eoPowerStateIndex OBJECT-TYPE     
            SYNTAX          IANAPowerStateSet      
            MAX-ACCESS      not-accessible 
            STATUS          current 
            DESCRIPTION 
                "  
                This object specifies the index of the Power State of 
                the Energy Object within a Power State Set. The 
                semantics of the specific Power State can be obtained 
                from the Power State Set definition." 
            ::= { eoPowerStateEntry 1 } 
      
      
        eoPowerStateMaxPower OBJECT-TYPE 
            SYNTAX          Integer32 
            UNITS           "Watts" 
            MAX-ACCESS      read-only 
            STATUS          current 
            DESCRIPTION 
               "This object indicates the maximum power for the Energy 
               Object at the particular Power State. This value is 
               specified in SI units of watts with the magnitude of the 
               units (milliwatts, kilowatts, etc.) indicated separately 
               in eoPowerStatePowerUnitMultiplier. If the maximum power 
               is not known for a certain Power State, then the value is 
               encoded as 0xFFFF. 
                
               For Power States not enumerated, the value of 
               eoPowerStateMaxPower might be interpolated by using the 
               next highest supported Power State."  
            ::= { eoPowerStateEntry 3 } 
      
      
     <Claise, et. Al>        Expires April 31, 2012           [Page 44] 
         

     Internet-Draft <Power and Energy Monitoring MIB>   October 2011 
      
         
        eoPowerStatePowerUnitMultiplier OBJECT-TYPE 
            SYNTAX          UnitMultiplier  
            MAX-ACCESS      read-only 
            STATUS          current 
            DESCRIPTION 
               "The magnitude of watts for the usage value in 
               eoPowerStateMaxPower."  
            ::= { eoPowerStateEntry 4 } 
         
        eoPowerStateTotalTime OBJECT-TYPE 
            SYNTAX      TimeTicks 
            MAX-ACCESS  read-only 
            STATUS      current 
            DESCRIPTION 
              "This object indicates the total time in hundreds 
              of seconds that the Energy Object has been in this power 
              state since the last reset, as specified in the 
              sysUpTime." 
            ::= { eoPowerStateEntry 5 } 
         
        eoPowerStateEnterCount OBJECT-TYPE 
            SYNTAX      Counter64 
            MAX-ACCESS  read-only 
            STATUS      current 
            DESCRIPTION 
               "This object indicates how often the Energy  
                Object has 
                entered this power state, since the last reset of the 
                device as specified in the sysUpTime." 
            ::= { eoPowerStateEntry 6  } 
      
      
        eoEnergyParametersTable OBJECT-TYPE 
            SYNTAX          SEQUENCE OF EoEnergyParametersEntry 
            MAX-ACCESS      not-accessible 
            STATUS          current 
            DESCRIPTION 
           "This table is used to configure the parameters for Energy 
           measurement collection in the table  eoEnergyTable."     
            ::= { energyObjectMibObjects 4 } 

        eoEnergyParametersEntry OBJECT-TYPE 
            SYNTAX          EoEnergyParametersEntry 
            MAX-ACCESS      not-accessible 
            STATUS          current 
            DESCRIPTION 

      
      
     <Claise, et. Al>        Expires April 31, 2012           [Page 45] 
         

     Internet-Draft <Power and Energy Monitoring MIB>   October 2011 
      
               "An entry controls an energy measurement in 
               eoEnergyTable." 
            INDEX  { eoPowerIndex }  
            ::= { eoEnergyParametersTable 1 } 
         
        EoEnergyParametersEntry ::= SEQUENCE { 
                eoEnergyParametersIntervalLength     TimeInterval, 
                eoEnergyParametersIntervalNumber     Integer32, 
                eoEnergyParametersIntervalMode       Integer32, 
                eoEnergyParametersIntervalWindow     TimeInterval, 
                eoEnergyParametersSampleRate         Integer32, 
                eoEnergyParametersStatus             RowStatus 
        } 
         
        eoEnergyParametersIntervalLength OBJECT-TYPE 
            SYNTAX          TimeInterval 
            UNITS           "Seconds" 
            MAX-ACCESS      read-create 
            STATUS          current 
            DESCRIPTION 
               "This object indicates the length of time in seconds over 
               which to compute the average eoEnergyIntervalEnergyUsed 
               measurement in the eoEnergyTable table. The computation 
               is based on the Energy Object's internal sampling rate of 
               power consumed or produced by the Energy Object. The 
               sampling rate is the rate at which the Energy Object can 
               read the power usage and may differ based on device 
               capabilities. The average energy consumption is then 
               computed over the length of the interval."  
            DEFVAL { 900 } 
            ::= { eoEnergyParametersEntry 1 } 
         
        eoEnergyParametersIntervalNumber OBJECT-TYPE 
            SYNTAX          Integer32 
            MAX-ACCESS      read-create 
            STATUS          current 
            DESCRIPTION 
               "The number of intervals maintained in the eoEnergyTable. 
               Each interval is characterized by a specific 
               eoEnergyIntervalStartTime, used as an index to the table 
               eoEnergyTable . Whenever the maximum number of entries is 
               reached, the measurement over the new interval replaces 
               the oldest measurement , except if the oldest measurement 
               were to be the maximum eoEnergyIntervalMax, in which case 
               the measurement the measurement over the next oldest 
               interval is replaced." 
             DEFVAL { 10 }  
      
      
     <Claise, et. Al>        Expires April 31, 2012           [Page 46] 
         

     Internet-Draft <Power and Energy Monitoring MIB>   October 2011 
      
          ::= { eoEnergyParametersEntry 2 } 
         
        eoEnergyParametersIntervalMode OBJECT-TYPE 
          SYNTAX          INTEGER  { 
                              period(1), 
                              sliding(2), 
                              total(3) 
                          } 
          MAX-ACCESS      read-create 
          STATUS          current 
          DESCRIPTION 
            "A control object to define the mode of interval calculation 
            for the computation of the average 
            eoEnergyIntervalEnergyUsed measurement in the eoEnergyTable 
            table.    
               
              A mode of period(1) specifies non-overlapping periodic 
              measurements. 
             
              A mode of sliding(2) specifies overlapping sliding windows 
              where the interval between the start of one interval and 
              the next is defined in eoEnergyParametersIntervalWindow. 
             
              A mode of total(3) specifies non-periodic measurement.  In 
              this mode only one interval is used as this is a 
              continuous measurement since the last reset. The value of 
              eoEnergyParametersIntervalNumber should be (1) one and 
              eoEnergyParametersIntervalLength is ignored. "  
           ::= { eoEnergyParametersEntry 3 } 
         
        eoEnergyParametersIntervalWindow OBJECT-TYPE 
          SYNTAX          TimeInterval 
          UNITS           "Seconds" 
          MAX-ACCESS      read-create 
          STATUS          current 
          DESCRIPTION 
             "The length of the duration window between the starting 
             time of one sliding window and the next starting time in 
             seconds, in order to compute the average 
             eoEnergyIntervalEnergyUsed measurement in the eoEnergyTable 
             table  This is valid only when the 
             eoEnergyParametersIntervalMode is sliding(2). The 
             eoEnergyParametersIntervalWindow value should be a multiple 
             of eoEnergyParametersSampleRate." 
               ::= { eoEnergyParametersEntry 4 } 
         
        eoEnergyParametersSampleRate OBJECT-TYPE 
            SYNTAX          Integer32 
      
      
     <Claise, et. Al>        Expires April 31, 2012           [Page 47] 
         

     Internet-Draft <Power and Energy Monitoring MIB>   October 2011 
      
            UNITS           "Milliseconds" 
            MAX-ACCESS      read-create 
            STATUS          current 
            DESCRIPTION 
               "The sampling rate, in milliseconds, at which the  Energy 
               Object should poll power usage in order to compute the 
               average eoEnergyIntervalEnergyUsed measurement in the 
               table eoEnergyTable.  The  Energy Object should initially 
               set this sampling rate to a reasonable value, i.e., a 
               compromise between intervals that will provide good 
               accuracy by not being too long, but not so short that 
               they affect the  Energy Object performance by requesting 
               continuous polling. If the sampling rate is unknown, the 
               value 0 is reported. The sampling rate should be selected 
               so that eoEnergyParametersIntervalWindow is a multiple of 
               eoEnergyParametersSampleRate." 
             DEFVAL { 1000 }  
            ::= { eoEnergyParametersEntry 5 } 
         
        eoEnergyParametersStatus OBJECT-TYPE 
            SYNTAX          RowStatus 
            MAX-ACCESS      read-create 
            STATUS          current 
            DESCRIPTION 
              "The status of this row. The eoEnergyParametersStatus is 
              used to start or stop energy usage logging. An entry 
              status may not be active(1) unless all objects in the 
              entry have an appropriate value.  If this object is not 
              equal to active(1), all associated usage-data logged into 
              the eoEnergyTable will be deleted. The data can be 
              destroyed by setting up the eoEnergyParametersStatus to 
              destroy(2)." 
            ::= {eoEnergyParametersEntry 6 } 
      
        eoEnergyTable OBJECT-TYPE 
            SYNTAX          SEQUENCE OF EoEnergyIntervalEntry  
            MAX-ACCESS      not-accessible 
            STATUS          current 
            DESCRIPTION 
               "This table lists Energy Object energy measurements.  
               Entries in this table are only created if the 
               corresponding value of object eoPowerMeasurementCaliber 
               is active(2), i.e., if the power is actually metered." 
            ::= { energyObjectMibObjects 5 } 
         
        eoEnergyIntervalEntry OBJECT-TYPE 
      
      
     <Claise, et. Al>        Expires April 31, 2012           [Page 48] 
         

