draft-ietf-eman-framework-06
Network Working Group                                  B. Claise 
     Internet-Draft                                        J. Parello 
     Intended Status: Informational               Cisco Systems, Inc. 
     Expires: March 12, 2013                             B. Schoening 
                                                Independent Consultant 
                                                            J. Quittek 
                                                       NEC Europe Ltd. 
                                                            B. Nordman 
                                                     Lawrence Berkeley 
                                                   National Laboratory 

                                                     October 21, 2012 

                                            

      
                        Energy Management Framework 
                       draft-ietf-eman-framework-06 

     Status of this Memo 

        This Internet-Draft is submitted to IETF in full conformance 
        with the provisions of BCP 78 and BCP 79.  
         
        Internet-Drafts are working documents of the Internet 
        Engineering Task Force (IETF), its areas, and its working 
        groups.  Note that other groups may also distribute working 
        documents as Internet-Drafts.  
         
        Internet-Drafts are draft documents valid for a maximum of six 
        months and may be updated, replaced, or obsoleted by other 
        documents at any time.  It is inappropriate to use Internet-
        Drafts as reference material or to cite them other than as  
        "work in progress."  
         
        The list of current Internet-Drafts can be accessed at 
        http://www.ietf.org/ietf/1id-abstracts.txt  
         
        The list of Internet-Draft Shadow Directories can be accessed  
        at http://www.ietf.org/shadow.html  
         
        This Internet-Draft will expire on March, 2013.                     


      
     <Claise, et. Al>         Expires Mar 12 2013          [Page 1] 

     Internet-Draft           <EMAN Framework>        October 2012 
      
     Copyright Notice 
      
        Copyright (c) 2012 IETF Trust and the persons identified as 
        the document authors.  All rights reserved. 
         
        This document is subject to BCP 78 and the IETF Trust's Legal 
        Provisions Relating to IETF Documents 
        (http://trustee.ietf.org/license-info) in effect on the date 
        of publication of this document.  Please review these 
        documents carefully, as they describe your rights and 
        restrictions with respect to this document.  Code Components 
        extracted from this document must include Simplified BSD 
        License text as described in Section 4.e of the Trust Legal 
        Provisions and are provided without warranty as described in 
        the Simplified BSD License. 
         
      
      
     Abstract 

        This document defines a framework for providing Energy 
        Management for devices within or connected to communication 
        networks, and components thereof.  The framework defines an 
        Energy Management Domain as a set of Energy Objects, for which 
        each Energy Object is identified, classified and given 
        context.   Energy Objects can be monitored and/or controlled 
        with respect to Power, Power State, Energy, Demand, Power 
        Quality, and battery.  Additionally the framework models 
        relationships and capabilities between Energy Objects.   
         
         
         
         
         
         
      
         
                                            


      
      
     <Claise, et. Al>         Expires Mar 12,2013          [Page 2] 
         

     Internet-Draft           <EMAN Framework>        October 2012 
      
      
     Table of Contents 
         
        1. Introduction............................................ 5 
           1.1. Energy Management Document Overview................ 6 
        2. Terminology............................................. 6 
           Device.................................................. 6 
           Component............................................... 6 
           Energy Management....................................... 7 
           Energy Management System (EnMS)......................... 7 
           ISO Energy Management System............................ 8 
           Energy.................................................. 8 
           Power................................................... 8 
           Demand.................................................. 9 
           Power Characteristics................................... 9 
           Power Quality........................................... 9 
           Electrical Equipment................................... 10 
           Non-Electrical Equipment (Mechanical Equipment)........ 10 
           Energy Object.......................................... 10 
           Electrical Energy Object............................... 10 
           Non-Electrical Energy Object........................... 11 
           Energy Monitoring...................................... 11 
           Energy Control......................................... 11 
           Provide Energy:........................................ 11 
           Receive Energy:........................................ 11 
           Power Interface........................................ 11 
           Energy Management Domain............................... 12 
           Energy Object Identification........................... 12 
           Energy Object Context.................................. 12 
           Energy Object Relationship............................. 13 
           Aggregation Relationship............................... 13 
           Metering Relationship.................................. 13 
           Power Source Relationship.............................. 14 
           Proxy Relationship..................................... 14 
           Energy Object Parent................................... 14 
           Energy Object Child.................................... 14 
           Power State............................................ 15 
           Power State Set........................................ 15 
           Nameplate Power........................................ 15 
        3. Requirements & Use Cases............................... 16 
        4. Energy Management Issues............................... 17 

           4.1. Power Supply...................................... 18 
           4.2. Power and Energy Measurement...................... 23 
           4.3. Reporting Sleep and Off States.................... 24 
           4.4. Device and Device Components...................... 25 
           4.5. Non-Electrical Equipment.......................... 25 
        5. Energy Management Reference Model...................... 26 
           5.1. Reference Topologies.............................. 26 
      
      
     <Claise, et. Al>         Expires Mar 12,2013          [Page 3] 
         

     Internet-Draft           <EMAN Framework>        October 2012 
      
           5.2. Generalized Relationship Model.................... 35 
           5.3. Energy Object, Energy Object Components and 
           Containment Tree....................................... 37 
        6. Framework High Level Concepts and Scope................ 38 
           6.1. Energy Object and Energy Management Domain........ 39 
           6.2. Power Interface................................... 39 
           6.3. Energy Object Identification and Context.......... 40 
           6.4. Energy Object Relationships....................... 42 
           6.5. Energy Monitoring................................. 47 
           6.6. Energy Control.................................... 50 
        7. Structure of the Information Model: UML Representation. 54 
        8. Configuration.......................................... 59 
        9. Fault Management....................................... 60 
        10. Examples.............................................. 60 
           Example I: Simple Device with one Source............... 61 
           Example II: Multiple Inlets............................ 62 
           Example III: Multiple Sources.......................... 62 
        11. Relationship with Other Standards Development 
        Organizations............................................. 63 
           11.1. Information Modeling............................. 63 
        12. Security Considerations............................... 64 
           12.1 Security Considerations for SNMP.................. 64 
        13. IANA Considerations................................... 65 
        14. Acknowledgments....................................... 65 
        15. References............................................ 66 
           Normative References................................... 66 
           Informative References................................. 66 
         

      

        OPEN ISSUES: 
        Are Tracked via Issue Tracker. See 
        https://trac.tools.ietf.org/wg/eman/trac/report/1 

         
                          

      
      
     <Claise, et. Al>         Expires Mar 12,2013          [Page 4] 
         

     Internet-Draft           <EMAN Framework>        October 2012 
      
         
         
     1. Introduction 

        Network management is divided into the five main areas defined 
        in the ISO Telecommunications Management Network model: Fault, 
        Configuration, Accounting, Performance, and Security 
        Management (FCAPS) [X.700].  Absent from this management model 
        is any consideration of Energy Management, which is now 
        becoming a critical area of concern worldwide as seen in 
        [ISO50001].  
         
        Note that Energy Management has particular challenges in that 
        a power distribution network is responsible for the supply of 
        energy to various devices and components, while a separate 
        communication network is typically used to monitor and control 
        the power distribution network. 
         
        This document defines a framework for providing Energy 
        Management for devices within or connected to communication 
        networks.  The framework describes how to identify, classify 
        and provide context for a device in a communications network 
        from the point of view of Energy Management. 
      
        The identified device or identified components within a device 
        can then be monitored for Energy Management by obtaining 
        measurements for Power, Energy, Demand and Power Quality.  If 

        a device contains batteries, they can be also be monitored and 
        managed.  An Energy Object state can be monitored or 
        controlled by providing an interface expressed as one or more 
        Power State Sets.  The most basic example of Energy Management 
        is a single Energy Object reporting information about itself.  
        However, in many cases, energy is not measured by the Energy 
        Object itself, but by a meter located upstream in the power 
        distribution tree.  An example is a power distribution unit 
        (PDU) that measures energy received by attached devices and 
        may report this to an Energy Management System (EnMS).  
        Therefore, Energy Objects are recognized as having 
        relationships to other devices in the network from the point 
        of view of Energy Management.  These relationships include 
        Aggregation Relationship, Metering Relationship, Power Source 
        Relationship, and Proxy Relationship.  
      
                             

      
      
     <Claise, et. Al>         Expires Mar 12,2013          [Page 5] 
         

     Internet-Draft           <EMAN Framework>        October 2012 
      
     1.1. Energy Management Document Overview 

        The EMAN standard provides a set of specifications for Energy 
        Management.  This document specifies the framework, per the 
        Energy Management requirements specified in [EMAN-REQ]. 
         
        The applicability statement document [EMAN-AS] provides a list 
        of use cases, a cross-reference between existing standards and 
        the EMAN standard, and shows how this framework relates to 
        other frameworks. 
         
        The Energy-aware Networks and Devices MIB [EMAN-AWARE-MIB] 
        specifies objects for addressing Energy Object Identification, 
        classification, context information, and relationships from 
        the point of view of Energy Management. 
                           
        The Power and Energy Monitoring MIB [EMAN-MON-MIB] contains  
        objects for monitoring of Power, Energy, Demand, Power Quality 
        and Power States. 
         

        Further, the battery monitoring MIB [EMAN-BATTERY-MIB] defines 
        managed objects that provide information on the status of 
        batteries in managed devices. 
         
         
     2. Terminology 

        The key words "MUST", "MUST NOT", "REQUIRED", "SHALL", "SHALL 
        NOT", "SHOULD", "SHOULD NOT", "RECOMMENDED", "MAY", and 
        "OPTIONAL" in this document are to be interpreted as described 
        in RFC 2119 [RFC2119]. 
         
       EDITOR'S NOTE:  
        All terms are copied over from the version 6 of the [EMAN-
        TERMINOLOGY] draft.   
              
      
       Device 

          A piece of electrical or non-electrical equipment. 
          Reference: Adapted from [IEEE100]  
         

       Component 

          A part of an electrical or non-electrical equipment 
          (Device).  
      
      
     <Claise, et. Al>         Expires Mar 12,2013          [Page 6] 
         

     Internet-Draft           <EMAN Framework>        October 2012 
      
          Reference: Adapted from [ITU-T-M-3400] 

       Energy Management 

          Energy Management is a set of functions for 
          measuring, modeling, planning, and optimizing 
          networks to ensure that the network elements and 
          attached devices use energy efficiently and is 
          appropriate for the nature of the application and 
          the cost constraints of the organization.  
          Reference: Adapted from [ITU-T-M-3400] 
          Example: A set of computer systems that will poll 
          electrical meters and store the readings  
          NOTES:  

          1. Energy management refers to the activities, 
            methods, procedures and tools that pertain to 
            measuring, modeling, planning, controlling and 
            optimizing the use of energy in networked 
            systems [NMF]. 
          2. Energy Management is a management domain which 
            is congruent to any of FCAPS areas of 
            management in the ISO/OSI Network Management 
            Model [TMN]. Energy Management for 
            communication networks and attached devices is 
            a subset or part of an organization's greater 
            Energy Management Policies. 
           
       Energy Management System (EnMS) 

          An Energy Management System is a combination of 
          hardware and software used to administer a 
          network with the primary purpose being Energy 
          Management. 
          Reference: Adapted from [1037C] 
          Example: A single computer system that polls data 
          from devices using SNMP 
          NOTES: 
          1. An Energy Management System according to 
            [ISO50001] (ISO-EnMS) is a set of systems or 
            procedures upon which organizations can develop 
            and implement an energy policy, set targets, 
            action plans and take into account legal 

      
      
     <Claise, et. Al>         Expires Mar 12,2013          [Page 7] 
         

     Internet-Draft           <EMAN Framework>        October 2012 
      
            requirements related to energy use.  An EnMS 
            allows organizations to improve energy 
            performance and demonstrate conformity to 
            requirements, standards, and/or legal 
            requirements.   
          2. Example ISO-EnMS:  Company A defines a set of 
            policies and procedures indicating there should 
            exist multiple computerized systems that will 
            poll energy from their meters and pricing / 
            source data from their local utility. Company A 
            specifies that their CFO should collect 
            information and summarize it quarterly to be 

            sent to an accounting firm to produce carbon 
            accounting reporting as required by their local 
            government.  
          3. For the purposes of EMAN, the definition from 
            [1037C] is the preferred meaning of an Energy 
            Management System (EnMS).  The definition from 
            [ISO50001] can be referred to as ISO Energy 
            Management System (ISO-EnMS). 
           
       ISO Energy Management System 

         Energy Management System as defined by [ISO50001]  
          
       Energy  

          That which does work or is capable of doing work. 
          As used by electric utilities, it is generally a 
          reference to electrical energy and is measured in 
          kilo-watt hours (kWh). 
          Reference: [IEEE100] 
          NOTES 
          1. Energy is the capacity of a system to produce 
            external activity or perform work [ISO50001] 
           
       Power 

          The time rate at which energy is emitted, 
          transferred, or received; usually expressed in 
          watts (or in joules per second). 
          Reference: [IEEE100] 
      
      
     <Claise, et. Al>         Expires Mar 12,2013          [Page 8] 
         

     Internet-Draft           <EMAN Framework>        October 2012 
      
           
       Demand  

          The average value of power or a related quantity 
          over a specified interval of time. Note: Demand 
          is expressed in kilowatts, kilovolt-amperes, 
          kilovars, or other suitable units. 
           
          Reference: [IEEE100] 
          NOTES: 
          1.  Typically kilowatts.  

          2.  Energy providers typically bill by Demand 
          measurements as well as for maximum Demand per 
          billing periods.  Power values may spike during 
          short-terms by devices, but Demand measurements 
          recognize that maximum Demand does not equal 
          maximum Power during an interval. 
           