     Internet-Draft <Power and Energy Monitoring MIB>   October 2011 
      
            SYNTAX          EoEnergyIntervalEntry 
            MAX-ACCESS      not-accessible 
            STATUS          current 
            DESCRIPTION 
                "An entry describing energy measurements." 
            INDEX  { eoPowerIndex, eoEnergyParametersIntervalMode, 
        eoEnergyIntervalStartTime } 
            ::= { eoEnergyTable 1 } 

        EoEnergyIntervalEntry ::= SEQUENCE { 
             eoEnergyIntervalStartTime            TimeTicks,   
             eoEnergyIntervalEnergyConsumed       Integer32,   
             eoEnergyIntervalEnergyProduced       Integer32,  
             eoEnergyIntervalEnergyNet            Integer32, 
             eoEnergyIntervalEnergyUnitMultiplier UnitMultiplier, 
             eoEnergyIntervalEnergyAccuracy       Integer32, 
             eoEnergyIntervalMaxConsumed          Integer32, 
             eoEnergyIntervalMaxProduced          Integer32, 
             eoEnergyIntervalDiscontinuityTime    TimeTicks 
        } 
         
        eoEnergyIntervalStartTime OBJECT-TYPE 
            SYNTAX          TimeTicks 
            UNITS           "hundredths of seconds" 
            MAX-ACCESS      not-accessible 
            STATUS          current 
            DESCRIPTION 
               "The time (in hundredths of a second) since the 
               network management portion of the system was last 
               re-initialized, as specified in the sysUpTime [RFC3418]. 
               This object is useful for reference of interval periods 
               for which the energy is measured."  
            ::= { eoEnergyIntervalEntry 1 } 
         
         
         
         
        eoEnergyIntervalEnergyConsumed OBJECT-TYPE 
            SYNTAX          Integer32 
            UNITS           "Watt-hours" 
            MAX-ACCESS      read-only 
            STATUS          current 
            DESCRIPTION 
        "This object indicates the energy consumed in units of watt-
        hours for the Energy Object over the defined interval.  
        This value is specified in the common billing units of watt-
        hours with the magnitude of watt-hours (kW-Hr, MW-Hr, etc.)  
      
      
     <Claise, et. Al>        Expires April 31, 2012           [Page 49] 
         

     Internet-Draft <Power and Energy Monitoring MIB>   October 2011 
      
        indicated separately in eoEnergyIntervalEnergyUnitMultiplier."  
            ::= { eoEnergyIntervalEntry 2 } 
         
         
        eoEnergyIntervalEnergyProduced OBJECT-TYPE 
            SYNTAX          Integer32 
            UNITS           "Watt-hours" 
            MAX-ACCESS      read-only 
            STATUS          current 
            DESCRIPTION 
        "This object indicates the energy produced in units of watt-
        hours for the Energy Object over the defined interval.  
        This value is specified in the common billing units of watt-
        hours with the magnitude of watt-hours (kW-Hr, MW-Hr, etc.)  
        indicated separately in eoEnergyIntervalEnergyUnitMultiplier."  
            ::= { eoEnergyIntervalEntry 3 } 
         
         
         
         
         
         
        eoEnergyIntervalEnergyNet OBJECT-TYPE 
            SYNTAX          Integer32 
            UNITS           "Watt-hours" 
            MAX-ACCESS      read-only 
            STATUS          current 
            DESCRIPTION 
        "This object indicates the resultant of the energy consumed and 
        energy produced for an energy object in units of watt-hours for  
        the Energy Object over the defined interval. This value is 
        specified in the common billing units of watt-hours  
        with the magnitude of watt-hours (kW-Hr, MW-Hr, etc.)  
        indicated separately in eoEnergyIntervalEnergyUnitMultiplier."  
            ::= { eoEnergyIntervalEntry 4 } 
         
        eoEnergyIntervalEnergyUnitMultiplier OBJECT-TYPE 
            SYNTAX          UnitMultiplier 
            MAX-ACCESS      read-only 
            STATUS          current 
            DESCRIPTION 
               "This object is the magnitude of watt-hours for the 
               energy field in eoEnergyIntervalEnergyUsed."  
            ::= { eoEnergyIntervalEntry 5  } 
         
         
        eoEnergyIntervalEnergyAccuracy OBJECT-TYPE 
            SYNTAX          Integer32 (0..10000) 
      
      
     <Claise, et. Al>        Expires April 31, 2012           [Page 50] 
         

     Internet-Draft <Power and Energy Monitoring MIB>   October 2011 
      
            UNITS           "hundredths of percent" 
            MAX-ACCESS      read-only 
            STATUS          current 
            DESCRIPTION 
        "This object indicates a percentage value, in 100ths of a 
        percent, representing the presumed accuracy of Energy usage 
        reporting. eoEnergyIntervalEnergyAccuracy is applicable to all 
        Energy measurements in the eoEnergyTable. 
         
        For example: 1010 means the reported usage is accurate to +/- 
        10.1 percent. 
        This value is zero if the accuracy is unknown." 
         
            ::= { eoEnergyIntervalEntry 6 } 
         
        eoEnergyIntervalMaxConsumed OBJECT-TYPE 
            SYNTAX          Integer32 
            UNITS           "Watt-hours" 
            MAX-ACCESS      read-only 
            STATUS          current 
            DESCRIPTION 
               "This object is the maximum energy ever observed in 
               eoEnergyIntervalEnergyConsumed since the monitoring 
               started. This value is specified in the common billing 
               units of watt-hours with the magnitude of watt-hours (kW-
               Hr,   MW-Hr, etc.) indicated separately in 
               eoEnergyIntervalEnergyUnits."  
            ::= { eoEnergyIntervalEntry 7  } 
         
         
        eoEnergyIntervalMaxProduced OBJECT-TYPE 
            SYNTAX          Integer32 
            UNITS           "Watt-hours" 
            MAX-ACCESS      read-only 
            STATUS          current 
            DESCRIPTION 
               "This object is the maximum energy ever observed in 
               eoEnergyIntervalEnergyProduced since the monitoring 
               started. This value is specified in the units of watt-
               hours with the magnitude of watt-hours (kW-Hr,   MW-Hr, 
               etc.) indicated separately in 
               eoEnergyIntervalEnergyUnits."  
            ::= { eoEnergyIntervalEntry 8 } 
      
         
         eoEnergyIntervalDiscontinuityTime OBJECT-TYPE 
            SYNTAX      TimeTicks 
            MAX-ACCESS  read-only 
      
      
     <Claise, et. Al>        Expires April 31, 2012           [Page 51] 
         

     Internet-Draft <Power and Energy Monitoring MIB>   October 2011 
      
            STATUS      current 
            DESCRIPTION 
              "The value of sysUpTime [RFC3418] on the most recent 
              occasion at which any one or more of this entity's energy 
              consumption counters suffered a discontinuity. If no such 
              discontinuities have occurred since the last re-
              initialization of the local management subsystem, then 
              this object contains a zero value." 
            ::= { eoEnergyIntervalEntry 9 } 
         
        -- Notifications 
         
        eoPowerStateChange NOTIFICATION-TYPE 
            OBJECTS       {eoPowerAdminState, eoPowerOperState, 
        eoPowerStateEnterReason} 
            STATUS        current 
            DESCRIPTION 
                "The SNMP entity generates the eoPowerStateChange when 
                the value(s) of eoPowerAdminState or eoPowerOperState, 
               in the context of the Power State Set, have changed for 
               the Energy Object represented by the eoPowerIndex." 
           ::= { energyObjectMibNotifs 1 } 
         
        -- Conformance 
         
        energyObjectMibCompliances  OBJECT IDENTIFIER 
            ::= { energyObjectMib 3 } 
         
        energyObjectMibGroups  OBJECT IDENTIFIER 
            ::= { energyObjectMib 4 } 
         
        energyObjectMibFullCompliance MODULE-COMPLIANCE 
            STATUS          current 
            DESCRIPTION 
                "When this MIB is implemented with support for 
                read-create, then such an implementation can  
                claim full compliance. Such devices can then  
                be both monitored and configured with this MIB." 
            MODULE          -- this module 
            MANDATORY-GROUPS { 
                        energyObjectMibTableGroup, 
                        energyObjectMibStateTableGroup, 
                        energyObjectMibEnergyTableGroup,                          
                        energyObjectMibEnergyParametersTableGroup, 
                        energyObjectMibNotifGroup 
                            } 
            ::= { energyObjectMibCompliances 1 } 
         
      
      
     <Claise, et. Al>        Expires April 31, 2012           [Page 52] 
         

     Internet-Draft <Power and Energy Monitoring MIB>   October 2011 
      
        energyObjectMibReadOnlyCompliance MODULE-COMPLIANCE 
            STATUS          current 
            DESCRIPTION 
                "When this MIB is implemented without support for 
                read-create (i.e. in read-only mode), then such an  
                implementation can claim read-only compliance.  Such a  
                device can then be monitored but cannot be  
                configured with this MIB. " 
            MODULE          -- this module 
            MANDATORY-GROUPS { 
                                energyObjectMibTableGroup, 
                                energyObjectMibStateTableGroup,   
                                energyObjectMibNotifGroup 
                            } 
         
            OBJECT          eoPowerOperState 
            MIN-ACCESS      read-only 
            DESCRIPTION 
                "Write access is not required."  
            ::= { energyObjectMibCompliances 2 } 
         
        -- Units of Conformance 
         
        energyObjectMibTableGroup OBJECT-GROUP 
            OBJECTS         { 
                                eoPower, 
                                eoPowerNameplate, 
                                eoPowerUnitMultiplier, 
                                eoPowerAccuracy,                         
                                eoPowerMeasurementCaliber, 
                                eoPowerCurrentType, 
                                eoPowerOrigin, 
                                eoPowerAdminState, 
                                eoPowerOperState,  
                                eoPowerStateEnterReason                              
                            }               
                    STATUS          current 
            DESCRIPTION 
                "This group contains the collection of all the objects 
                related to the PowerMonitor." 
            ::= { energyObjectMibGroups 1 } 
         
        energyObjectMibStateTableGroup OBJECT-GROUP 
               OBJECTS      { 
                                 eoPowerStateMaxPower, 
                                 eoPowerStatePowerUnitMultiplier, 
                                 eoPowerStateTotalTime,                        
                                 eoPowerStateEnterCount            
      
      
     <Claise, et. Al>        Expires April 31, 2012           [Page 53] 
         

     Internet-Draft <Power and Energy Monitoring MIB>   October 2011 
      
                            } 
                    STATUS          current 
                    DESCRIPTION 
                        "This group contains the collection of all the  
                        objects related to the Power State." 
                    ::= { energyObjectMibGroups 2 } 
         
         
         
         
        energyObjectMibEnergyParametersTableGroup OBJECT-GROUP 
            OBJECTS         { 
                                eoEnergyParametersIntervalLength, 
                                eoEnergyParametersIntervalNumber, 
                                eoEnergyParametersIntervalMode, 
                                eoEnergyParametersIntervalWindow, 
                                eoEnergyParametersSampleRate, 
                                eoEnergyParametersStatus 
                            }     
            STATUS          current 
            DESCRIPTION 
                "This group contains the collection of all the objects 
                related to the configuration of the Energy Table." 
            ::= { energyObjectMibGroups 3 } 
         
        energyObjectMibEnergyTableGroup OBJECT-GROUP 
            OBJECTS         { 
                                -- Note that object  
                                -- eoEnergyIntervalStartTime is not 
                                -- included since it is not-accessible 
         
                                eoEnergyIntervalEnergyConsumed, 
                                eoEnergyIntervalEnergyProduced, 
                                eoEnergyIntervalEnergyNet,  
                                eoEnergyIntervalEnergyUnitMultiplier, 
                                eoEnergyIntervalEnergyAccuracy,  
                                eoEnergyIntervalMaxConsumed, 
                                eoEnergyIntervalMaxProduced, 
                                eoEnergyIntervalDiscontinuityTime   
                            }     
            STATUS          current 
            DESCRIPTION 
                "This group contains the collection of all the objects 
                related to the Energy Table." 
            ::= { energyObjectMibGroups 4 } 
         
        energyObjectMibNotifGroup NOTIFICATION-GROUP 

      
      
     <Claise, et. Al>        Expires April 31, 2012           [Page 54] 
         

     Internet-Draft <Power and Energy Monitoring MIB>   October 2011 
      
           NOTIFICATIONS    { 
                                eoPowerStateChange 
                            } 
            STATUS          current 
            DESCRIPTION 
                "This group contains the notifications for the power and 
                energy monitoring MIB Module." 
            ::= { energyObjectMibGroups 5 } 
         
        END 
         
         
        -- ************************************************************ 
        --    
        -- This MIB module is used to monitor power quality of networked  
        -- devices with measurements. 
        -- 
        -- This MIB module is an extension of energyObjectMib module. 
        --    
        -- ************************************************************* 
         
        POWER-QUALITY-MIB DEFINITIONS ::= BEGIN 
         
        IMPORTS 
            MODULE-IDENTITY, 
            OBJECT-TYPE, 
            mib-2, 
            Integer32    
               FROM SNMPv2-SMI 
            MODULE-COMPLIANCE, 
            OBJECT-GROUP 
                FROM SNMPv2-CONF 
            UnitMultiplier, eoPowerIndex 
                FROM ENERGY-OBJECT-MIB 
            OwnerString 
                FROM RMON-MIB; 
         
        powerQualityMIB MODULE-IDENTITY 
             
            LAST-UPDATED    "201110310000Z"     -- 31 October 2011 
         
            ORGANIZATION    "IETF EMAN Working Group" 
            CONTACT-INFO 
                    "WG charter: 
                    http://datatracker.ietf.org/wg/eman/charter/ 
         
                  Mailing Lists: 
                     General Discussion: eman@ietf.org 
      
      
     <Claise, et. Al>        Expires April 31, 2012           [Page 55] 
         

     Internet-Draft <Power and Energy Monitoring MIB>   October 2011 
      
                     To Subscribe:  
                     https://www.ietf.org/mailman/listinfo/eman 

                     Archive:  
                     http://www.ietf.org/mail-archive/web/eman 

                  Editors: 

                     Mouli Chandramouli 
                     Cisco Systems, Inc. 
                     Sarjapur Outer Ring Road 
                     Bangalore, 
                     IN 
                     Phone: +91 80 4426 3947 
                     Email: moulchan@cisco.com 

                     Brad Schoening 
                     44 Rivers Edge Drive 
                     Little Silver, NJ 07739 
                     US 
                     Email: brad@bradschoening.com 

                     Juergen Quittek 
                     NEC Europe Ltd. 
                     NEC Laboratories Europe 
                     Network Research Division 
                     Kurfuersten-Anlage 36 
                     Heidelberg  69115 
                     DE 
                     Phone: +49 6221 4342-115 
                     Email: quittek@neclab.eu 

                     Thomas Dietz 
                     NEC Europe Ltd. 
                     NEC Laboratories Europe 
                     Network Research Division 
                     Kurfuersten-Anlage 36 
                     69115 Heidelberg 
                     DE 
                     Phone: +49 6221 4342-128 
                     Email: Thomas.Dietz@nw.neclab.eu 

                     Benoit Claise 
                     Cisco Systems, Inc. 
                     De Kleetlaan 6a b1 
                     Degem 1831 
                     Belgium 

      
      
     <Claise, et. Al>        Expires April 31, 2012           [Page 56] 
         

     Internet-Draft <Power and Energy Monitoring MIB>   October 2011 
      
                     Phone:  +32 2 704 5622 
                     Email: bclaise@cisco.com" 

            DESCRIPTION 
                   "This MIB is used to report AC power quality in 
                   devices. The table is a sparse augmentation of the 
                   eoPowerTable table from the energyObjectMib module. 
                   Both three-phase and single-phase power 
                   configurations are supported." 
            REVISION 
         
                "201110310000Z"    -- 31 October 2011 
         
         
         
          DESCRIPTION 
               "Initial version, published as RFC YYY." 
         