        Power Characteristics 

          Measurements of the electrical current, voltage, phase and 
          frequencies at a given point in an electrical power system. 

          Reference: Adapted from [IEC60050] 

          NOTES:  

          1. Power Characteristics is not intended to be judgmental 
          with respect to a reference or technical value and are 
          independent of any usage context. 

        Power Quality  

          Characteristics of the electric current, voltage, phase and 
          frequencies at a given point in an electric power system, 
          evaluated against a set of reference technical parameters. 
          These parameters might, in some cases, relate to the 
          compatibility between electricity supplied in an electric 
          power system and the loads connected to that electric power 
          system. 

          Reference: [IEC60050] 

          NOTES:  
      
      
     <Claise, et. Al>         Expires Mar 12,2013          [Page 9] 
         

     Internet-Draft           <EMAN Framework>        October 2012 
      
          1. Electrical characteristics representing power quality 
          information are typically required by customer facility 
          energy management systems. It is not intended to satisfy the 
          detailed requirements of power quality monitoring. Standards 
          typically also give ranges of allowed values; the 
          information attributes are the raw measurements, not the 
          "yes/no" determination by the various standards.  


          Reference: [ASHRAE-201] 

         

       Electrical Equipment 

          A general term including materials, fittings, 
          devices, appliances, fixtures, apparatus, 
          machines, etc., used as a part of, or in 
          connection with, an electric installation. 
          Reference: [IEEE100] 
        
       Non-Electrical Equipment (Mechanical Equipment) 

           A general term including materials, fittings, 
          devices appliances, fixtures, apparatus, 
          machines, etc., used as a part of, or in 
          connection with, non-electrical power 
          installations. 
          Reference: Adapted from [IEEE100] 
        
       Energy Object      

          An Energy Object (EO) is a piece of equipment 
          that is part of or attached to a communications 
          network that is monitored, controlled, or aids in 
          the management of another device for Energy 
          Management. 
           
        
       Electrical Energy Object  

          An Electrical Energy Object (EEO) is an Energy 
          Object that is a piece of Electrical Equipment  
           
            

      
      
     <Claise, et. Al>         Expires Mar 12,2013         [Page 10] 
         

     Internet-Draft           <EMAN Framework>        October 2012 
      
       Non-Electrical Energy Object  

          A Non-Electrical Energy Object (NEEO) an Energy 
          Object that is a piece of Non-Electrical 

          Equipment. 
           
           
       Energy Monitoring 

          Energy Monitoring is a part of Energy Management 
          that deals with collecting or reading information 
          from Energy Objects to aid in Energy Management.   
          NOTES:  
          1. This could include Energy, Power, Demand, Power 
            Quality, Context and/or Battery information. 
        
       Energy Control 

          Energy Control is a part of Energy Management 
          that deals with directing influence over Energy 
          Objects.  
        
          NOTES:  
          1. Typically in order to optimize or ensure its 
             efficiency. 
      
       Provide Energy: 

          An Energy Object "provides" energy to another Energy Object 
          if there is an energy flow from this Energy Object to the 
          other one. 

        Receive Energy: 

          An Energy Object "receives" energy from another Energy 
          Object if there is an energy flow from the other Energy 
          Object to this one. 

        Power Interface 

           A Power Interface (or simply interface) is an 
           interconnection among devices or components where energy 
           can be provided, received or both.  

        Power Inlet  
      
      
     <Claise, et. Al>         Expires Mar 12,2013         [Page 11] 
         

     Internet-Draft           <EMAN Framework>        October 2012 
      

           A Power Inlet (or simply inlet) is an interface at which a 
           device or component receives energy from another device or 
           component.  

        Power Outlet  

          A Power Outlet (or simply outlet) is an interface at which 
          a device or component provides energy to another device or 
          component. 

       Energy Management Domain 

          An Energy Management Domain is a set of Energy Objects 
          where all objects in the domain are considered one unit of 
          management.  
           
          For example, power distribution units and all of the 
          attached Energy Objects are part of the same Energy 
          Management Domain. 
        
          For example, all EEO's drawing power from the 
          same distribution panel with the same AC voltage 
          within a building, or all EEO's in a building for 
          which there is one main meter, would comprise an 
          Energy Management Domain.  
           
          NOTES:  
          1. Typically, this set will have as members all 
             EO's that are powered from the same source. 
      
           
       Energy Object Identification 

          Energy Object Identification is a set of 
          attributes that enable an Energy Object to be: 
          uniquely identified among all Energy Management 
          Domains; linked to other systems; classified as 
          to type, model, and or manufacturer 
        
       Energy Object Context 

          Energy Object Context is a set of attributes that 
          allow an Energy Management System to classify the 
          use of the Energy Object within an organization.   
          NOTES:  
      
      
     <Claise, et. Al>         Expires Mar 12,2013         [Page 12] 
         


     Internet-Draft           <EMAN Framework>        October 2012 
      
          1. The classification could contain the use and/or 
            the ranking of the Energy Object as compared to 
            other Energy Objects in the Energy Management 
            Domain. 
           
            
       Energy Object Relationship 

          An Energy Object Relationship is a functional association 
          among Energy Objects 
           
          NOTES 
          1. Relationships can be named and could include 
          Aggregation, Metering, Power Source, and Proxy. 
          2. The Energy Object is the noun or entity in the 
          relationship with the relationship described as the verb. 
           
          Example: If EO x is a piece of Electrical Equipment and EO 
          y is an electrical meter clamped onto x's power cord, then 
          x and y have a Metering Relationship. It follows that y 
          meters x and that x is metered by y. 
          Reference: Adapted from [CHEN] 
         

        Aggregation Relationship 

         
          An Aggregation Relationship is an Energy Object 
          Relationship where one Energy Object aggregates the Energy 
          Management information of one or more other Energy Objects. 
          These Energy Objects are referred to as having an 
          Aggregation Relationship.   
           
          NOTES:  
          Aggregate values may be obtained by collecting values from 
          multiple Energy Objects and producing a single value of 
          more significant meaning such as average, count, maximum, 
          median, minimum, mode and most commonly sum [SQL]. 
           
        Metering Relationship 

         
          A Metering Relationship is an Energy Object Relationship 
          where one Energy Object measures the Power or Energy of one 
          or more other Energy Objects. These Energy Objects are 
          referred to as having a Metering Relationship. 
           
      
      
     <Claise, et. Al>         Expires Mar 12,2013         [Page 13] 
         


     Internet-Draft           <EMAN Framework>        October 2012 
      
          Example: a PoE port on a switch measures the Power it 
          provides to the connected Energy Object. 
      
         
        Power Source Relationship 

        
          A Power Source Relationship is an Energy Object 
          Relationship where one Energy Object is the source of or 
          distributor of Power to one or more other Energy Objects. 
          These Energy Objects are referred to as having a Power 
          Source Relationship.   
           
          Example: a PDU provides power for a connected device. 
           
         
        Proxy Relationship 

           
          A Proxy Relationship is an Energy Object Relationship where 
          one Energy Object provides the Energy Management 
          capabilities on behalf of one or more other Energy Objects. 
          These Energy Objects are referred to as having a Proxy 
          Relationship.  
           
          Example: a protocol gateways device for Building Management 
          Systems (BMS) with subtended devices. 
           
           
       Energy Object Parent 

          An Energy Object Parent is an Energy Object that 
          participates in an Energy Object Relationships 
          and is considered as providing the capabilities 
          in the relationship.   
           
          Example: in a Metering Relationship, the Energy 
          Object that is metering is called the Energy 
          Object Parent, while the Energy Object that is 
          metered is called the Energy Object Child.  
           
        
       Energy Object Child 

          An Energy Object Child is an Energy Object that 
          participates in an Energy Object Relationships 
          and is considered as receiving the capabilities 
          in the relationship. 
      
      
     <Claise, et. Al>         Expires Mar 12,2013         [Page 14] 
         


     Internet-Draft           <EMAN Framework>        October 2012 
      
           
          Example: in a Metering Relationship, the Energy 
          Object that is metering is called the Energy 
          Object Parent, while the Energy Object that is 
          metered is called the Energy Object Child.  
           
      
       Power State 

          A Power State is a condition or mode of a device 
          that broadly characterizes its capabilities, 
          power consumption, and responsiveness to input. 
           
          Reference: Adapted from [IEEE1621]   
           
          NOTES:  
           
          1. A Power State can be seen as a power setting 
             of an Energy Object that influences the power 
             consumption, the available functionality, and 
             the responsiveness of the Energy Object.   
           
          2. A Power State can be viewed as one method for 
             Energy Control 
           
           
       Power State Set 

          A collection of Power States that comprise one 
          named or logical grouping of control is a Power 
          State Set.   
        
          Example: The states {on, off, and sleep} as 
          defined in [IEEE1621], or the 16 power states as 
          defined by the [DMTF] can be considered two 
          different Power State Sets. 
           
           
       Nameplate Power 

          The Nameplate Power is the nominal Power of a 
          device as specified by the device manufacturer.  
        
          NOTES:  
           
          1. This is typically determined via load testing 
             and is specified by the manufacturer as the 
             maximum value required for operating the 
      
      
     <Claise, et. Al>         Expires Mar 12,2013         [Page 15] 
         


     Internet-Draft           <EMAN Framework>        October 2012 
      
             device.  This is sometimes referred to as the 
             worst-case Power.  The actual or average Power 
             may be lower.  The Nameplate Power is 
             typically used for provisioning and capacity 
             planning. 
      
      
      
     3. Requirements & Use Cases  

        Requirements for Power and Energy monitoring for networking 
        devices are specified in [EMAN-REQ].  The Energy Management 
        use cases covered by this framework are covered in the EMAN 
        applicability statement document in [EMAN-AS].  Typically 
        requirements and use cases for communication networks cover 
        the devices that make up the communication network and 
        endpoints.  
         
        With Energy Management, there exists a wide variety of devices 
        that may be contained in the same deployments as a 
        communication network but comprise a separate facility, home, 
        or power distribution network.   

        Target devices for Energy Management are all Energy Objects 
        that can directly or indirectly be monitored or controlled by 
        an Energy Management System (EnMS) using the Internet 
        protocol, for example:  
            - Simple electrical appliances / fixtures  
            - Hosts, such as a PC, a datacenter server, or a printer 
            - Routers  
            - Switches 
            - A component within devices, such as a battery inside a 
        PC, a line card inside a switch, etc... 
            - Power over Ethernet (PoE) endpoints 
            - Power Distribution Units (PDU)  
            - Protocol gateway devices for Building Management Systems 
        (BMS) 
            - Electrical meters 
            - Sensor controllers with subtended sensors 
      
        There may also exist varying protocols deployed among these 
        power distributions and communication networks.  
         
        For an Energy Management framework to be useful, it should 
        also apply to these types of separate networks as they connect 
        and interact with a communications network.  
         

      
      
     <Claise, et. Al>         Expires Mar 12,2013         [Page 16] 
         


     Internet-Draft           <EMAN Framework>        October 2012 
      
        This is the first version of the IETF Energy Management 
        framework.  Though it already covers a wide range of use 
        cases, there are still a lot of potential ones that are not 
        covered, yet.  A simple example is the limitation to discrete 
        power states without parameters.  Some devices have energy-
        related properties that not well described with discrete power 
        states, for example a dimmer with a continuous power range 
        from 0%-100%.  Other devices may have even more parameters 
        than just a single percentage value.   
         
        This framework definces an informtion model containing various 
        values that are measured on a device for the purpose of 
        monitor and control. The framework does not cover setting 
        bounds or conditions for these values for the purpose of 
        policy management - for example specifying that power MUST NOT 
        exceed a limit. While implementations can set bounds and 
        notification when exceeding those bounds while monitored, 
        physically preventing a device to not exceed the bound is 
        beyond the scope of this framework. It is up to future updates 
        of this document to select more of such use-cases and to cover 
        them by extensions or revisions of the present framework. 
      
      
         
     4. Energy Management Issues 

        This section explains special issues of Energy Management 
        particularly concerning power supply, Power and Energy 
        metering, and the reporting of low Power States. 

        To illustrate the issues we start with a simple and basic 
        scenario with a single powered device that receives Energy and 
        that reports energy-related information about itself to an 
        Energy Management System (EnMS), see Figure 1 

         

                               +--------------------------+                           
                               | Energy Management System |                           
                               +--------------------------+                           
                                           ^  ^ 
                                monitoring |  | control 
                                           v  v 
                                    +-----------------+ 
                                    | powered device  | 
                                    +-----------------+ 

      
      
     <Claise, et. Al>         Expires Mar 12,2013         [Page 17] 
         


     Internet-Draft           <EMAN Framework>        October 2012 
      
                  Figure 1: Basic energy management scenario 
         

        The powered device may have local energy control mechanisms, 
        for example putting itself into a sleep mode when appropriate, 
        and it may receive energy control commands for similar 
        purposes from the EnMS.  Information reported from a powered 
        device to the EnMS includes at least the Power State of the 
        powered device (on, sleep, off, etc.). 

        This and similar cases are well understood and likely to 
        become very common for Energy Management.  They can be handled 
        with well established and standardized management procedures.  
        The only missing components today are standardized information 
        and data models for reporting and configuration, such as, for 
        example, energy-specific MIB modules [RFC2578] and YANG 
        modules [RFC6020]. 

        However, the nature of energy supply and use introduces some 
        issues that are special to Energy Management.  The following 
        subsections address these issues and illustrate them by 
        extending the basic scenario in Figure 1. 

         

     4.1. Power Supply 

        A powered device may supply itself with power.  Sensors, for 
        example, commonly have batteries or harvest Energy.  However, 
        most powered devices that are managed by an EnMS receive 
        external power. 
         