           ::= { mib-2 yyy } 
         
         
        powerQualityMIBConform  OBJECT IDENTIFIER 
            ::= { powerQualityMIB 0 } 
         
         
        powerQualityMIBObjects OBJECT IDENTIFIER 
            ::= { powerQualityMIB 1 } 
         
        -- Objects 
         
         
        eoACPwrQualityTable OBJECT-TYPE 
            SYNTAX          SEQUENCE OF EoACPwrQualityEntry 
            MAX-ACCESS      not-accessible 
            STATUS          current 
            DESCRIPTION 
                "This table defines power quality measurements for 
                supported eoPowerIndex entities. It is a sparse 
                extension of the eoPowerTable." 
            ::= { powerQualityMIBObjects 1 } 
         
        eoACPwrQualityEntry OBJECT-TYPE 
            SYNTAX          EoACPwrQualityEntry 
            MAX-ACCESS      not-accessible 
            STATUS          current 
            DESCRIPTION 
                "This is a sparse extension of the eoPowerTable with 
                entries for power quality measurements or 
      
      
     <Claise, et. Al>        Expires April 31, 2012           [Page 57] 
         

     Internet-Draft <Power and Energy Monitoring MIB>   October 2011 
      
                configuration.  Each measured value corresponds to an 
                attribute in IEC 61850-7-4 for non-phase measurements 
                within the object MMUX." 
            INDEX { eoPowerIndex } 
            ::= { eoACPwrQualityTable 1 } 
         
        EoACPwrQualityEntry ::= SEQUENCE { 
            eoACPwrQualityConfiguration       INTEGER,  
            eoACPwrQualityAvgVoltage          Integer32, 
            eoACPwrQualityAvgCurrent          Integer32, 
            eoACPwrQualityFrequency           Integer32, 
            eoACPwrQualityPowerUnitMultiplier UnitMultiplier, 
            eoACPwrQualityPowerAccuracy       Integer32, 
            eoACPwrQualityTotalActivePower    Integer32, 
            eoACPwrQualityTotalReactivePower  Integer32, 
            eoACPwrQualityTotalApparentPower  Integer32, 
            eoACPwrQualityTotalPowerFactor    Integer32,     
            eoACPwrQualityThdAmpheres         Integer32, 
            eoACPwrQualityThdVoltage          Integer32 
        } 
         
        eoACPwrQualityConfiguration OBJECT-TYPE 
            SYNTAX INTEGER {  
                sngl(1),  
                del(2),  
                wye(3) 
                   } 
            MAX-ACCESS      read-only 
            STATUS          current 
            DESCRIPTION 
                 "Configuration describes the physical configurations 
                 of the power supply lines: 
                  
                    * alternating current, single phase (SNGL) 
                    * alternating current, three phase delta (DEL) 
                    * alternating current, three phase Y (WYE) 
                  
                 Three-phase configurations can be either connected in 
                 a triangular delta (DEL) or star Y (WYE) system.  WYE 
                 systems have a shared neutral voltage, while DEL 
                 systems do not.  Each phase is offset 120 degrees to 
                 each other." 
            ::= { eoACPwrQualityEntry 1 } 
         
        eoACPwrQualityAvgVoltage OBJECT-TYPE 
            SYNTAX          Integer32 
            UNITS           "0.1 Volt AC" 
            MAX-ACCESS      read-only 
      
      
     <Claise, et. Al>        Expires April 31, 2012           [Page 58] 
         

     Internet-Draft <Power and Energy Monitoring MIB>   October 2011 
      
            STATUS          current 
            DESCRIPTION 
                "A measured value for average of the voltage measured 
                over an integral number of AC cycles   For a 3-phase 
                system, this is the average voltage (V1+V2+V3)/3.  IEC 
                61850-7-4 measured value attribute 'Vol'" 
            ::= { eoACPwrQualityEntry 2 } 
         
        eoACPwrQualityAvgCurrent OBJECT-TYPE 
            SYNTAX          Integer32 
            UNITS           "Ampheres" 
            MAX-ACCESS      read-only 
            STATUS          current 
            DESCRIPTION 
                "A measured value of the current per phase. IEC 61850-
                7-4 attribute 'Amp'" 
            ::= { eoACPwrQualityEntry 3 } 
         
        eoACPwrQualityFrequency OBJECT-TYPE 
            SYNTAX          Integer32 (4500..6500) -- UNITS 0.01 Hertz 
            UNITS           "hertz" 
            MAX-ACCESS      read-only 
            STATUS          current 
            DESCRIPTION 
                "A measured value for the basic frequency of the AC 
                circuit.  IEC 61850-7-4 attribute 'Hz'." 
            ::= { eoACPwrQualityEntry 4 } 
         
        eoACPwrQualityPowerUnitMultiplier OBJECT-TYPE 
            SYNTAX          UnitMultiplier 
            MAX-ACCESS      read-only 
            STATUS          current 
            DESCRIPTION 
                "The magnitude of watts for the usage value in 
                eoACPwrQualityTotalActivePower, 
                eoACPwrQualityTotalReactivePower  
                and eoACPwrQualityTotalApparentPower measurements.  For 
                3-phase power systems, this will also include  
                eoACPwrQualityPhaseActivePower, 
                eoACPwrQualityPhaseReactivePower and 
                eoACPwrQualityPhaseApparentPower"  
            ::= { eoACPwrQualityEntry 5 } 
         
        eoACPwrQualityPowerAccuracy OBJECT-TYPE 
            SYNTAX          Integer32 (0..10000) 
            UNITS           "hundredths of percent" 
            MAX-ACCESS      read-only 
            STATUS          current 
      
      
     <Claise, et. Al>        Expires April 31, 2012           [Page 59] 
         

     Internet-Draft <Power and Energy Monitoring MIB>   October 2011 
      
            DESCRIPTION 
                "This object indicates a percentage value, in 100ths of 
                a percent, representing the presumed accuracy of 
                active, reactive, and apparent power usage reporting. 
                For example: 1010 means the reported usage is accurate 
                to +/- 10.1 percent.  This value is zero if the 
                accuracy is unknown. 
                 
                ANSI and IEC define the following accuracy classes for 
                power measurement: IEC 62053-22 & 60044-1 class 0.1, 
                0.2, 0.5, 1 & 3. 
                ANSI C12.20 class 0.2 & 0.5" 
            ::= { eoACPwrQualityEntry 6 } 
         
        eoACPwrQualityTotalActivePower OBJECT-TYPE 
            SYNTAX          Integer32 
            UNITS           " watts" 
            MAX-ACCESS      read-only 
            STATUS          current 
            DESCRIPTION 
                "A measured value of the actual power delivered to or 
                consumed by the load.  IEC 61850-7-4 attribute 'TotW'." 
            ::= { eoACPwrQualityEntry 7 } 
         
        eoACPwrQualityTotalReactivePower OBJECT-TYPE 
            SYNTAX          Integer32 
            UNITS           "volt-amperes reactive" 
            MAX-ACCESS      read-only 
            STATUS          current 
            DESCRIPTION 
                "A mesured value of the reactive portion of the 
                apparent power.  IEC 61850-7-4 attribute 'TotVAr'." 
            ::= { eoACPwrQualityEntry 8 } 
         
        eoACPwrQualityTotalApparentPower OBJECT-TYPE 
            SYNTAX          Integer32  
            UNITS           "volt-amperes" 
            MAX-ACCESS      read-only 
            STATUS          current 
            DESCRIPTION 
                "A measured value of the voltage and current which 
                determines the apparent power.  The apparent power is 
                the vector sum of real and reactive power.  
                  
                Note: watts and volt-ampheres are equivalent units and 
                may be combined.  IEC 61850-7-4 attribute 'TotVA'." 
            ::= { eoACPwrQualityEntry 9 } 
         
      
      
     <Claise, et. Al>        Expires April 31, 2012           [Page 60] 
         

     Internet-Draft <Power and Energy Monitoring MIB>   October 2011 
      
        eoACPwrQualityTotalPowerFactor OBJECT-TYPE 
            SYNTAX          Integer32 (-10000..10000) 
            UNITS           "hundredths of percent" 
            MAX-ACCESS      read-only 
            STATUS          current 
            DESCRIPTION 
                "A measured value ratio of the real power flowing to 
                the load versus the apparent power. It is dimensionless 
                and expressed here as a percentage value in 100ths of a 
                percent. A power factor of 100% indicates there is no 
                inductance load and thus no reactive power. Power 
                Factor can be positive or negative, where the sign 
                should be in lead/lag (IEEE) form.  IEC 61850-7-4 
                attribute 'TotPF'." 
            ::= { eoACPwrQualityEntry 10 } 
         
        eoACPwrQualityThdAmpheres OBJECT-TYPE 
            SYNTAX          Integer32 (0..10000) 
            UNITS           "hundredths of percent" 
            MAX-ACCESS      read-only 
            STATUS          current 
            DESCRIPTION 
                "A calculated value for the current total harmonic 
                distortion (THD).  Method of calculation is not 
                specified.  IEC 61850-7-4 attribute 'ThdAmp'." 
            ::= { eoACPwrQualityEntry 11 } 
         
        eoACPwrQualityThdVoltage OBJECT-TYPE 
            SYNTAX          Integer32 (0..10000) 
            UNITS           "hundredths of percent" 
            MAX-ACCESS      read-only 
            STATUS          current 
            DESCRIPTION 
                "A calculated value for the voltage total harmonic 
                distortion (THD).  Method of calculation is not 
                specified.  IEC 61850-7-4 attribute 'ThdVol'." 
            ::= { eoACPwrQualityEntry 12 } 
         
        eoACPwrQualityPhaseTable OBJECT-TYPE 
            SYNTAX          SEQUENCE OF EoACPwrQualityPhaseEntry 
            MAX-ACCESS      not-accessible 
            STATUS          current 
            DESCRIPTION 
                "This table describes 3-phase power quality 
                measurements.  It is a sparse extension of the 
                eoACPwrQualityTable." 
            ::= { powerQualityMIBObjects 2 } 
         
      
      
     <Claise, et. Al>        Expires April 31, 2012           [Page 61] 
         

     Internet-Draft <Power and Energy Monitoring MIB>   October 2011 
      
        eoACPwrQualityPhaseEntry OBJECT-TYPE 
            SYNTAX          EoACPwrQualityPhaseEntry 
            MAX-ACCESS      not-accessible 
            STATUS          current 
            DESCRIPTION 
                "An entry describes common 3-phase power quality 
                measurements. 
                 
                This optional table describes 3-phase power quality 
                measurements, with three entries for each supported 
                eoPowerIndex entity.  Entities having single phase 
                power shall not have any entities.  
                 
                This table describes attributes common to both WYE and 
                DEL.  Entities having single phase power shall not have 
                any entries here.  It is a sparse extension of the 
                eoACPwrQualityTable.   
                 
                These attributes correspond to IEC 61850-7.4 MMXU phase 
                measurements." 
            INDEX { eoPowerIndex, eoPhaseIndex } 
            ::= { eoACPwrQualityPhaseTable 1 } 
         
        EoACPwrQualityPhaseEntry ::= SEQUENCE { 
                eoPhaseIndex                       Integer32, 
                eoACPwrQualityPhaseAvgCurrent      Integer32, 
                eoACPwrQualityPhaseActivePower     Integer32, 
                eoACPwrQualityPhaseReactivePower   Integer32, 
                eoACPwrQualityPhaseApparentPower   Integer32, 
                eoACPwrQualityPhasePowerFactor     Integer32,     
                eoACPwrQualityPhaseImpedance       Integer32      
        } 
         
        eoPhaseIndex OBJECT-TYPE 
            SYNTAX          Integer32 (0..359) 
            MAX-ACCESS      not-accessible 
            STATUS          current 
            DESCRIPTION 
               "A phase angle typically corresponding to 0, 120, 240." 
             ::= { eoACPwrQualityPhaseEntry 1 } 
         
        eoACPwrQualityPhaseAvgCurrent OBJECT-TYPE 
            SYNTAX          Integer32 
            UNITS           "Ampheres" 
            MAX-ACCESS      read-only 
            STATUS          current 
            DESCRIPTION 

      
      
     <Claise, et. Al>        Expires April 31, 2012           [Page 62] 
         

     Internet-Draft <Power and Energy Monitoring MIB>   October 2011 
      
                "A measured value of the current per phase. IEC 61850-
                7-4 attribute 'A'" 
            ::= { eoACPwrQualityPhaseEntry 2 } 
         
        eoACPwrQualityPhaseActivePower OBJECT-TYPE 
            SYNTAX          Integer32 
            UNITS           " watts" 
            MAX-ACCESS      read-only 
            STATUS          current 
            DESCRIPTION 
                "A measured value of the actual power delivered to or 
                consumed by the load. IEC 61850-7-4 attribute 'W'" 
            ::= { eoACPwrQualityPhaseEntry 3 } 
         
        eoACPwrQualityPhaseReactivePower OBJECT-TYPE 
            SYNTAX          Integer32 
            UNITS           "volt-amperes reactive" 
            MAX-ACCESS      read-only 
            STATUS          current 
            DESCRIPTION 
                "A measured value of the reactive portion of the 
                apparent power.  IEC 61850-7-4 attribute 'VAr'" 
            ::= { eoACPwrQualityPhaseEntry 4 } 
         
        eoACPwrQualityPhaseApparentPower OBJECT-TYPE 
            SYNTAX          Integer32  
            UNITS           "volt-amperes" 
            MAX-ACCESS      read-only 
            STATUS          current 
            DESCRIPTION 
                "A measured value of the voltage and current determines 
                the apparent power.  Active plus reactive power equals 
                the total apparent powwer. 
                  
                Note: Watts and volt-ampheres are equivalent units and 
                may be combined.  IEC 61850-7-4 attribute 'VA'." 
            ::= { eoACPwrQualityPhaseEntry 5 } 
         
        eoACPwrQualityPhasePowerFactor OBJECT-TYPE 
            SYNTAX          Integer32 (-10000..10000) 
            UNITS           "hundredths of percent" 
            MAX-ACCESS      read-only 
            STATUS          current 
            DESCRIPTION 
                "A measured value ratio of the real power flowing to 
                the load versus the apparent power for this phase.  IEC 
                61850-7-4 attribute 'PF'. Power Factor can be positive 

      
      
     <Claise, et. Al>        Expires April 31, 2012           [Page 63] 
         

     Internet-Draft <Power and Energy Monitoring MIB>   October 2011 
      
                or negative where the sign should be in lead/lag (IEEE) 
                form." 
            ::= { eoACPwrQualityPhaseEntry 6 } 
         
        eoACPwrQualityPhaseImpedance OBJECT-TYPE 
            SYNTAX          Integer32  
            UNITS           "volt-amperes" 
            MAX-ACCESS      read-only 
            STATUS          current 
            DESCRIPTION 
        "A measured value of the impedance.  IEC 61850-7-4 attribute 
        'Z'." 
            ::= { eoACPwrQualityPhaseEntry 7 } 
         
        eoACPwrQualityDelPhaseTable OBJECT-TYPE 
            SYNTAX          SEQUENCE OF EoACPwrQualityDelPhaseEntry  
            MAX-ACCESS      not-accessible 
            STATUS          current 
            DESCRIPTION 
               "This table describes DEL configuration phase-to-phase 
               power quality measurements.  This is a sparse extension 
               of the eoACPwrQualityPhaseTable." 
            ::= { powerQualityMIBObjects 3 } 
         
        eoACPwrQualityDelPhaseEntry OBJECT-TYPE 
            SYNTAX          EoACPwrQualityDelPhaseEntry 
            MAX-ACCESS      not-accessible 
            STATUS          current 
            DESCRIPTION 
               "An entry describes quality attributes of a phase in a 
               DEL 3-phase power system.  Voltage measurements are 
               provided both relative to each other and zero. 
                
               Measured values are from IEC 61850-7-2 MMUX and THD from 
               MHAI objects. 
                