        While a huge number of devices receive Power from unmanaged 
        supply systems, the number of manageable power supply devices 
        is increasing. 
         
        In datacenters, many Power Distribution Units (PDUs) allow the 
        EnMS to switch power individually for each socket and also to 
        measure the provided Power.  Here there is a big difference to 
        many other network management tasks: In such and similar 
        cases, switching power supply for a powered device or 
        monitoring its power is not done by communicating with the 
        actual powered device, but with an external power supply 
        device (in this case, the PDU). Note that those external power 
        supply devices may be an external power meter). 
         
        Consequently, a standard for Energy Management must not just 
        cover the powered devices that provide services for users, but 
      
      
     <Claise, et. Al>         Expires Mar 12,2013         [Page 18] 
         


     Internet-Draft           <EMAN Framework>        October 2012 
      
        also the power supply devices (which are powered devices as 
        well) that monitor or control the power supply for other 
        powered devices. 
         
        A very simple device such as a plain light bulb can be 
        switched on or off only by switching its power supply.  More 
        complex devices may have the ability to switch off themselves 
        or to bring themselves to states in which they consume very 
        little power.  For these devices as well, it is desirable to 
        monitor and control their power supply. 
         
        This extends the basic scenario from Figure 1 by a power 
        supply device, see Figure 2. 
         

                    +-----------------------------------------+ 
                    |         energy management system        | 
                    +-----------------------------------------+ 
                          ^  ^                       ^  ^ 
               monitoring |  | control    monitoring |  | control 
                          v  v                       v  v 
                    +--------------+        +-----------------+ 
                    | power supply |########| powered device  | 
                    +--------------+        +-----------------+ 

                            ######## power supply line 

                            Figure 2: Power Supply 
                                        
        The power supply device can be as simple as a plain power 
        switch.  It may offer interfaces to the EnMS to monitor and to 
        control the status of its power outlets, as with PDUs and 
        Power over Ethernet (PoE) [IEEE-802.3at] switches. 
         
        The relationship between supply devices and the powered 
        devices they serve creates several problems for managing power 
        supply: 
           o  Identification of corresponding devices 
              *  A given powered device may be need to identify the  
                 supplying power supply device. 
              *  A given power supply device may need to identify the 
                 corresponding supplied powered device(s). 
           o  Aggregation of monitoring and control for multiple 
        powered  
              devices 
              *  A power supply device may supply multiple powered  
                 devices with a single power supply line. 

      
      
     <Claise, et. Al>         Expires Mar 12,2013         [Page 19] 
         


     Internet-Draft           <EMAN Framework>        October 2012 
      
           o  Coordination of power control for devices with multiple  
              power inlets 
              *  A powered device may receive power via multiple power  
                 lines controlled by the same or different power 
        supply devices. 
         

     4.1.1 Identification of Power Supply and Powered Devices 

        When a power supply device controls or monitors power supply 
        at one of its power outlets, the effect on other devices is 
        not always clear without knowledge about wiring of power 
        lines.  The same holds for monitoring.  The power supplying 
        device can report that a particular socket is powered, and it 
        may even be able to measure power and conclude that there is a 
        consumer drawing power at that socket, but it may not know 
        which powered device receives the provided power. 
         
        In many cases it is obvious which other device is supplied by 
        a certain outlet, but this always requires additional 
        (reliable) information about power line wiring.  Without 
        knowing which device(s) are powered via a certain outlet, 
        monitoring data are of limited value and the consequences of 
        switching power on or off may be hard to predict. 
         
        Even in well organized operations, powered devices' power 
        cords can be plugged into the wrong socket, or wiring plans 
        changed without updating the EnMS accordingly. 
         
        For reliable monitoring and control of power supply devices, 
        additional information is needed to identify the device(s) 
        that receive power provided at a particular monitored and 
        controlled socket. 
         
        This problem also occurs in the opposite direction.  If power 
        supply control or monitoring for a certain device is needed, 
        then the supplying power supply device has to be identified. 
         
        To conduct Energy Management tasks for both power supply 
        devices and other powered devices, sufficiently unique 
        identities are needed, and knowledge of their power supply 
        relationship is required. 
         

     4.1.2 Multiples Devices Supplied by a Single Power Line 

        The second fundamental problem is the aggregation of 
        monitoring and control that occurs when multiple powered 
      
      
     <Claise, et. Al>         Expires Mar 12,2013         [Page 20] 
         


     Internet-Draft           <EMAN Framework>        October 2012 
      
        devices are supplied by a single power supply line.  It is 
        often required that the EnMS has the full list of powered 
        devices connected to a single outlet as in Figure 3. 
         

         

                      +---------------------------------------+ 
                      |       energy management system        | 
                      +---------------------------------------+ 
                         ^  ^                       ^  ^ 
              monitoring |  | control    monitoring |  | control 
                         v  v                       v  v 
                      +--------+        +------------------+ 
                      | power  |########| powered device 1 | 
                      | supply |   #    +------------------+-+ 
                      +--------+   #######| powered device 2 | 
                                     #    +------------------+-+ 
                                     #######| powered device 3 | 
                                            +------------------+ 

                 Figure 3: Multiple Powered Devices Supplied  
                             by Single Power Line 
         

        With this list, the single status value has clear meaning and 
        is the sum of all powered devices.  Control functions are 
        limited by the fact that supply for the concerned devices can 
        only be switched on or off for all of them at once.  
        Individual control at the supply is not possible. 
         
        If the full list of devices powered by a single supply line is 
        not known by the controlling power supply device, then control 
        of power supply is problematic, because the consequences of 
        control actions can only be partially known. 
         

     4.1.3 Multiple Power Supply for a Single Powered Device 

        The third problem arises from the fact that there are devices 
        with multiple power supplies.  Some have this for redundancy 
        of power supply, some for just making internal power 
        converters (for example, from AC mains power to DC internal 
        power) redundant, and some because the capacity of a single 
        supply line is insufficient. 
         

      
      
     <Claise, et. Al>         Expires Mar 12,2013         [Page 21] 
         


     Internet-Draft           <EMAN Framework>        October 2012 
      
                   +----------------------------------------------+ 
                   |          energy management system            | 
                   +----------------------------------------------+ 
                       ^  ^              ^  ^              ^  ^ 
                  mon. |  | ctrl.   mon. |  | ctrl.   mon. |  | ctrl. 
                       v  v              v  v              v  v 
                   +----------+      +----------+      +----------+ 
                   | power    |######| powered  |######| power    | 
                   | supply 1 |######| device   |      | supply 2 | 
                   +----------+      +----------+      +----------+ 

          Figure 4: Multiple Power Supply for Single Powered Device 
         
        The example in Figure 4 does not necessarily show a real world 
        scenario, but it shows the two cases to consider: 
           o  multiple power supply lines between a single power 
        supply  
              device and a powered device 
           o  different power supply devices supplying a single 
        powered     
              device 
        In any such case there may be a need to identify the supplying 
        power supply device individually for each power inlet of a 
        powered device. 
         
        Without this information, monitoring and control of power 
        supply for the powered device may be limited. 
         
         
     4.1.4 Bidirectional Power Interfaces 

        Low wattage DC systems may allow power to be delivered bi-
        directionally.  Energy stored in batteries on one device can 
        be delivered back to a power hub which redirects the current 
        to power another device.  In this situation, the interface can 
        function as both an inlet and outlet.   
         
        The framework for Energy Management introduces the notion of  
        Power Interface, which can model a power inlet and a power 
        outlet, depending on the conditions.  The Power Interface 
        reports power direction, as well as the energy received, 
        supplied and the net result. 
         

     4.1.5 Relevance of Power Supply Issues 

        In some scenarios, the problems with power supply do not exist 
        or can be sufficiently solved.  With Power over Ethernet (PoE) 
      
      
     <Claise, et. Al>         Expires Mar 12,2013         [Page 22] 
         


     Internet-Draft           <EMAN Framework>        October 2012 
      
        [IEEE-802.3at], there is always a one-to-one relationship 
        between a Power Sourcing Equipment (PSE) and a Powered Device 
        (PD).  Also, the Ethernet link on the line used for powering 
        can be used to identify the two connected devices. 
         
        For supply of AC mains power, the three problems described 
        above cannot be solved in general.  There is no commonly 
        available protocol or automatic mechanism for identifying 
        endpoints of a power line. 
         
        And, AC power lines support supplying multiple powered devices 
        with a single line and commonly do. 
         

     4.1.6 Remote Power Supply Control 

        There are three ways for an energy management system to change 
        the Power State of an powered devices.  First is for the EnMS 
        to provide policy or other useful information (like the 
        electricity price) to the powered device for it to use in 
        determining its Power State.  The second is sending the 
        powered devices a command to switch to another Power State.  
        The third is to utilize an upstream device (to the powered 
        device) that has capabilities to switch on and off power at 
        its outlet. 
         
        Some Energy Objects do not have capabilities for receiving 
        commands or changing their Power States by themselves.  Such 
        Energy Objects may be controlled by switching on and off the 
        power supply for them and so have particular need for the 
        third method. 
         
        In Figure 4, the power supply can switch on and off power at 
        its power outlet and thereby switch on and off power supply 
        for the connected powered device. 
         

     4.2. Power and Energy Measurement 

        Some devices include hardware to directly measure their Power 
        and Energy consumption.  However, most common networked 
        devices do not provide an interface that gives access to 
        Energy and Power measurements.  Hardware instrumentation for 
        this kind of measurements is typically not in place and adding 
        it incurs an additional cost. 
         
        With the increasing cost of Energy and the growing importance 
        of Energy Monitoring, it is expected that in future more 
      
      
     <Claise, et. Al>         Expires Mar 12,2013         [Page 23] 
         


     Internet-Draft           <EMAN Framework>        October 2012 
      
        devices will include instrumentation for power and energy 
        measurements, but this may take quite some time. 
         

     4.2.1 Local Estimates 

        One solution to this problem is for the powered device to 
        estimate its own Power and consumed Energy.  For many Energy 
        Management tasks, getting an estimate is much better than not 
        getting any information at all. 

        Estimates can be based on actual measured activity level of a 
        device or it can just depend on the power state (on, sleep, 
        off, etc.).       

        The advantage of estimates is that they can be realized 
        locally and with much lower cost than hardware 
        instrumentation.  Local estimates can be dealt with in 
        traditional ways.  They don't need an extension of the basic 
        scenarios above.  However, the powered device needs an energy 
        model of itself to make estimates. 

         

     4.2.2 Management System Estimates 

        Another approach to the lack of instrumentation is estimation 
        by the EnMS.  The EnMS can estimate Power based on basic 
        information on the powered device, such as the type of device, 
        or also its brand/model and functional characteristics. 
         
        Energy estimates can combine the typical power level by Power 
        State with reported data about the Power State. 
         
        If the EnMS has a detailed energy model of the device, it can 
        produce better estimates including the actual power state and 
        actual activity level of the device.  Such information can be 
        obtained by monitoring the device with conventional means of 
        performance monitoring. 
         
         
     4.3. Reporting Sleep and Off States 

        Low power modes pose special challenges for energy reporting 
        because they may preclude a device from listening to and 
        responding to network requests.  Devices may still be able to 
        reliably track energy use in these modes, as power levels are 

      
      
     <Claise, et. Al>         Expires Mar 12,2013         [Page 24] 
         


     Internet-Draft           <EMAN Framework>        October 2012 
      
        usually static and internal clocks can track elapsed time in 
        these modes. 
         
        Some devices do have out-of-band or proxy abilities to respond 
        to network requests in low-power modes.  Others could use 
        proxy abilities in an energy management protocol to improve 
        this reporting, particularly if the powered device sends out 
        notifications of power state changes. 
         
     4.4. Device and Device Components 

        While the primary focus of energy management is entire powered 
        Devices,  sometimes it is necessary or desirable to manage 
        Components such as line cards, fans, disks, etc.   
         
        The concept of a Power Interface may not apply to Components 
        since they may receive Energy from a pool available from the 
        encompassing device.  For example, a DC-powered blade server 
        in a chassis may have its own identity on the network and be 
        managed as a single device but its energy may be received from 
        a shared power source among all blades in the chassis. 
         
         
     4.5. Non-Electrical Equipment 

        The primary focus of this framework is for the management of 
        Electrical Equipment.  Some Non-Electrical Equipment may be 
        connected to a communication networks and could have their 
        energy managed if normalize to the electrical units for power 
        and energy. 
         
        Some examples of Non-Electrical Equipment that may be 
        connected to a communication network are: 
        1) A controller for compressed air.  The controller is 
          electrical only for its network connection.  The controller 
          is fueled by natural gas and produces compressed air.  The 
          energy transferred via compressed air is distributed to 
          devices on a factory floor via a Power Interface: tools 
          (drills, screwdrivers, assembly line conveyor belts). The 
          energy measured is non-electrical (compressed air).   
          EDITOR'S NOTE: Note that, in such as case, some might argue 
          that the "energy interface" term might be more accurate than 
          Power Interface. To be discussed. 
            
        2) A controller for steam. The controller is electrical for its 
          network attachment but it burns tallow and produces steam to 
          subtended boilers. The energy is non-electrical (steam). 
           
      
      
     <Claise, et. Al>         Expires Mar 12,2013         [Page 25] 
         


     Internet-Draft           <EMAN Framework>        October 2012 
      
        3) A controller or regulator for gas. The controller is 
          electrical for its network attachment but it has physical 
          non-electrical components for control. The energy is non-
          electrical (BTU). 
         