               For phase-to-phase measurements, the eoPhaseIndex is 
               compared against the following phase at +120 degrees.  
               Thus, the possible values are: 
                
                             eoPhaseIndex        Next Phase Angle 
                                   0                 120 
                                 120                 240 
                                 240                   0    
               " 
            INDEX { eoPowerIndex, eoPhaseIndex} 
            ::= { eoACPwrQualityDelPhaseTable 1} 
         
      
      
     <Claise, et. Al>        Expires April 31, 2012           [Page 64] 
         

     Internet-Draft <Power and Energy Monitoring MIB>   October 2011 
      
        EoACPwrQualityDelPhaseEntry ::= SEQUENCE { 
            eoACPwrQualityDelPhaseToNextPhaseVoltage      Integer32, 
            eoACPwrQualityDelThdPhaseToNextPhaseVoltage   Integer32, 
            eoACPwrQualityDelThdCurrent                   Integer32 
        } 
         
        eoACPwrQualityDelPhaseToNextPhaseVoltage OBJECT-TYPE 
            SYNTAX          Integer32 
            UNITS           "0.1 Volt AC" 
            MAX-ACCESS      read-only 
            STATUS          current 
            DESCRIPTION 
               "A measured value of phase to next phase voltages, where 
               the next phase is IEC 61850-7-4 attribute 'PPV'." 
            ::= { eoACPwrQualityDelPhaseEntry 2 } 
         
        eoACPwrQualityDelThdPhaseToNextPhaseVoltage OBJECT-TYPE 
            SYNTAX          Integer32 (0..10000) 
            UNITS           "hundredths of percent" 
            MAX-ACCESS      read-only 
            STATUS          current 
            DESCRIPTION 
               "A calculated value for the voltage total harmonic 
               disortion for phase to next phase. Method of calculation 
               is not specified.  IEC 61850-7-4 attribute 'ThdPPV'." 
            ::= { eoACPwrQualityDelPhaseEntry 3 } 
         
        eoACPwrQualityDelThdCurrent OBJECT-TYPE 
            SYNTAX          Integer32 (0..10000) 
            UNITS           "hundredths of percent" 
            MAX-ACCESS      read-only 
            STATUS          current 
          DESCRIPTION  
               "A calculated value for the voltage total harmonic 
               disortion (THD) for phase to phase.  Method of 
               calculation is not specified.   
               IEC 61850-7-4 attribute 'ThdPPV'." 
            ::= { eoACPwrQualityDelPhaseEntry 4 } 
         
        eoACPwrQualityWyePhaseTable OBJECT-TYPE 
            SYNTAX          SEQUENCE OF EoACPwrQualityWyePhaseEntry  
            MAX-ACCESS      not-accessible 
            STATUS          current 
            DESCRIPTION 
               "This table describes WYE configuration phase-to-neutral 
               power quality measurements.  This is a sparse extension 
               of the eoACPwrQualityPhaseTable." 
            ::= { powerQualityMIBObjects 4 } 
      
      
     <Claise, et. Al>        Expires April 31, 2012           [Page 65] 
         

     Internet-Draft <Power and Energy Monitoring MIB>   October 2011 
      
         
        eoACPwrQualityWyePhaseEntry OBJECT-TYPE 
            SYNTAX          EoACPwrQualityWyePhaseEntry 
            MAX-ACCESS      not-accessible 
            STATUS          current 
            DESCRIPTION 
               "This table describes measurements of WYE configuration 
               with phase to neutral power quality attributes. Three 
               entries are required for each supported eoPowerIndex 
               entry.  Voltage measurements are relative to neutral. 
                
               This is a sparse extension of the 
               eoACPwrQualityPhaseTable. 
                
               Each entry describes quality attributes of one phase of 
               a WYE 3-phase power system. 
                
               Measured values are from IEC 61850-7-2 MMUX and THD from 
               MHAI objects." 
            INDEX { eoPowerIndex, eoPhaseIndex } 
            ::= { eoACPwrQualityWyePhaseTable 1} 
         
        EoACPwrQualityWyePhaseEntry ::= SEQUENCE { 
                eoACPwrQualityWyePhaseToNeutralVoltage       Integer32, 
                eoACPwrQualityWyePhaseCurrent                Integer32, 
                eoACPwrQualityWyeThdPhaseToNeutralVoltage    Integer32 
        } 
         
        eoACPwrQualityWyePhaseToNeutralVoltage OBJECT-TYPE 
            SYNTAX          Integer32 
            UNITS           "0.1 Volt AC" 
            MAX-ACCESS      read-only 
            STATUS          current 
            DESCRIPTION 
               "A measured value of phase to neutral voltage.  IEC 
               61850-7-4 attribute 'PhV'." 
            ::= { eoACPwrQualityWyePhaseEntry 1 } 
         
        eoACPwrQualityWyePhaseCurrent OBJECT-TYPE 
            SYNTAX          Integer32 
            UNITS           "0.1 ampheres AC" 
            MAX-ACCESS      read-only 
            STATUS          current 
            DESCRIPTION 
               "A measured value of phase currents.  IEC 61850-7-4 
               attribute 'A'." 
            ::= { eoACPwrQualityWyePhaseEntry 2 } 
         
      
      
     <Claise, et. Al>        Expires April 31, 2012           [Page 66] 
         

     Internet-Draft <Power and Energy Monitoring MIB>   October 2011 
      
        eoACPwrQualityWyeThdPhaseToNeutralVoltage OBJECT-TYPE 
            SYNTAX          Integer32 (0..10000) 
            UNITS           "hundredths of percent" 
            MAX-ACCESS      read-only 
            STATUS          current 
            DESCRIPTION 
               "A calculated value of the voltage total harmonic 
               distortion (THD) for phase to neutral. IEC 61850-7-4 
               attribute 'ThdPhV'." 
            ::= { eoACPwrQualityWyePhaseEntry 3 } 
         
        -- Conformance 
         
        powerQualityMIBCompliances  OBJECT IDENTIFIER 
            ::= { powerQualityMIB 2 } 
         
        powerQualityMIBGroups  OBJECT IDENTIFIER 
            ::= { powerQualityMIB 3 } 
         
        powerQualityMIBFullCompliance MODULE-COMPLIANCE 
            STATUS          current 
            DESCRIPTION 
               "When this MIB is implemented with support for read-
               create, then such an implementation can claim full 
               compliance. Such devices can then be both monitored and 
               configured with this MIB." 
            MODULE          -- this module 
            MANDATORY-GROUPS { 
                                powerACPwrQualityMIBTableGroup, 
                                powerACPwrQualityPhaseMIBTableGroup 
                             } 
         
            GROUP       powerACPwrQualityDelPhaseMIBTableGroup 
            DESCRIPTION 
               "This group must only be implemented for a DEL phase 
               configuration." 
         
            GROUP       powerACPwrQualityWyePhaseMIBTableGroup 
            DESCRIPTION 
               "This group must only be implemented for a WYE phase 
               configuration." 
            ::= { powerQualityMIBCompliances 1 } 
         
         
        -- Units of Conformance 
         
        powerACPwrQualityMIBTableGroup OBJECT-GROUP 
            OBJECTS         { 
      
      
     <Claise, et. Al>        Expires April 31, 2012           [Page 67] 
         

     Internet-Draft <Power and Energy Monitoring MIB>   October 2011 
      
                                -- Note that object eoPowerIndex is NOT  
                                -- included since it is not-accessible 
                                eoACPwrQualityConfiguration, 
                                eoACPwrQualityAvgVoltage, 
                                eoACPwrQualityAvgCurrent, 
                                eoACPwrQualityFrequency, 
                                eoACPwrQualityPowerUnitMultiplier, 
                                eoACPwrQualityPowerAccuracy, 
                                eoACPwrQualityTotalActivePower, 
                                eoACPwrQualityTotalReactivePower, 
                                eoACPwrQualityTotalApparentPower, 
                                eoACPwrQualityTotalPowerFactor, 
                                eoACPwrQualityThdAmpheres, 
                                eoACPwrQualityThdVoltage 
                            }    STATUS          current 
            DESCRIPTION 
               "This group contains the collection of all the power 
               quality objects related to the Energy Object." 
            ::= { powerQualityMIBGroups  1 } 
         
         
        powerACPwrQualityPhaseMIBTableGroup OBJECT-GROUP 
            OBJECTS         { 
                                -- Note that object eoPowerIndex is NOT  
                                -- included since it is not-accessible 
                                eoACPwrQualityPhaseAvgCurrent, 
                                eoACPwrQualityPhaseActivePower, 
                                eoACPwrQualityPhaseReactivePower, 
                                eoACPwrQualityPhaseApparentPower, 
                                eoACPwrQualityPhasePowerFactor,   
                                eoACPwrQualityPhaseImpedance      
                            } 
            STATUS          current 
            DESCRIPTION 
               "This group contains the collection of all 3-phase power 
               quality objects related to the Power State." 
            ::= { powerQualityMIBGroups  2 } 
         
        powerACPwrQualityDelPhaseMIBTableGroup OBJECT-GROUP 
            OBJECTS         { 
                            -- Note that object eoPowerIndex and  
                            -- eoPhaseIndex are NOT included 
                            -- since they are not-accessible 
                            eoACPwrQualityDelPhaseToNextPhaseVoltage , 
                            eoACPwrQualityDelThdPhaseToNextPhaseVoltage, 
                            eoACPwrQualityDelThdCurrent 
                            } 
            STATUS          current 
      
      
     <Claise, et. Al>        Expires April 31, 2012           [Page 68] 
         

     Internet-Draft <Power and Energy Monitoring MIB>   October 2011 
      
            DESCRIPTION 
                "This group contains the collection of all quality 
                attributes of a phase in a DEL 3-phase power system." 
            ::= { powerQualityMIBGroups  3 } 
         
        powerACPwrQualityWyePhaseMIBTableGroup OBJECT-GROUP 
            OBJECTS         { 
                               -- Note that object eoPowerIndex and  
                               -- eoPhaseIndex are NOT included 
                               -- since they are not-accessible 
                               eoACPwrQualityWyePhaseToNeutralVoltage, 
                               eoACPwrQualityWyePhaseCurrent, 
                               eoACPwrQualityWyeThdPhaseToNeutralVoltage 
                            } 
            STATUS          current 
            DESCRIPTION 
                "This group contains the collection of all WYE 
                configuration phase-to-neutral power quality 
                measurements." 
            ::= { powerQualityMIBGroups  4 } 
         
         
         
        END 
         
     11. Security Considerations 

        Some of the readable objects in these MIB modules (i.e., objects 
        with a MAX-ACCESS other than not-accessible) may be considered 
        sensitive or vulnerable in some network environments.  It is 
        thus important to control even GET and/or NOTIFY access to these 
        objects and possibly to even encrypt the values of these objects 
        when sending them over the network via SNMP.   
         