     5. Energy Management Reference Model 

        The scope of this framework is to enable network and network-
        attached devices to be administered for Energy Management.  
        The framework recognizes that in complex deployments Energy 
        Objects may communicate over varying protocols.  For example 
        the communications network may use IP Protocols (SNMP) but 
        attached Energy Object Parent may communicate to Energy Object 
        Children over serial communication protocols like BACNET, 
        MODBUS etc.  The likelihood of getting these different 
        topologies to convert to a single protocol is not very high 
        considering the rate of upgrades of facilities and energy 
        related devices. Therefore the framework must address the 
        simple case of a uniform IP network and a more complex mixed 
        topology/deployment. 
         
        In this section we will describe the topologies that can exist 
        when describing a device, components and the relationships 
        among them in an Energy Management Domain. 
         
        We will then generalize those topologies by using an 
        information model based upon relationships. The most abstract 
        and general relationship between devices is a Parent and Child 
        relationship. Specific types of relationships are defined and 
        used in concert to describe the topologies of an Energy 
        Management Domain. 
         
     5.1. Reference Topologies 

        The reference model defines physical and logical topologies of 
        devices and the relationship among them in a communication 
        network. 

        The physical topology defined by the model defines 
        relationships between devices that reflect provisioning,  
        transfer of energy, and aid in management. 

        Logical topologies concern monitoring and controlling devices 
        and covers metering of energy and power, reporting information 
        relevant for energy management, and energy-related control of 
        devices. 

      
      
     <Claise, et. Al>         Expires Mar 12,2013         [Page 26] 
         


     Internet-Draft           <EMAN Framework>        October 2012 
      
     5.1.1 Power Source Topology 

        As described in Section 4, the power source(s) of a device  is 
        important for energy management. The energy management 
        reference model addresses this by a "Power Source" 
        Relationship. This is a relationship among devices providing 
        energy and devices receiving energy. 

        A simple example is a PoE PSE, for example, an Ethernet 
        switch, providing power to a PoE PD, for example, a desktop 
        phone.  Here the switch provides energy and the phone receives 
        energy.  This relationship can be seen in the figure below. 

              +----------+   power source  +---------+ 

              |  switch  | <-------------- |  phone  | 

              +----------+                 +---------+ 

                        Figure 5: Simple Power Source  
                                        
        A single power provider can act as power source of multiple 
        power receivers.  An example is a power distribution unit 
        (PDU) providing AC power for multiple switches. 

         

              +-------+   power source  +----------+ 

              |  PDU  | <----------+--- | switch 1 | 

              +-------+            |    +----------+ 

                                   | 

                                   |    +----------+ 

                                   +--- | switch 2 | 

                                   |    +----------+ 

                                   | 

                                   |    +----------+ 

                                   +--- | switch 3 | 

                                        +----------+ 
      
      
     <Claise, et. Al>         Expires Mar 12,2013         [Page 27] 
         


     Internet-Draft           <EMAN Framework>        October 2012 
      
                       Figure 6: Multiple Power Source  
                            

        This level of modeling is sufficient if there is no need to 
        distinguish in monitoring and control between the individual 
        receivers at the switch. 

        However, if there is a need to monitor or control power supply 
        for individual receivers at the power provider, then a more 
        detailed level of modeling is needed. 

        Devices receive or provide energy at power interfaces 
        connecting them to a transmission medium.  .  The Power Source 
        relationship can be used also between power interfaces at the 
        power provider side as well as at the power receiver side.  
        The example below shows a power providing device with a power 
        interface (PI) per connected receiving device. 

         

              +-------+------+   power source  +----------+ 

              |       | PI 1 | <-------------- | switch 1 | 

              |       +------+                 +----------+ 

              |       |     

              |       +------+   power source  +----------+ 

              |  PDU  | PI 2 | <-------------- | switch 2 | 

              |       +------+                 +----------+ 

              |       |     

              |       +------+   power source  +----------+ 

              |       | PI 3 | <-------------- | switch 3 | 

              +-------+------+                 +----------+ 

                          

      
      
     <Claise, et. Al>         Expires Mar 12,2013         [Page 28] 
         


     Internet-Draft           <EMAN Framework>        October 2012 
      
         

                 Figure 7: Power Source with Power interfaces 

        Power interfaces may also be modeled at the receiving device, 
        for examples for consistency. 

         

              +-------+------+   power source  +----+----------+ 

              |       | PI 1 | <-------------- | PI | switch 1 | 

              |       +------+                 +----+----------+ 

              |       |     

              |       +------+   power source  +----+----------+ 

              |  PDU  | PI 2 | <-------------- | PI | switch 2 | 

              |       +------+                 +----+----------+ 

              |       |     

              |       +------+   power source  +----+----------+ 

              |       | PI 3 | <-------------- | PI | switch 3 | 

              +-------+------+                 +----+----------+ 

                Figure 8: Power Interfaces at Receiving Device 
         

         

        Power Source relationships are between peering devices and 
        their interfaces.  They are not transitive.  In the examples 
        below there is a PDU powering a switch powering a phone. 

         

              +-------+   power   +--------+   power   +---------+ 

              |  PDU  | <-------- | switch | <-------- |  phone  | 

              +-------+   source  +--------+   source  +---------+ 

      
      
     <Claise, et. Al>         Expires Mar 12,2013         [Page 29] 
         


     Internet-Draft           <EMAN Framework>        October 2012 
      
                    Figure 9: Power Source Non-Transitive  
         

        Power Source Relationships are between the PDU and the switch 
        and between the switch and the phone.   

        Power Source Relationships are between the PDU and the 
        switchand between the switch and the phone.  Consequently, 
        there is logically exists a power source relation between the 
        PDU and the phone. 

              +-------+   power   +--------+   power   +---------+ 

              |  PDU  | <-------- | switch | <-------- |  phone  | 

              +-------+   source  +--------+   source  +---------+ 

                  ^                                          | 

                  |              power source                | 

                  +------------------------------------------+ 

                      Figure 10: Power Source Transitive  
         

     5.1.2 Metering Topology 

        Metering Between Two Device 

        The power metering topology between two devices is closely 
        related to the power source topology.  It is based on the 
        assumption that in many cases the power provided and the power 
        received is the same for both peers of a power source 
        relationship.  Then power measured at one end can be taken as 
        the actual power value at the other end.  Obviously, the same 
        applies to energy at both ends. 

        We define in this case a Power Metering Relationship between 
        two devices or power interfaces of devices that have a power 
        source relationship.  Power and energy values measured at one 
        peer of the power source relationship are reported for the 
        other peer as well. 

        The Power Metering Relationship is independent of the 
        direction of the Power source Relationship.  The more common 
        case is that values measured at the power provider are 
        reported for the power receiver, but also the reverse case is 
      
      
     <Claise, et. Al>         Expires Mar 12,2013         [Page 30] 
         


     Internet-Draft           <EMAN Framework>        October 2012 
      
        possible with values measured at the power receiver being 
        reported for the power provider. 

                                power                power 

           +-----+----------+   source  +--------+   source +-------+ 

           | PDU |PI + meter| <-------- | switch | <------- | phone | 

           +-----+----------+  metering +--------+         +-------+ 

                       ^                                           | 

                       |                                           | 

                       +-------------------------------------------+ 

                                        metering 

                    Figure 11: Direct and One Hop Metering  
                                        
        Metering At a Point in Power Distribution 

        A Sub-meter in a power distribution system can logically 
        measure the power or energy for all devices downstream from 
        the meter in the power distribution system. As such a Power 
        metering relationship can be seen as a relationship between a 
        meter and all of the devices downstream from the meter. 

        We define in this case a Power Metering relationship between a 
        metering device and devices downstream from the meter. 

        In cases where the Power Source topology cannot be discovered 
        or derived from the information available in the Energy 
        Management Domain, the Metering Topology can be used to relate 
        the upstream meter to the downstream devices in the absence of 
        specific power source relationships.  

        A metering relationship can occur between devices that are 
        notdirectly connected as shown by the figure below.   

         

        An analogy to communication networks would be modeling 
        connections between servers (meters) and clients (devices) 
        when the complete Layer 2 topology between the servers and 
        clients is not known. 

      
      
     <Claise, et. Al>         Expires Mar 12,2013         [Page 31] 
         


     Internet-Draft           <EMAN Framework>        October 2012 
      
                           +---------------+     

                           |   Device 1    |             

                           +---------------+  

                           |      PI       |  

                           +---------------+           

                                   |                  

                           +---------------+  

                           |   Meter       |  

                           +---------------+  

                                   . 

                                   : 

            +----------+   +----------+   +-----------+   

            | Device A |   | Device B |   | Device C  |  

            +----------+   +----------+   +-----------+   

                     Figure 12: Complex Metering Topology 

     5.1.3 Proxy Topology 

        Some devices may provide energy management capabilities on 
        behalf of other devices. For example a controller may 
        logically model power interfaces but the physical topology may 
        require that the controller communicate to another device 
        using a BMS protocol. These subtended devices that are 
        represented as power interfaces may be directly connected or 
        may be controlled over a communication network with no direct 
        connection. 

        While the EnMS may look at the logical representation of the 
        controller as a device with power interfaces, it may require 
        to report the physical topology and relationship to the 
        subtended devices. To model this we define a proxy 
        relationship to provide this visibility. 

         
      
      
     <Claise, et. Al>         Expires Mar 12,2013         [Page 32] 
         


     Internet-Draft           <EMAN Framework>        October 2012 
      
              +-------+------+   

              |       | PI 1 |  

              |       +------+  

              |       |     

              |       +------+  

              |  PDU  | PI 2 |  

              |       +------+  

              |       |     

              |       +------+  

              |       | PI 3 |  

              +-------+------+  

         

                          

      
      
     <Claise, et. Al>         Expires Mar 12,2013         [Page 33] 
         


     Internet-Draft           <EMAN Framework>        October 2012 
      
         

              +-------+  proxy   +----+----------+ 

              |       |<-------- | PI 1 Physical | 

              |       +          +----+----------+ 

              |       |     

              |       +   proxy   +----+----------+ 

              |  PDU  |<--------- | PI 2 Physical | 

              |       +           +----+----------+ 

              |       |     

              |       +   proxy   +----+----------+ 

              |       |<--------- | PI 3 Physical | 

              +-------+           +----+----------+ 

         

              Figure 13: Proxy Relationship Virtual and Physical 

     5.1.4 Aggregation Topology 

        Some devices in a domain can act as aggregation points for 
        other devices. For example a PDU contoller device may contain 
        the summation of power and energy readings for many PDU 
        devices. The PDU controller will have aggregate values for 
        power and energy for a  group of PDU devices.  

        This aggregation is independent of the physical power or 
        communication topology.  

        The functions that the aggregation point may perform include 
        values such as average, count, maximum, median, minimum or 
        listing (collection) of the aggregation. 

        We define in this case an Aggregation Relationship between a 
        device containing aggregate values for arbitrary groups of 
        other devices.  

      
      
     <Claise, et. Al>         Expires Mar 12,2013         [Page 34] 
         


     Internet-Draft           <EMAN Framework>        October 2012 
      
        While any power or energy values monitored from a device/power 
        interface can be seen as a summation for all devices 
        downstream from the monitoring device, the aggregation 
        relationship is used to represent a summation when it is not 
        obvious from the powering topology or a device to component 
        containment. 

         
     5.2. Generalized Relationship Model 

        As displayed in Figure 5, the most basic energy management 
        reference model is composed of an EnMS that obtains Energy 
        Management information from Energy Objects.  The Energy Object 
        (EO) returns information for Energy Management directly to the 
        EnMS.  
         
        The protocol of choice for Energy Management is SNMP, as three 
        MIBs are specified for Energy Management: the energy-aware MIB 
        [EMAN-AWARE-MIB], the energy monitoring MIB [EMAN-MON-MIB], 
        and the battery MIB [EMAN-BATTERY-MIB].  However, the EMAN 
        requirement document [EMAN-REQ] also requires support for a 
        push model distribution of time series values.  The following 
        diagrams mention IPFIX [RFC5101] as one possible solution for 
        implementing a push mode transfer, however this is for 
        illustration purposes only.  The EMAN standard does not 
        require the use of IPFIX and acknowledges that other 
        alternative solutions may also be acceptable. 
         
                            +---------------+     
                            |      EnMS     |                -   - 
                            +-----+---+-----+                ^   ^ 
                                  |   |                      |   | 
                                  |   |                      |S  |I 
                        +---------+   +----------+           |N  |P 
                        |                        |           |M  |F 
                        |                        |           |P  |I 
               +-----------------+      +--------+--------+  |   |X 
               | EO            1 |  ... | EO            N |  v   | 
               +-----------------+      +-----------------+  -   - 
                                               
                     Figure 14: Simple Energy Management  
         
         
        As displayed in the Figure 5, a more complex energy reference 
        model includes Energy Managed Object Parents and Children.  
        The Energy Managed Object Parent returns information for 
        themselves as well as information according to the Energy 
        Managed Object Relationships. 
      
      
     <Claise, et. Al>         Expires Mar 12,2013         [Page 35] 
         


     Internet-Draft           <EMAN Framework>        October 2012 
      
         
         
         
         
                           +---------------+     
                           |      EnMS     |               -   - 
                           +-----+--+------+               ^   ^ 
                                 |  |                      |   | 
                                 |  |                      |S  |I 
                    +------------+  +--------+             |N  |P 
                    |                        |             |M  |F 
                    |                        |             |P  |I 
            +------------------+     +------+-----------+  |   |X 
            | EO               |     | EO               |  v   | 
            | Parent 1         | ... | Parent N         |  -   - 
            +------------------+     +------------------+ 
                           |||                  .      
          One or           |||                  .      
          Multiple         |||                  .      
          Energy           |||                  .    
          Object           |||                  .      
          Relationship(s): |||                     
          - Aggregation    |||      +-----------------------+ 
          - Metering       |||------| EO Child 1            | 
          - Power Source   ||       +-----------------------+ 
          - Proxy          ||        
                           ||       +-----------------------+ 
                           ||-------| EO Child 2            | 
                           |        +-----------------------+ 
                           | 
                           |         
                           |--------           ...      
                           |         
                           |         
                           |        +-----------------------+ 
                           |--------| EO Child M            | 
                                    +-----------------------+ 
                                               
         
                                               
                  Figure 15: Complex Energy Management Model 
         
      
        While both the simple and complex Energy Management models 
        contain an EnMS, this framework doesn't impose any 
        requirements regarding a topology with a centralized EnMS or 
        one with distributed Energy Management via the Energy Objects 
        within the deployment. 
      
      
     <Claise, et. Al>         Expires Mar 12,2013         [Page 36] 
         


     Internet-Draft           <EMAN Framework>        October 2012 
      
         
        Given the pattern in Figure 6, the complex relationships 
        between Energy Objects can be modeled (refer also to section 
        5.3):   
             - A PoE device modeled as an Energy Object Parent with 
               the Power Source, Metering, and Proxy Relationships for 
               one or more Energy Object Children 
             - A PDU modeled as an Energy Object Parent with the Power 
               Source and Metering Relationships for the plugged in 
               Electrical Equipment (the Energy Object Children) 
             - Building management gateway, used as proxy for non IP 
               protocols, is modeled as an Energy Object Parent with 
               the Proxy Relationship, and potentially the Aggregation 
               Relationship to the managed Electrical Equipment  
             - Etc. 
      
     The communication between the Energy Object Parent and Energy 
     Object Children is out of the scope of this framework. 
         
     5.3. Energy Object, Energy Object Components and Containment Tree 

        The framework for Energy Management manages two different 
        types of Energy Objects: Devices and Components. A typical 
        example of an Device is a switch.  However, a port within the 
        switch, which provides Power to one end point, is also an 
        Energy Object if it meters the power provided.  A second 
        example is PC, which is a typical Device, while the battery 
        inside the PC is a Component, managed as an individual Energy 
        Object.  Some more examples of Components: power supply within 
        a router,  an outlet within a smart PDU, etc... 
         
        In the [EMAN-AWARE-MIB], each Energy Object is managed with an 
        unique value of the entPhysicalIndex index from the ENTITY-MIB 
        [RFC4133]  
         
        The ENTITY-MIB [RFC4133] specifies the notion of physical 
        containment tree, as: 
          "Each physical component may be modeled as 'contained' 
          within 
          another physical component.  A "containment-tree" is the 
          conceptual sequence of entPhysicalIndex values that uniquely 
          specifies the exact physical location of a physical 
          component within the managed system.  It is generated by 
          'following and recording' each 'entPhysicalContainedIn' 
          instance 'up the tree towards the root', until a value of 
          zero indicating no further containment is found." 

      
      
     <Claise, et. Al>         Expires Mar 12,2013         [Page 37] 
         


     Internet-Draft           <EMAN Framework>        October 2012 
      
         
        A Energy Object Component in the Energy Management context is 
        a special Energy Object that is a physical component as 
        specified by the ENTITY-MIB physical containment tree.  
         
         
         
     6. Framework High Level Concepts and Scope 

        Energy Management can be organized into areas of concern that 
        include: 
         
        - Energy Object Identification and Context - for modeling and 
        planning  
        - Energy Monitoring - for energy measurements 
        - Energy Control - for optimization 
        - Energy Procurement - for optimization of resources 
         
        While an EnMS may be a central point for corporate reporting, 
        cost, environmental impact, and regulatory compliance, Energy 
        Management in this framework excludes Energy procurement and 
        the environmental impact of energy use.  As such the framework 
        does not include: 
        - Manufacturing costs of an Energy Object in currency or 
        environmental units 
        - Embedded carbon or environmental equivalences of an Energy 
        Object 
        - Cost in currency or environmental impact to dismantle or 
        recycle an Energy Object 
        - Supply chain analysis of energy sources for Energy Object 
        deployment 
        - Conversion of the usage or production of energy to units 
        expressed from the source of that energy (such as the 
        greenhouse gas emissions associated with 1000kW from a diesel 
        source). 
         
        The next sections describe Energy Management organized into 
        the following areas: 
         
         - Energy Object and Energy Management Domain 
         - Energy Object Identification and Context  
         - Energy Object Relationships 
         - Energy Monitoring  
         - Energy Control   
         - Deployment Topologies 
        
         
      
      
     <Claise, et. Al>         Expires Mar 12,2013         [Page 38] 
         


     Internet-Draft           <EMAN Framework>        October 2012 
      
     6.1. Energy Object and Energy Management Domain 

        In building management, a meter refers to the meter provided 
        by the utility used for billing and measuring power to an 
        entire building or unit within a building.  A sub-meter refers 
        to a customer or user installed meter that is not used by the 
        utility to bill but instead used to get readings from sub 
        portions of a building.  

        An Energy Management Domain should map 1:1 with a metered or 
        sub-metered portion of the site.  An Energy Object is part of 
        a single Energy Management Domain.  The Energy Management 
        Domain MAY be configured on an Energy Object: the default 
        value is a zero-length string. 

        If all Energy Objects in the physical containment tree (see 
        ENTITY-MIB) are part of the same Energy Management Domain, 
        then it is safe to state that the Energy Object at the root of 
        that containment tree is in that Energy Management Domain. 

        An Energy Object Child may inherit the domain value from an 
        Energy Object Parent or the Energy Management Domain may be 
        configured directly in an Energy Object Child.  

         

     6.2. Power Interface 

        There are some similarities between Power Interfaces and 
        network interfaces.  A network interface can be used in 
        different modes, such as sending or receiving on an attached 
        line.  The Power Interface can be receiving or providing 
        power. 
         
        Most Power Interfaces never change their mode, but as the mode 
        is simply a recognition of the current direction of 
        electricity flow, there is no barrier to a mode change. 
         
        A power interface can have capabilities for metering power and 
        other electric quantities at the shared power transmission 
        medium. 
         
        This capability is modeled by an association to a power meter. 
         
        In analogy to MAC addresses of network interfaces, a globally 
        unique identifier is assigned to each Power Interface.   
         
        Physically, a Power Interface can be located at an AC power 
      
      
     <Claise, et. Al>         Expires Mar 12,2013         [Page 39] 
         


     Internet-Draft           <EMAN Framework>        October 2012 
      
        socket, an AC power cord attached to a device, an 8P8C (RJ45) 
        PoE socket, etc. 
           
         

     6.3. Energy Object Identification and Context  

     6.3.1 Energy Object Identification 

        Energy Objects MUST be associated with a value that uniquely 
        identifies the Energy Object among all the Energy Management 
        Domains within an EnMS.  A Universal Unique Identifier (UUID) 
        [RFC4122] MUST be used to uniquely and persistently identify 
        an Energy Object.  

        Every Energy Object SHOULD have a unique printable name within 
        the Energy Management Domain.  Possible naming conventions 
        are: textual DNS name, MAC-address of the device, interface 
        ifName, or a text string uniquely identifying the Energy 
        Object.  As an example, in the case of IP phones, the Energy 
        Object name can be the device's DNS name. 

         

     6.3.2 Context in General 

        In order to aid in reporting and in differentiation between 
        Energy Objects, each Energy Object optionally contains 
        information establishing its business, site, or organizational 
        context within a deployment, i.e. the Energy Object Context. 

         

     Context: Importance 

        An Energy Object can provide an importance value in the range 
        of 1 to 100 to help rank a device's use or relative value to 
        the site.  The importance range is from 1 (least important) to 
        100 (most important).  The default importance value is 1.   

        For example: A typical office environment has several types of 
        phones, which can be rated according to their business impact.  
        A public desk phone has a lower importance (for example, 10) 
        than a business-critical emergency phone (for example, 100).  
        As another example: A company can consider that a PC and a 
        phone for a customer-service engineer is more important than a 
        PC and a phone for lobby use. 

      
      
     <Claise, et. Al>         Expires Mar 12,2013         [Page 40] 
         


     Internet-Draft           <EMAN Framework>        October 2012 
      
        Although EnMS and administrators can establish their own 
        ranking, the following is a broad recommendation: 

        . 90 to 100 Emergency response  

        . 80 to 90 Executive or business-critical  

        . 70 to 79 General or Average  

        . 60 to 69 Staff or support  

        . 40 to 59 Public or guest  

        . 1  to 39 Decorative or hospitality 

         

     Context: Keywords 

        An Energy Object can provide a set of keywords.  These 
        keywords are a list of tags that can be used for grouping, 
        summary reporting within or between Energy Management Domains, 
        and for searching.  All alphanumeric characters and symbols 
        (other than a comma), such as #, (, $, !, and &, are allowed.  
        Potential examples are: IT, lobby, HumanResources, Accounting, 
        StoreRoom, CustomerSpace, router, phone, floor2, or 
        SoftwareLab.  There is no default value for a keyword. 

        Multiple keywords can be assigned to a device.  White spaces 
        before and after the commas are excluded, as well as within a 
        keyword itself. In such cases, the keywords are separated by 
        commas and no spaces between keywords are allowed.  For 
        example, "HR,Bldg1,Private". 

         

     Context: Role 

        An Energy Object can provide a "role description" string that 
        indicates the purpose the Energy Object serves in the EnMS.  
        This could be a string describing the context the device 
        fulfills in deployment. 

        Administrators can define any naming scheme for the role of a 
        device.  As guidance a two-word role that combines the service 
        the device provides along with type can be used [IPENERGY] 

      
      
     <Claise, et. Al>         Expires Mar 12,2013         [Page 41] 
         


     Internet-Draft           <EMAN Framework>        October 2012 
      
        Example types of devices: Router, Switch, Light, Phone, 
        WorkStation, Server, Display, Kiosk, HVAC. 

        Example Services by Line of Business: 

          Line of Business     Service 

           Education            Student, Faculty, Administration,  
                                Athletic 

          Finance              Trader, Teller, Fulfillment 

          Manufacturing        Assembly, Control, Shipping 

          Retail               Advertising, Cashier 

          Support              Helpdesk, Management 

          Medical              Patient, Administration, Billing 

        Role as a two-word string: "Faculty Desktop", "Teller Phone", 
        "Shipping HVAC", "Advertising Display", "Helpdesk Kiosk", 
        "Administration Switch". 

         

     6.4. Energy Object Relationships 

        Two Energy Objects MAY establish an Energy Object 
        Relationship. Within a relationship one Energy Object becomes 
        an Energy Object Parent while the other becomes an Energy 
        Object Child. 

        The Power Source Relationship gives the view the wiring 
        topology.  For example: a data center server receiving power 
        from two specific Power Interfaces from two different PDUs.  

        The Metering Relationship gives the view of the metering 
        topology.  Standalone meters can be placed anywhere in a power 
        distribution tree.  For example, utility meters monitor and 
        report accumulated power consumption of the entire building. 
        Logically, the metering topology overlaps with the wiring 
        topology, as meters are connected to the wiring topology.  A 
        typical example is meters that clamp onto the existing wiring. 

        The Proxy Relationship allows software objects to be inserted 
        into the wiring or metering topology to aid in managing 
        (monitoring and/or control) the Energy Domain.  
      
      
     <Claise, et. Al>         Expires Mar 12,2013         [Page 42] 
         


     Internet-Draft           <EMAN Framework>        October 2012 
      
        From a EnMS management point of view, this implies that there 
        is yet another management topology that EnMS will need to be 
        aware of. 

        In the ideal situation, the wiring, the metering, and the 
        management topologies overlap.  For Example: A Power-over-
        Ethernet (PoE) device (such as an IP phone or an access point) 
        is attached to a switch port.  The switch port is the source 
        of power for the attached device, so the Energy Object Parent 
        is the switch port, which acts as a Power Interface, and the 
        Energy Object Child is the device attached to the switch.  
        This Energy Object Parent (the switch) has three Energy Object 
        Relations with this Energy Object Child (the remote Energy 
        Object): Power Source Relationship, Metering Relationship, and 
        Proxy Relationship. 

        However, the three topologies (wiring, metering, and 
        management) don't always overlap.  For example, when a 
        protocol gateways device for Building Management Systems (BMS) 
        controls subtended devices, which themselves receive Power 
        from PDUs or wall sockets. 

        Note: The Aggregation Relationship is slightly different 
        compared to the other relationships (Power Source, Metering, 
        and Proxy Relationships) as this refers more to a management 
        function. 

        The communication between the parent and child for monitoring 
        or collection of power data is left to the device 
        manufacturer.  For example: A parent switch may use LLDP to 
        communicate with a connected child, and a parent lighting 
        controller may use BACNET to communicate with child lighting 
        devices. 

        The Energy Object Child MUST keep track of its Energy Object 
        Parent(s) along with the Energy Object Relationships type(s).  
        The Energy Object Parent MUST keep track of its Energy Object 
        Child(ren), along with the Energy Object Relationships 
        type(s). 

         

     6.4.1 Energy Object Children Discovery 

        There are multiple ways that the Energy Object Parent can 
        discover its Energy Object Children: : 
         

      
      
     <Claise, et. Al>         Expires Mar 12,2013         [Page 43] 
         


     Internet-Draft           <EMAN Framework>        October 2012 
      
          . In case of PoE, the Energy Object Parent automatically 
             discovers an Energy Object Child when the Child requests 
             power. 
          . The Energy Object Parent and Children may run the Link 
             Layer Discovery Protocol [LLDP], or any other discovery 
             protocol, such as Cisco Discovery Protocol (CDP).  The 
             Energy Object Parent might even support the LLDP-MED MIB 
             [LLDP-MED-MIB], which returns extra information on the 
             Energy Object Children.  
          . The Energy Object Parent may reside on a network 
             connected to a facilities gateway.  A typical example is 
             a converged building gateway, monitoring several other 
             devices in the building, and serving as a proxy between 
             SNMP and a protocol such as BACNET. 
          . A different protocol between the Energy Object Parent and 
             the Energy Object Children.  Note that the communication 
             specifications between the Energy Object Parent and 
             Children is out of the scope of this document.   
          