        There are a number of management objects defined in these MIB 
        modules with a MAX-ACCESS clause of read-write and/or read-
        create.  Such objects MAY be considered sensitive or vulnerable 
        in some network environments.  The support for SET operations in 
        a non-secure environment without proper protection can have a 
        negative effect on network operations.  The following are the 
        tables and objects and their sensitivity/vulnerability: 
         
        - Unauthorized changes to the eoPowerOperState (via 
          theeoPowerAdminState ) MAY disrupt the power settings of the 
          differentEnergy Objects, and therefore the state of 
          functionality of the respective Energy Objects. 
        - Unauthorized changes to the eoEnergyParametersTable MAY 
          disrupt energy measurement in the eoEnergyTable table.  
      
      
     <Claise, et. Al>        Expires April 31, 2012           [Page 69] 
         

     Internet-Draft <Power and Energy Monitoring MIB>   October 2011 
      
         
        SNMP versions prior to SNMPv3 did not include adequate security. 
        Even if the network itself is secure (for example, by using 
        IPsec), there is still no secure control over who on the secure 
        network is allowed to access and GET/SET 
        (read/change/create/delete) the objects in these MIB modules. 
         
        It is RECOMMENDED that implementers consider the security 
        features as provided by the SNMPv3 framework (see [RFC3410], 
        section 8), including full support for the SNMPv3 cryptographic 
        mechanisms (for authentication and privacy). 
         
        Further, deployment of SNMP versions prior to SNMPv3 is NOT 
        RECOMMENDED.  Instead, it is RECOMMENDED to deploy SNMPv3 and to 
        enable cryptographic security.  It is then a customer/operator 
        responsibility to ensure that the SNMP entity giving access to 
        an instance of these MIB modules is properly configured to give 
        access to the objects only to those principals (users) that have 
        legitimate rights to GET or SET (change/create/delete) them. 
         

     12. IANA Considerations 

     12.1. IANA Considerations for the MIB Modules 

      

        The MIB modules in this document uses the following IANA-
        assigned OBJECT IDENTIFIER values recorded in the SMI Numbers 
        registry: 
         
               Descriptor            OBJECT IDENTIFIER value 
               ----------            ----------------------- 
               energyObjectMib         { mib-2 xxx } 
               powerQualityMIB         { mib-2 yyy } 
         
        Additions to the MIB modules are subject to Expert Review 
        [RFC5226], i.e., review by one of a group of experts designated 
        by an IETF Area Director.  The group of experts MUST check the 
        requested MIB objects for completeness and accuracy of the 
        description.  Requests for MIB objects that duplicate the 
        functionality of existing objects SHOULD be declined.  The 
        smallest available OIDs SHOULD be assigned to the new MIB 
        objects.  The specification of new MIB objects SHOULD follow the 
        structure specified in Section 10.  and MUST be published using 
        a well-established and persistent publication medium.   
      

      
      
     <Claise, et. Al>        Expires April 31, 2012           [Page 70] 
         

     Internet-Draft <Power and Energy Monitoring MIB>   October 2011 
      
     12.2. IANA Registration of new Power State Set 

        This document specifies an initial set of Power State Sets. The 
        list of these Power State Sets with their numeric identifiers is 
        given in Section 5.2.1.  IANA maintains a Textual Convention 
        IANAPowerStateSet with the initial set of Power State Sets and 
        the Power States within those Power State Sets. The current 
        version of Textual convention can be accessed 
        http://www.iana.org/assignments/IANAPowerStateSet 
         
        New Assignments to Power State Sets shall be administered by 
        IANA and the guidelines and procedures are listed in this 
        Section.  
      
        New assignments for Power State Set will be administered by IANA 
        through Expert Review [RFC5226], i.e., review by one of a group 
        of experts designated by an IETF Area Director.  The group of 
        experts MUST check the requested state for completeness and 
        accuracy of the description. A pure vendor specific 
        implementation of Power State Set shall not be adopted; since it 
        would lead to proliferation of Power State Sets.  
      
         
      
     12.2.1. IANA Registration of the IEEE1621 Power State Set 

        This document specifies a set of values for the IEEE1621 Power 
        State Set [IEEE1621].  The list of these values with their 
        identifiers is given in Section 5.2.1.  The Internet Assigned 
        Numbers Authority (IANA) created a new registry for IEEE1621 
        Power State Set identifiers and filled it with the initial 
        listin the Textual Convention IANAPowerStateSet..  
         
        New assignments (or potentially deprecation) for IEEE1621 Power 
        State Set will be administered by IANA through Expert Review 
        [RFC5226], i.e., review by one of a group of experts designated 
        by an IETF Area Director.  The group of experts MUST check the 
        requested state for completeness and accuracy of the 
        description. 
         
     12.2.2. IANA Registration of the DMTF Power State Set 

        This document specifies a set of values for the DMTF Power State 
        Set.  The list of these values with their identifiers is given 
        in Section 5.2.1.  The Internet Assigned Numbers Authority 
        (IANA) has created a new registry for DMTF Power State Set 
        identifiers and filled it with the initial list in  the Textual 
        Convention IANAPowerStateSet. 
      
      
     <Claise, et. Al>        Expires April 31, 2012           [Page 71] 
         

     Internet-Draft <Power and Energy Monitoring MIB>   October 2011 
      
        New assignments (or potentially deprecation) for DMTF Power 
        State Set will be administered by IANA through Expert Review 
        [RFC5226], i.e., review by one of a group of experts designated 
        by an IETF Area Director.  The group of experts MUST check the 
        conformance with the DMTF standard [DMTF], on the top of 
        checking for completeness and accuracy of the description. 
         
         
     12.2.3. IANA Registration of the EMAN Power State Set 

        This document specifies a set of values for the EMAN Power State 
        Set.  The list of these values with their identifiers is given 
        in Section 5.2.1.  The Internet Assigned Numbers Authority 
        (IANA) has created a new registry for EMAN Power State Set 
        identifiers and filled it with the initial list in the Textual 
        Convention IANAPowerStateSet. 
        New assignments (or potentially deprecation) for EMAN Power 
        State Set will be administered by IANA through Expert Review 
        [RFC5226], i.e., review by one of a group of experts designated 
        by an IETF Area Director.  The group of experts MUST check the 
        requested state for completeness and accuracy of the 
        description. 
         
         
         
     12. Contributors 

        This document results from the merger of two initial proposals. 
        The following persons made significant contributions either in 
        one of the initial proposals or in this document. 
         
        John Parello 
         
        Rolf Winter 
         
        Dominique Dudkowski 
         
         

     13. Acknowledgment 

        The authors would like to thank Shamita Pisal for her prototype 
        of this MIB module, and her valuable feedback.  The authors 
        would like to Michael Brown for improving the text dramatically. 
         
         

      
      
     <Claise, et. Al>        Expires April 31, 2012           [Page 72] 
         

     Internet-Draft <Power and Energy Monitoring MIB>   October 2011 
      
        We would like to thank Juergen Schoenwalder for proposing the 
        design of the Textual Convention for IANAPowerStateSet and Ira 
        McDonald for his feedback.  
         

     14. Open Issues 

         
        OPEN ISSUE 1 : Double-check all the IEC references in the draft.  
         