        However, in some situations, it is not possible to discover 
        the Energy Object Relationships, and they must be set 
        manually.  For example, in today' network, an administrator 
        must assign the connected Energy Object to a specific PDU 
        Power Interface, with no means of discovery other than that 
        manual connection. 
              
         
        When an Energy Object Parent is a Proxy, the Energy Object 
        Parent SHOULD enumerate the capabilities it is providing for 
        the Energy Object Child.  The child would express that it 
        wants its parent to proxy capabilities such as, energy 
        reporting, power state configurations, non physical wake 
        capabilities (such as WoL)), or any combination of 
        capabilities. 
         

     6.4.2 Energy Object Relationship Conventions and Guidelines 

         
        This Energy Management framework does not impose many "MUST" 
        rules related to Energy Object Relationships. There are always 
        corner cases that could be excluded with too strict 
        specifications of relationships. However, this Energy 
        Management framework proposes a series of guidelines, 
        indicated with "SHOULD" and "MAY". 
         
        Aggregation  
         
      
      
     <Claise, et. Al>         Expires Mar 12,2013         [Page 44] 
         


     Internet-Draft           <EMAN Framework>        October 2012 
      
        Aggregation relationships are intended to identify when one 
        device is used to accumulate values from other devices. 
        Typically this is for energy or power values among devices and 
        not for Components or Power Interfaces on the same device.  
        The intent of Aggregation relationships is to indicate when 
        one device is providing aggregate values for a set of other 
        devices when it is not obvious form the power source or simple 
        containment within a device. 
         
        Establishing aggregation relationships within the same device 
        would make modeling more complex and the aggregated values can 
        be implied form the use of Power Inlets, outlet and Energy 
        Object value son the same device. 
         
        Additionally since an EnMS is naturally a point of aggregation 
        for information in an Energy Management Domain it is not 
        necessary to model aggregation for an EnMS(s). 
         
        Aggregation SHOULD be used for power and energy. It MAY be 
        used for aggregation of other values from the information 
        model for example but the rules and logical ability to 
        aggregated each attribute is out of scope for this document. 
         
         
        - A Device SHOULD NOT establish an Aggregation Relationship 
          with a Component. 
        - A Device SHOULD NOT establish an Aggregation Relationship 
          with the Power Interfaces contained on the same device. 
        - A Device SHOULD NOT establish an Aggregation Relationship 
          with the an EnMS.  
        - Aggregators SHOULD log or provide notification in the case 
          of errors or missing values while performing aggregation. 
           
      
        Power Source 
         
        Power Source relationships are intended to identify the 
        connections between Power Interfaces. This is analogous to a 
        Layer 2 connection in networking devices (a "one hop" 
        connection). 
         
        The preferred modeling would be for Power Interfaces to 
        participate in Power Source Relationships.  
         
        It may happen that the some Energy Objects may not have the 
        capability to model Power Interfaces.  Therefore, it may 
        happen that a Power Source Relationship is established between 
        two Energy Objects or two non-connected Power Interfaces. 
      
      
     <Claise, et. Al>         Expires Mar 12,2013         [Page 45] 
         


     Internet-Draft           <EMAN Framework>        October 2012 
      
         
        While strictly speaking Components and Power Interfaces on the 
        same device do provide or receive energy from each other the 
        Power Source relationship is intended to show energy transfer 
        between Devices. Therefore relationship is implied on the same 
        Device. 
         
      
        - An Energy Object SHOULD NOT establish a Power Source 
          Relationship with a Component.  
        - A Power Source Relationship SHOULD be established with next 
          known Power Interface in the wiring topology.   
             o The next known Power Interface in the wiring topology 
               would be the next device implementing the framework. In 
               some cases the domain of devices under management may 
               include some devices that do not implement the 
               framework As such the Power Source relationship can be 
               established with the next device in the topology that 
               implements the framework and logically shows the Power 
               Source of the device. 
        - Transitive Power Source relationships SHOULD NOT be 
          established.  For examples if an Energy Object A has a Power 
          Source Relationship "Poweredby" with the Energy Object B, 
          and if the Energy Object B has a Power Source Relationship 
          "Poweredby" with the Energy Object C, then the Energy Object 
          A SHOULD NOT have a Power Source Relationship "PoweredBby" 
          the Energy Object C. 
         
        Metering Relationship 
         
        Metering Relationships are intended to show when one Device is 
        measuring the power or energy at a point in a power 
        distribution system. Since one point of a power distribution 
        system may cover many Devices with a complex wiring topology, 
        this relationship type can be seen as an arbitrary set. 
         
        Additionally, Devices may include metering hardware for 
        components and Power Interfaces or for the entire Device.  
         
        For example some PDU's may have the ability to measure Power 
        for each Power Interface (metered by outlet). Others may only 
        be able to control power at each Power Interface but only 
        measure Power at the Power Inlet and a total for all Power 
        Interfaces (metered by device).       
         
        In such cases a Device SHOULD be modeled as an Energy Object 
        that meters all of its Power Outlets and each Power Outlet MAY 
        be metered by the Energy Object representing the Device. 
      
      
     <Claise, et. Al>         Expires Mar 12,2013         [Page 46] 
         


     Internet-Draft           <EMAN Framework>        October 2012 
      
         
        - A Meter Relationship MAY be established with any other 
          Energy Object, Component, or Power Interface. 
        - Transitive Meter relationships MAY be used. 
        - When there is a series of meters for one Enegry Object, the 
          Energy Object MAY establish a relationship with one or more 
          of the meters.   
         
        Proxy 
         
        A Proxy relationship is intended to show when one Device is 
        providing the Energy Object capabilities for another Device 
        typically for protocol translations. Strictly speaking a  a 
        Component of a Device may provide the Energy Object 
        capabilities for that Device (and vice versa) this 
        relationship is intended to model relationships between 
        Devices.  
         
        - A Proxy relationship SHOULD be limited when possible to 
          Energy Objects of different Devices.  
            
     6.4.3 Energy Objects Relationship Extensions  

        This framework for Energy Management, is based on four Energy 
        Objects Relationships: Aggregation Relationship, Metering 
        Relationship, Power Source Relationship, and Proxy 
        Relationship.   

        This framework is defined with possible extension of new 
        Energy Objects Relationships in mind.  For example, a Power 
        Distribution Unit (PDU) that allows physical entities like 
        outlets to be "ganged" together as a logical entity for 
        simplified management purposes, could be modeled with a future 
        extension based on "gang relationship", whose semantic would 
        specify the Energy Objects grouping. 

         

     6.5. Energy Monitoring 

        For the purposes of this framework energy will be limited to 
        electrical energy in watt hours.  Other forms of Energy 
        Objects that use or produce non-electrical energy may be part 
        of an Energy Management Domain (See Section 4.5. )  but MUST 
        provide information converted to and expressed in watt hours. 

        An analogy for understanding power versus energy measurements 
        can be made to speed and distance in automobiles. Just as a 
      
      
     <Claise, et. Al>         Expires Mar 12,2013         [Page 47] 
         


     Internet-Draft           <EMAN Framework>        October 2012 
      
        speedometer indicates the rate of change of distance, a power 
        meter indicates the rate of transfer of energy. The odometer 
        in an automobile measures the cumulative distance traveled and 
        an energy meter indicates the accumulate energy transferred. 
        So a less formal statement of the analogy is that power meters 
        measures "speed" while energy meters measure "distance". 

        Each Energy Object will have information that describes power 
        information, along with how that measurement was obtained or 
        derived (actual measurement, estimated, or presumed).  For 
        Energy Objects that can report actual power readings, an 
        optional energy measurement can be provided. 

        Optionally, an Energy Object can further describe the Power 
        information with Power Quality information reflecting the 
        electrical characteristics of the measurement. 

        Optionally, an Energy Object that can report actual power 
        readings can have energy meters that provide the energy used, 
        produced, and net energy in kWh. These values are energy 
        meters that accumulate the power readings.  If energy values 
        are returned then the three energy meters must be provided 
        along with a description of accuracy. 

        Optionally, an Energy Object can provide demand information 
        over time.  

         

     6.5.1 Power Measurement 

        A power measurement MUST be qualified with the units, 
        magnitude, direction of power flow, and SHOULD be qualified by 
        what means the measurement was made (ex: Root Mean Square 
        versus Nameplate). 

        In addition, the Energy Object should describe how it intends 
        to measure power as one of consumer, producer or meter of 
        usage.  Given the intent, readings can be summarized or 
        analyzed by an EnMS.  For example metered usage reported by a 
        meter and consumption usage reported by a device connected to 
        that meter may naturally measure the same usage.  With the two 
        measurements identified by intent a proper summarization can 
        be made by an EnMS. 

        Power measurement magnitude should conform to the IEC 61850 
        definition of unit multiplier for the SI (System 
        International) units of measure.  Measured values are 
      
      
     <Claise, et. Al>         Expires Mar 12,2013         [Page 48] 
         


     Internet-Draft           <EMAN Framework>        October 2012 
      
        represented in SI units obtained by BaseValue * (10 ^ Scale).  
        For example, if current power usage of an Energy Object is 3, 
        it could be 3 W, 3 mW, 3 KW, or 3 MW, depending on the value 
        of the scaling factor.  3W implies that the BaseValue is 3 and 
        Scale = 0, whereas 3mW implies BaseValue = 3 and ScaleFactor = 
        -3. 

        Energy is often billed in kilowatt-hours instead of megajoules 
        from the SI units.  Similarly, battery charge is often 
        measured as miliamperes-hour (mAh) instead of coulombs from 
        the SI units.  The units used in this framework are: W, A, Wh, 
        Ah, V.  A conversion from Wh to Joule and from Ah to Coulombs 
        is obviously possible, and can be described if required. 

        In addition to knowing the usage and magnitude, it is useful 
        to know how an Energy Object usage measurement was obtained:  

        . Whether the measurements were made at the device itself or 
        from a remote source. 

        . Description of the method that was used to measure the 
        power and whether this method can distinguish actual or 
        estimated values.  

        An EnMS can use this information to account for the accuracy 
        and nature of the reading between different implementations. 

        The EnMS can use the Nameplate Power for provisioning, 
        capacity planning and potentially billing. 

         

     6.5.2 Optional Power Quality 

        Given a power measurement, it may in certain circumstances be 
        desirable to know the Power Quality associated with that 
        measurement.  The information model must adhere to the IEC 
        61850 7-2 standard for describing AC measurements.  Note that 
        the Power Quality includes two sets of characteristics: 
        characteristics as received from the utility, and 
        characteristics depending on how the power is used. 

        In some Energy Management Domains, the power quality may not 
        be needed, available, or relevant to the EnMS.   

        Optional Demand  

      
      
     <Claise, et. Al>         Expires Mar 12,2013         [Page 49] 
         


     Internet-Draft           <EMAN Framework>        October 2012 
      
        It is well known in commercial electrical utility rates that 
        demand is part of the calculation for billing.  The highest 
        peak demand measured over a time horizon, such as 1 month or 1 
        year, is often the basis for charges.  A single window of time 
        of high usage can penalize the consumer with higher energy 
        consumption charges.  However, it is relevant to measure the 
        demand only when there are actual power measurements from an 
        Energy Object, and not when the power measurement is assumed 
        or predicted.    

        Optional Battery  

        Some Energy Objects may use batteries for storing energy and 
        for receiving power supply.  These Energy Objects should 
        report their current power supply (battery, power line, etc.) 
        and the battery status for each contained battery.   Battery-
        specific information to be reported should include the number 
        of batteries contained in the device and per battery the state 
        information as defined in [EMAN-REQ]. 

        Beyond that a device containing a battery should be able to 
        generate alarms when the battery charge falls below a given 
        threshold and when the battery needs to be replaced.  

         

     6.6. Energy Control  

        An Energy Object can be controlled by setting it to a specific 
        Power State.  An Object implements a set of Power States 
        consisting of at least two states, an on state and an off 
        state. 

        A Power State is an interface by which an Energy Object can be 
        controlled.  Each Energy Object should indicate the set of 
        Power States that it implements.  Well known Power States / 
        Sets should be registered with IANA.   

        When a device is set to a particular Power State, it may be 
        busy. The device will set the desired Power State and then 
        update the actual Power State when it changes.  There are then 
        two Power State control variables: actual and desired. 

        There are many existing standards for and implementations of 
        Power States.  An Energy Object can support a mixed set of 
        Power States defined in different standards. A basic example 
        is given by the three Power States defined in IEEE1621 

      
      
     <Claise, et. Al>         Expires Mar 12,2013         [Page 50] 
         


     Internet-Draft           <EMAN Framework>        October 2012 
      
        [IEEE1621]: on, off, and sleep. The DMTF [DMTF], ACPI [ACPI], 
        and PWG define larger numbers of Power States. 

        The semantics of a power state is specified by 

           a) the functionality provided by an Energy Object in this 
        state, 

           b) a limitation of the power that an Energy Object uses in 
        this state, 

           c) a combination of a) and b) 

        The semantics of a Power State should be clearly defined. 
        Limitation (curtailment) of the power used by an Energy Object 
        in a state can be specified by 

           - an absolute power value 

           - a percentage value of power relative to the energy 
        object's nameplate power 

           - an indication of used power relative to another power 
        state - for example: by stating used power in state A is less 
        than in state B. 

        For supporting Power State management it is useful to provide 
        statistics on Power States including the time an Energy Object 
        spent in a certain Power State and/or the number of times an 
        Energy Object entered a power state. 

        Power States should be registered at IANA with a name and a 
        number.  

        When requesting an Energy object to enter a Power State an 
        indication of its name or its number can be used. Optionally 
        an absolute or percentage of Nameplate Power can be provided 
        to allow the Energy Object to transition to a nearest or 
        equivalent Power State. 

     6.6.1 EMAN Power State Set 

        An EMAN Power State Set represents an attempt for a standard 
        approach to model the different levels of power of a device.  
        The EMAN Power States are an expansion of the basic Power 
        States as defined in [IEEE1621] that also incorporates the 
        Power States defined in [ACPI] and [DMTF].  Therefore, in 
        addition to the non-operational states as defined in [ACPI] 
      
      
     <Claise, et. Al>         Expires Mar 12,2013         [Page 51] 
         


     Internet-Draft           <EMAN Framework>        October 2012 
      
        and [DMTF] standards, several intermediate operational states 
        have been defined.  

        There are twelve Power States, that expand on [IEEE1621] on, 
        sleep and off.  The expanded list of Power States are divided 
        into six operational states, and six non-operational states.  
        The lowest non-operational state is 1 and the highest is 6.  
        Each non-operational state corresponds to an [ACPI] Global and 
        System states between G3 (hard-off) and G1 (sleeping).  Each 
        operational state represents a performance state, and may be 
        mapped to [ACPI] states P0 (maximum performance power) through 
        P5 (minimum performance and minimum power).  

        In each of the non-operational states (from mechoff(1) to 
        ready(6)), the Power State preceding it is expected to have a 
        lower Power value and a longer delay in returning to an 
        operational state:  

                 mechoff(1) : An off state where no Energy Object 
        features are available.  The Energy Object is unavailable.  No 
        energy is being consumed and the power connector can be 
        removed. This corresponds to ACPI state G3.                  

                 softoff(2) : Similar to mechoff(1), but some 
        components remain powered or receive trace power so that the 
        Energy Object can be awakened from its off state.  In 
        softoff(2), no context is saved and the device typically 
        requires a complete boot when awakened.  This corresponds to 
        ACPI state G2.          

                hibernate(3): No Energy Object features are 
        available.   The Energy Object may be awakened without 
        requiring a complete boot, but the time for availability is 
        longer than sleep(4). An example for state hibernate(3) is a 
        save to-disk state where DRAM context is not maintained.  
        Typically, energy consumption is zero or close to zero.  This 
        corresponds to state G1, S4 in ACPI. 

                 sleep(4)    : No Energy Object features are 
        available, except for out-of-band management, such as wake-up 
        mechanisms.  The time for availability is longer than 
        standby(5). An example for state sleep(4) is a save-to-RAM 
        state, where DRAM context is maintained.  Typically, energy 
        consumption is close to zero.  This corresponds to state G1, 
        S3 in ACPI. 

                 standby(5) : No Energy Object features are available, 
        except for out-of-band management, such as wake-up mechanisms.  
      
      
     <Claise, et. Al>         Expires Mar 12,2013         [Page 52] 
         


     Internet-Draft           <EMAN Framework>        October 2012 
      
        This mode is analogous to cold-standy.  The time for 
        availability is longer than ready(6).  For example, the 
        processor context is not maintained. Typically, energy 
        consumption is close to zero.  This corresponds to state G1, 
        S2 in ACPI. 

                 ready(6)    : No Energy Object features are 
        available, except for out-of-band management, such as wake-up 
        mechanisms. This mode is analogous to hot-standby.  The Energy 
        Object can be quickly transitioned into an operational state.  
        For example, processors are not executing, but processor 
        context is maintained.  This corresponds to state G1, S1 in 
        ACPI.         lowMinus(7) : Indicates some Energy Object 
        features may not be available and the Energy Object has 
        selected measures/options to provide less than low(8) usage.  
        This corresponds to ACPI State G0.  This includes operational 
        states lowMinus(7) to full(12). 

                 low(8)      : Indicates some features may not be 
        available and the Energy Object has taken measures or selected 
        options to provideless than mediumMinus(9) usage. 

                 mediumMinus(9): Indicates all Energy Object features 
        are available but the Energy Object has taken measures or 
        selected options to provide less than medium(10) usage. 

                 medium(10)  : Indicates all Energy Object features 
        are available but the Energy Object has taken measures or 
        selected options to provide less than highMinus(11) usage. 

                 highMinus(11): Indicates all Energy Object features 
        are available and power usage is less than high(12). 

                 high(12)    : Indicates all Energy Object features 
        are available and the Energy Object is consuming the highest 
        power. 

        A comparison of Power States can be seen in the following 
        table: 
         
          IEEE1621  DMTF         ACPI           EMAN 
                    
          Non-operational states 
         
          off       Off-Hard     G3, S5         MechOff(1) 
          off       Off-Soft     G2, S5         SoftOff(2) 
          sleep     Hibernate    G1, S4         Hibernate(3) 
          sleep     Sleep-Deep   G1, S3         Sleep(4)  
      
      
     <Claise, et. Al>         Expires Mar 12,2013         [Page 53] 
         


     Internet-Draft           <EMAN Framework>        October 2012 
      
          sleep     Sleep-Light  G1, S2         Standby(5) 
          sleep     Sleep-Light  G1, S1         Ready(6)  
         
          Operational states: 
          on        on           G0, S0, P5     LowMinus(7) 
          on        on           G0, S0, P4     Low(8) 
          on        on           G0, S0, P3     MediumMinus(9) 
          on        on           G0, S0, P2     Medium(10) 
          on        on           G0, S0, P1     HighMinus(11) 
          on        on           G0, S0, P0     High(12) 
         
                    Figure 16: Comparison of Power States 
         
     7. Structure of the Information Model: UML Representation 

        The following basic UML represents an information model 
        expression of the concepts in this framework.  This 
        information model, provided as a reference for implementers, 
        is represented as a MIB in the different related IETF Energy 
        Monitoring documents.  However, other programming structure 
        with different data models could be used as well. 
         
        Notation is a shorthand UML with lowercase types considered 
        platform or atomic types (i.e. int, string, collection). 
        Uppercase types denote classes described further.  Collections 
        and cardinality are expressed via qualifier notation.  
        Attributes labeled static are considered class variables and 
        global to the class.  Algorithms for class variable 
        initialization, constructors or destructors are not shown 
      
        EDITOR'S NOTE: the first part of the UML must be aligned with 
        the latest [EMAN-AWARE-MIB] document version. Also, received 
        the following comment referring to the arrows in the following 
        figure: "It is not clear to me what UML relationships are 
        being specified here in the ASCIIfied UML relationships.  
        Please provide a legend to make your conventions for mapping 
        to UML clear." 
         
         
                      EO RELATIONSHIPS AND CONTEXT 
      
                                        +----------------------------+ 
                                        | _Child Specific Info __    | 
                                        |----------------------------| 
        +---------------------------+   |  parentId : UUID           | 
        |    Context Information    |   |  parentProxyAbilities      | 
        |---------------------------|   |           : bitmap         | 

      
      
     <Claise, et. Al>         Expires Mar 12,2013         [Page 54] 
         


     Internet-Draft           <EMAN Framework>        October 2012 
      
        |  roleDescription : string |   |  mgmtMacAddress : octets   | 
        |  keywords[0..n] : string  |   |  mgmtAddress : inetaddress | 
        |  importance : int         |   |  mgmtAddressType : enum    | 
        |  category :  enum         |   |  mgmtDNSName : inetaddress | 
        +---------------------------+   +----------------------------+ 
                  |                            |               
                  |                            |              
                  |                            | 
                  v                            v 
          +-----------------------------------------+ 
          |  Energy Object Information              | 
          |-----------------------------------------| 
          | index : int                             | 
          | energyObjectId | UUID                   | 
          | name : string                           |  
          | meterDomainName | string                | 
          | alternateKey | string                   | 
          +-----------------------------------------+ 
                  ^         
                  |                   
                  |                   
                  |                   
        +-------------------------+   
        |    Links Object         | 
        |-------------------------| 
        |  physicalEntity : int   | 
        |  ethPortIndex : int     | 
        |  ethPortGrpIndex : int  | 
        |  lldpPortNumber : int   |  
        +-------------------------+   
         
         
         
                     EO AND MEASUREMENTS  
         
         
        +-----------------------------------------------+ 
        |                 Energy Object                 | 
        |-----------------------------------------------| 
        |  nameplate : Measurement                      | 
        |  battery[0..n]: Battery                       | 
        |  measurements[0..n]: Measurement              | 
        | --------------------------------------------- | 
        | Measurement instantaneousUsage()              | 
        | DemandMeasurement historicalUsage()           | 
        +-----------------------------------------------+ 
         
          +-----------------------------------+ 
      
      
     <Claise, et. Al>         Expires Mar 12,2013         [Page 55] 
         


     Internet-Draft           <EMAN Framework>        October 2012 
      
          |  Measurements                     | 
          | __________________________________| 
          +-----------------------------------+ 
                            ^ 
                            | 
                            | 
         +------------------+----------------------------+   
         |         PowerMeasurement                      | 
         |-----------------------------------------------| 
         | value : long                                  | 
         | rate : enum {0,millisecond,seconds,           | 
         |              minutes,hours,...}               | 
         | multiplier : enum {-24..24}                   | 
         | units : "watts"                               | 
         | caliber : enum { actual, estimated,           | 
         |                  trusted, assumed...}         | 
         | accuracy : enum { 0..10000}                   | 
         | current :  enum {AC, DC}                      | 
         | origin : enum { self, remote }                | 
         | time : timestamp                              | 
         | quality : PowerQuality                        | 
         +-----------------------------------------------+                           
                            | 
                            | 
         +------------------+----------------------------+   
         |         EnergyMeasurement                     | 
         |-----------------------------------------------| 
         | consumed : long                               | 
         | generated : long                              | 
         | net : long                                    |   
         | accuracy : enum { 0..10000}                   | 
         +-----------------------------------------------+  
          
         
         +-----------------------------------------------+ 
         |         TimeMeasurement                       | 
         |-----------------------------------------------| 
         | startTime : timestamp                         | 
         | usage : Measurement                           | 
         | maxUsage : Measurement                        | 
         +-----------------------------------------------+ 
                            | 
                            | 
         +----------------------------------------+  
         |        TimeInterval                    | 
         |--------------------------------------- | 
         |value : long                            | 
         |units : enum { seconds, miliseconds..}  | 
      
      
     <Claise, et. Al>         Expires Mar 12,2013         [Page 56] 
         


     Internet-Draft           <EMAN Framework>        October 2012 
      
         +----------------------------------------+  
                            | 
                            | 
         +----------------------------------------+  
         |        DemandMeasurement               | 
         |----------------------------------------| 
         |intervalLength :  TimeInterval          | 
         |intervalNumbers: long                   | 
         |intervalMode :  enum { period, sliding, | 
         |total }                                 | 
         |intervalWindow : TimeInterval           | 
         |sampleRate : TimeInterval               | 
         |status : enum {active, inactive }       | 
         |measurements : TimedMeasurement[]       | 
         +----------------------------------------+  
                       
         
         
         
         
         
         
                       QUALITY 
         
         +----------------------------------------+          
         |            PowerQuality                | 
         |----------------------------------------| 
         |                                        | 
         +----------------------------------------+ 
                            ^ 
                            | 
                            | 
         +------------------+--------------------+  
         |         ACQuality                     | 
         |---------------------------------------|  
         | acConfiguration : enum {SNGL, DEL,WYE}|  
         | avgVoltage   : long                   | 
         | avgCurrent   : long                   | 
         | frequency    : long                   | 
         | unitMultiplier  : int                 | 
         | accuracy  : int                       | 
         | totalActivePower  : long              | 
         | totalReactivePower : long             | 
         | totalApparentPower : long             | 
         | totalPowerFactor : long               | 
         +---------+-----------------------------+  
                   | 1 
                   | 
      
      
     <Claise, et. Al>         Expires Mar 12,2013         [Page 57] 
         


     Internet-Draft           <EMAN Framework>        October 2012 
      
                   | 
                   | 
                   |        +------------------------------------+ 
                   |        |         ACPhase                    | 
                   |     *  |------------------------------------| 
                   +--------+ phaseIndex : long                  | 
                            | avgCurrent : long                  | 
                            | activePower : long                 | 
                            | reactivePower : long               | 
                            | apparentPower : long               | 
                            | powerFactor : long                 | 
                            +------------------------------------+ 
                                        ^           ^  
                                        |           | 
                                        |           | 
                                        |           | 
                                        |           | 
        +-------------------------------+---+       | 
        |        DelPhase                   |       | 
        |-----------------------------------|       | 
        |phaseToNextPhaseVoltage  : long    |       | 
        |thdVoltage : long                  |       | 
        |thdCurrent : long                  |       | 
        +-----------------------------------+       | 
                                                    | 
                                 +------------------+-----------+ 
                                 |        WYEPhase              | 
                                 |------------------------------| 
                                 |phaseToNeutralVoltage : long  | 
                                 |thdCurrent : long             | 
                                 |thdVoltage : long             | 
                                 +------------------------------+ 
         
      

      

                           EO & STATES 

           +----------------------------------------------+     
           |             Energy Object                    |      
           |----------------------------------------------|     
           | currentLevel : int                           |     
           | configuredLevel : int                        |     
           | configuredTime : timestamp                   |    
           | reason: string                               |   
           | emanLevels[0..11] : State                    | 
           | levelMappings[0..n] : LevelMapping           | 
      
      
     <Claise, et. Al>         Expires Mar 12,2013         [Page 58] 
         


     Internet-Draft           <EMAN Framework>        October 2012 
      
           +----------------------------------------------+  
         
            +-------------------------------+              
            |        State                  |               
            |-------------------------------|                
            | name : string                 |   
            | cardinality : int             | 
            | maxUsage : Measurement        |  
            +-------------------------------+ 
                             
         
         
      

               Figure 17: Information Model UML Representation 
      

     8. Configuration 

        This power management framework allows the configuration of 
        the following key parameters: 
         
      
          . Energy Object name: A unique printable name for the 
             Energy Object.  
          . Energy Object role: An administratively assigned name to 
             indicate the purpose an Energy Object serves in the 
             network.  
          . Energy Object importance: A ranking of how important the 
             Energy Object is, on a scale of 1 to 100, compared with 
             other Energy Objects in the same Energy Management 
             Domain.  
          . Energy Object keywords: A list of keywords that can be 
             used to group Energy Objects for reporting or searching. 
          . Energy Management Domain: Specifies the name of an Energy 
             Management Domain for the Energy Object. 
          . Energy Object Power State: Specifies the current Power 
             State for the Energy Object.  
          . Demand parameters: For example, which interval length to 
             report the Demand over, the number of intervals to keep, 
             etc. 
          . Assigning an Energy Object Parent to an Energy Object 
             Child 
          . Assigning an Energy Object Child to an Energy Object 
             Parent. 
         