          IEC 61850-7-4 has been widely referenced in many EMAN drafts.  
          The other IEC references suggested in the email list are   
          IEC 61000-4-30  and IEC 62053-21 and IEC 62301. It is 
          important to resolve the correct IEC references soon.  
           
      
        OPEN ISSUE 2 : Description clause of eoPowerIndex. Do we need 
        this text ? Juergen Quittek to comment:  
         
          "The identity provisioning method that has been chosen can be 
          retrieved by reading the value of powerStateEnergyConsumerOid. 
          In case of identities provided by the ENERGY-AWARE-MIB module, 
          this OID points to an exising instance of eoPowerIndex, in 
          case of the ENTITY MIB, the object points to a valid instance 
          of entPhysicalIndex, and in a similar way, it points to a 
          value of another MIB module if this is used for identifying 
          entities. If no other MIB module has been chosen for providing 
          entity identities, then the value of 
          powerStateEnergyConsumerOid MUST be 0.0 (zeroDotZero). 
           
           
         
        OPEN ISSUE 3: Time Series of measurements required ? Mechanism 
        pull or push ?  What shall the table consist of ?   
        Power, Voltage, Current, Energy and Demand.  
         
         
           
        OPEN ISSUE 4: Demand computation method  
           
          "Energy not obtained by periodically polling a power 
          measurement with a eoEnergyParametersSampleRate ; Energy (E) 
          is measured to the product's certified IEC 62053-21 accuracy 
          class" 
             
          Need to verify with IEC62053-21.  
           
             
      
      
     <Claise, et. Al>        Expires April 31, 2012           [Page 73] 
         

     Internet-Draft <Power and Energy Monitoring MIB>   October 2011 
      
        OPEN ISSUE 5: Consideration of IEEE-ISTO PWG in the IANA list of 
        Power State Set ? Printer Power series could be added once the 
        IANA procedure is in place. 
         
         
        OPEN ISSUE 6: check if all the requirements from [EMAN-REQ] are 
        covered.  
         
      
     15. References 

      15.2. Normative References 

         
        [RFC2119] S. Bradner, Key words for use in RFCs to Indicate 
                Requirement Levels, BCP 14, RFC 2119, March 1997. 
         
        [RFC2578]  McCloghrie, K., Ed., Perkins, D., Ed., and J. 
                Schoenwaelder, Ed., "Structure of Management 
                Information Version 2 (SMIv2)", STD 58, RFC 2578, April 
                1999. 
         
        [RFC2579]  McCloghrie, K., Ed., Perkins, D., Ed., and J. 
                Schoenwaelder, Ed., "Textual Conventions for SMIv2", 
                STD 58, RFC 2579, April 1999. 
         
        [RFC2580]  McCloghrie, K., Perkins, D., and J. Schoenwaelder, 
                "Conformance Statements for SMIv2", STD 58, RFC 2580, 
                April 1999. 
      
        [RFC3621] Berger, A., and D. Romascanu, "Power Ethernet MIB", 
                RFC3621, December 2003. 
      
        [RFC4133]  Bierman, A. and K. McCloghrie, "Entity MIB (Version 
                3)", RFC 4133, August 2005. 
         
         
        [LLDP-MED-MIB]  ANSI/TIA-1057, "The LLDP Management Information 
                Base extension module for TIA-TR41.4 media endpoint 
                discovery information", July 2005. 
         
        [EMAN-AWARE-MIB] J. Parello, and B. Claise, "draft-ietf-eman-
                energy-aware-mib-02 ", work in progress, July 2011. 
      
         
      15.3. Informative References 

         
      
      
     <Claise, et. Al>        Expires April 31, 2012           [Page 74] 
         

     Internet-Draft <Power and Energy Monitoring MIB>   October 2011 
      
        [RFC1628] S. Bradner, "UPS Management Information Base", RFC 
                1628, May 1994  
         
        [RFC3410]  Case, J., Mundy, R., Partain, D., and B. Stewart, 
                "Introduction and Applicability Statements for Internet 
                Standard Management Framework ", RFC 3410, December 
                2002. 
          
        [RFC3418]  Presun, R., Case, J., McCloghrie, K., Rose, M, and S. 
                Waldbusser, "Management Information Base (MIB) for the 
                Simple Network Management Protocol (SNMP)", RFC3418, 
                December 2002. 
         
        [RFC3433]  Bierman, A., Romascanu, D., and K. Norseth, "Entity 
                Sensor Management Information Base", RFC 3433, December 
                2002. 
         
        [RFC4268]  Chisholm, S. and D. Perkins, "Entity State MIB", RFC 
                4268,November 2005. 
         
        [RFC5226]  Narten, T. Alverstrand, H., A. and K. McCloghrie, 
                "Guidelines for Writing an IANA Considerations Section 
                in RFCs ", BCP 26, RFC 5226, May 2008. 
         
        [EMAN-REQ] Quittek, J., Winter, R., Dietz, T., Claise, B., and 
                M. Chandramouli, " Requirements for Energy Management 
                ", draft-ietf-eman-requirements-03 (work in 
                progress),July  2011. . 
         
        [EMAN-FRAMEWORK] Claise, B., Parello, J., Schoening, B., and J. 
                Quittek, "Energy Management Framework", draft-ietf-
                eman-framework-02 , July 2011. 
         
        [EMAN-MONITORING-MIB] M. Chandramouli, Schoening, B., Dietz, T., 
                Quittek, J. and B. Claise  "Energy and Power Monitoring 
                MIB ", draft-claise-energy-monitoring-mib-09, July 
                2011. 
         
        [EMAN-AS] Tychon, E., Laherty, M., and B. Schoening, "Energy 
                Management (EMAN) Applicability Statement", draft-
                tychon-eman-applicability-statement-02, work in 
                progress, June 2011. 
         
        [ACPI] "Advanced Configuration and Power Interface 
                Specification",http://www.acpi.info/DOWNLOADS/ACPIspec3
                0b.pdf  
         

      
      
     <Claise, et. Al>        Expires April 31, 2012           [Page 75] 
         

     Internet-Draft <Power and Energy Monitoring MIB>   October 2011 
      
        [DMTF] "Power State Management Profile DMTF  DSP1027  Version 
                2.0"  December 2009     
                http://www.dmtf.org/sites/default/files/standards/docum
                ents/DSP1027_2.0.0.pdf 
         
        [IEEE1621]  "Standard for User Interface Elements in Power 
                Control of Electronic Devices Employed in 
                Office/Consumer Environments", IEEE 1621, December 
                2004.  
         
        [IEC.61850-7-4] International Electrotechnical Commission, 
                "Communication networks and systems for power utility 
                automation Part 7-4: Basic communication structure 
                Compatible logical node classes and data object 
                classes", 2010. 
         
        [IEC.62053-21] International Electrotechnical Commission, 
                "Electricity metering equipment (a.c.) Particular 
                requirements Part 22: Static meters for active energy  
                (classes 1 and 2)", 2003. 
         
        [IEC.62053-22]International Electrotechnical Commission, 
                "Electricity metering equipment (a.c.) Particular 
                requirements Part 22: Static meters for active energy  
                (classes 0,2 S and 0,5 S)", 2003. 
         
         
     Authors' Addresses 
         
       
      Mouli Chandramouli 
      Cisco Systems, Inc. 
      Sarjapur Outer Ring Road 
      Bangalore, 
      IN 
       
      Phone: +91 80 4426 3947 
      Email: moulchan@cisco.com 
       
       
      Brad Schoening 
      44 Rivers Edge Drive 
      Little Silver, NJ 07739 
      US 
      Email: brad@bradschoening.com 
       
       

      
      
     <Claise, et. Al>        Expires April 31, 2012           [Page 76] 
         

     Internet-Draft <Power and Energy Monitoring MIB>   October 2011 
      
      Juergen Quittek 
      NEC Europe Ltd. 
      NEC Laboratories Europe 
      Network Research Division 
      Kurfuersten-Anlage 36 
      Heidelberg  69115 
      DE 
       
      Phone: +49 6221 4342-115 
      Email: quittek@neclab.eu 
       
      Thomas Dietz 
      NEC Europe Ltd. 
      NEC Laboratories Europe 
      Network Research Division 
      Kurfuersten-Anlage 36 
      Heidelberg  69115 
      DE 
       
      Phone: +49 6221 4342-128 
      Email: Thomas.Dietz@neclab.eu 
       
      Benoit Claise 
      Cisco Systems, Inc. 
      De Kleetlaan 6a b1 
      Diegem 1813 
      BE 
          
      Phone: +32 2 704 5622 
      Email: bclaise@cisco.com 
      
       
       
         

       

      
      
     <Claise, et. Al>        Expires April 31, 2012           [Page 77]