         

      
      
     <Claise, et. Al>         Expires Mar 12,2013         [Page 59] 
         


     Internet-Draft           <EMAN Framework>        October 2012 
      
        This framework supports multiple means for setting the Power 
        State of a specific Energy Objects. However, the Energy Object 
        might be busy executing an important task that requires the 
        current Power State for some more time.  For example, a PC 
        might have to finish a backup first, or an IP phone might be 
        busy with a current phone call.  Therefore a second value 
        contains the actual Power State.  A difference in values 
        between the two objects indicates that the Energy Object is 
        currently in Power State transition.  
         
        Other, already well established means for setting Power 
        States, such as DASH [DASH], already exist.  Such a protocol 
        may be implemented between the Energy Object Parent and the 
        Energy Object Child, when the Energy Object Parent acts as a 
        Proxy.  Note that the Wake-up-on-Lan (WoL) mechanism allows to 
        transition a device out of the Off Power State. 
         
        
         
     9. Fault Management 

        [EMAN-REQ] specifies some requirements about Power States such 
        as "the current state - the time of the last change", "the 
        total time spent in each state", "the number of transitions to 
        each state", etc.  Such requirements are fulfilled via the 
        pmPowerStateChange NOTIFICATION-TYPE [EMAN-MON-MIB].  This 
        SNMP notification is generated when the value(s) of Power 
        State has changed for the Energy Object. 
         
        Regarding high and low thresholding mechanism, the RMON alarm 
        and event [RFC2819] allows to periodically takes statistical 
        samples from Energy Object variables, compares them to 
        previously configured thresholds, and to generate an event 
        (i.e. an SNMP notification) if the monitored variable crosses 
        a threshold. The RMON alarm can monitor variables that resolve 
        to an ASN.1 primitive type of INTEGER (INTEGER, Integer32, 
        Counter32, Counter64, Gauge32, or TimeTicks), so basically 
        most the variables in [EMAN-MON-MIB]. 
         
         
     10. Examples 

         
        In this section we will give examples of how to use the Energy 
        Management framework.  In each example we will show how it can 
        be applied when Devices have the capability to model Power 
        Interfaces.  We will also show in each example how the 
        framework can be applied when devices cannot support Power 
      
      
     <Claise, et. Al>         Expires Mar 12,2013         [Page 60] 
         


     Internet-Draft           <EMAN Framework>        October 2012 
      
        Interfaces but only monitor information or control the Device 
        as a whole. For instance a PDU may only be able to measure 
        power and energy for the entire unit without the ability to 
        distinguish among the inlets or outlet. 
      
        Together these examples show how the framework can be adapted 
        for Devices with different capabilities (typically hardware) 
        for Energy Management. 
         
        Given for all Examples:  
         
        Device W: A computer with one power supply. Power interface 1 
        is an inlets for Device W. 
         
        Device X: A computer with two power supplies. Power interface 
        1 and power interface 2 are both inlets for Device X. 
           
        Device Y: A PDU with multiple Power Interfaces numbered 0..10, 
        Power interface 0 is an inlet and power interface 1..10 are 
        outlets. 
      
        Device Z: A PDU with multiple Power Interfaces numbered 0..10, 
        Power interface 0 is an inlet and power interface 1..10 are 
        outlets. 
         
         
     Example I: Simple Device with one Source 

         
        Topology:  
          Device W inlet 1 is plugged into Device Y outlet 8. 
                   
        With Power Interfaces: 
           
          Device W has an Energy Object representing the computer 
          itself as well as one Power Interface defined as an inlet.  
           
          Device Y would have an Energy Object representing the PDU 
          itself (the Device) with a Power Interface 0 defined as an 
          inlet and Power Interfaces 1..10 defined as outlets.  
        
          The interfaces of the devices would have a Power Source 
          Relationship such that: 
          Device W inlet 1 is powered by Device Y outlet 8 
         
        Without Power Interfaces: 
                

      
      
     <Claise, et. Al>         Expires Mar 12,2013         [Page 61] 
         


     Internet-Draft           <EMAN Framework>        October 2012 
      
          In this case Device W has an Energy Object representing the 
          computer.  Device Y would have an Energy Object representing 
          the PDU.  
           
          The devices would have a Power Source Relationship such 
          that: 
          Device W is powered by Device Y. 
           
         
     Example II: Multiple Inlets 

         
        Topology:  
          Device X inlet 1 is plugged into Device Y outlet 8. 
          Device X inlet 2 is plugged into Device Y outlet 9. 
         
        With Power Interfaces: 
      
          Device X has an Energy Object representing the computer 
          itself. It contains two Power Interface defined as inlets.  
           
          Device Y would have an Energy Object representing the PDU 
          itself  (the Device) with a Power Interface 0 defined as an 
          inlet and Power Interface 1..10 defined as outlets.  
        
           
          The interfaces of the devices would have a Power Source 
          Relationship such that: 
          Device X inlet 1 is powered by Device Y outlet 8 
          Device X inlet 2 is powered by Device Y outlet 9 
         
        Without Power Interfaces: 
                
          In this case Device X has an Energy Object representing the 
          computer. Device Y would have an Energy Object representing 
          the PDU.  
           
          The devices would have a Power Source Relationship such 
          that: 
          Device X is powered by Device Y. 
           
           
     Example III: Multiple Sources 

         
        Topology:  
          Device X inlet 1 is plugged into Device Y outlet 8. 
          Device X inlet 2 is plugged into Device Z outlet 9 
      
      
     <Claise, et. Al>         Expires Mar 12,2013         [Page 62] 
         


     Internet-Draft           <EMAN Framework>        October 2012 
      
         
        With Power Interfaces: 
      
          Device X has an Energy Object representing the computer 
          itself. It contains two Power Interface defined as inlets.  
           
          Device Y would have an Energy Object representing the PDU 
          itself  (the Device) with a Power Interface 0 defined as an 
          inlet and Power Interface 1..10 defined as outlets.  
        
          Device Z would have an Energy Object representing the PDU 
          itself  (the Device) with a Power Interface 0 defined as an 
          inlet and Power Interface 1..10 defined as outlets.  
           
          The interfaces of the devices would have a Power Source 
          Relationship such that: 
          Device X inlet 1 is powered by Device Y outlet 8 
          Device X inlet 2 is powered by Device Z outlet 9 
         
        Without Power Interfaces: 
                
          In this case Device X has an Energy Object representing the 
          computer. Device Y and Z would both have respective Energy 
          Objects representing each entire PDU.  
           
          The devices would have a Power Source Relationship such 
          that: 
          Device X is powered by Device Y and powered by Device Z. 
         
         
         
     11. Relationship with Other Standards Development Organizations 

     11.1. Information Modeling  

        This power management framework should, as much as possible, 
        reuse existing standards efforts, especially with respect to 
        information modeling and data modeling [RFC3444].  
         
        The data model for power and energy related objects is based 
        on IEC 61850.   
         
        Specific examples include: 
         
          . The scaling factor, which represents Energy Object usage 
             magnitude, conforms to the IEC 61850 definition of unit 
             multiplier for the SI (System International) units of 
             measure.  
      
      
     <Claise, et. Al>         Expires Mar 12,2013         [Page 63] 
         


     Internet-Draft           <EMAN Framework>        October 2012 
      
         
          . The electrical characteristic is based on the ANSI and 
             IEC Standards, which require that we use an accuracy 
             class for power measurement.  ANSI and IEC define the 
             following accuracy classes for power measurement:  
           
             . IEC 62053-22  60044-1 class 0.1, 0.2, 0.5, 1  3.    
             
             . ANSI C12.20 class 0.2, 0.5 
           
          . The electrical characteristics and quality adheres 
             closely to the IEC 61850 7-2 standard for describing AC 
             measurements.   
           
          . The power state definitions are based on the DMTF Power 
             State Profile and ACPI models, with operational state 
             extensions.  
              
         
     12. Security Considerations 

        Regarding the data attributes specified here, some or all may 
        be considered sensitive or vulnerable in some network 
        environments. Reading or writing these attributes without 
        proper protection such as encryption or access authorization 
        may have negative effects on the network capabilities. 
     12.1 Security Considerations for SNMP 

        Readable objects in a MIB modules (i.e., objects with a MAX-
        ACCESS other than not-accessible) may be considered sensitive 
        or vulnerable in some network environments.  It is thus 
        important to control GET and/or NOTIFY access to these objects 
        and possibly to encrypt the values of these objects when 
        sending them over the network via SNMP.   
         
        The support for SET operations in a non-secure environment 
        without proper protection can have a negative effect on 
        network operations.  For example: 
         
          . Unauthorized changes to the Power Domain or business 
             context of an Energy Object may result in misreporting or 
             interruption of power. 
          . Unauthorized changes to a power state may disrupt the 
             power settings of the different Energy Objects, and 
             therefore the state of functionality of the respective 
             Energy Objects. 
          . Unauthorized changes to the demand history may disrupt 
             proper accounting of energy usage.  
      
      
     <Claise, et. Al>         Expires Mar 12,2013         [Page 64] 
         


     Internet-Draft           <EMAN Framework>        October 2012 
      
      
        With respect to data transport SNMP versions prior to SNMPv3 
        did not include adequate security.  Even if the network itself 
        is secure (for example, by using IPsec), there is still no 
        secure control over who on the secure network is allowed to 
        access and GET/SET (read/change/create/delete) the objects in 
        these MIB modules. 
         
        It is recommended that implementers consider the security 
        features as provided by the SNMPv3 framework (see [RFC3410], 
        section 8), including full support for the SNMPv3 
        cryptographic mechanisms (for authentication and privacy). 
         
        Further, deployment of SNMP versions prior to SNMPv3 is not 
        recommended.  Instead, it is recommended to deploy SNMPv3 and 
        to enable cryptographic security.  It is then a 
        customer/operator responsibility to ensure that the SNMP 
        entity giving access to an instance of these MIB modules is 
        properly configured to give access to the objects only to 
        those principals (users) that have legitimate rights to GET or 
        SET (change/create/delete) them. 
         
         
         
     13. IANA Considerations 

      
        AUTHORS NOTE: Section needs to be modified to reflect Power 
        States text introduce in version 06 
         
        Initial values for the Power State Sets, together with the 
        considerations for assigning them, are defined in [EMAN-MON-
        MIB].   
      
         
      
     14. Acknowledgments  

        The authors would like to Michael Brown for improving the text 
        dramatically, and Rolf Winter for his feedback.  The award for 
        the best feedback and reviews goes to Bill Mielke. 
      
      

      
      
     <Claise, et. Al>         Expires Mar 12,2013         [Page 65] 
         


     Internet-Draft           <EMAN Framework>        October 2012 
      
     15. References 

     Normative References 

      
        [RFC2119]  Bradner, S., "Key words for use in RFCs to Indicate 
                Requirement Levels", BCP 14, RFC 2119, March 1997. 
         
        [RFC2819]  S. Waldbusser, "Remote Network Monitoring 
                Management Information Base", STD 59, RFC 2819, May 
                2000 
         
        [RFC3410]  Case, J., Mundy, R., Partain, D., and B. Stewart, 
                "Introduction and Applicability Statements for 
                Internet Standard Management Framework ", RFC 3410, 
                December 2002. 
         
        [RFC4133]  Bierman, A. and K. McCloghrie, "Entity MIB 
                (Version3)", RFC 4133, August 2005. 
         
        [RFC4122] Leach, P., Mealling, M., and R. Salz," A Universally 
                Unique IDentifier (UUID) URN Namespace", RFC 4122, 
                July 2005 
         
     Informative References 

         
        [RFC2578] McCloghrie, K., Perkins, D., and J. Schoenwaelder, 
                "Structure of Management Information Version 2 
                (SMIv2", RFC 2578, April 1999 
         
        [RFC3444] Pras, A., Schoenwaelder, J. "On the Differences 
                between Information Models and Data Models", RFC 
                3444, January 2003. 
      
        [RFC5101] B. Claise, Ed., Specification of the IP Flow 
                Information Export (IPFIX) Protocol for the Exchange 
                of IP Traffic Flow Information, RFC 5101, January 
                2008. 
         
        [RFC6020] M. Bjorklund, Ed., " YANG - A Data Modeling Language 
                for the Network Configuration Protocol (NETCONF)", 
                RFC 6020, October 2010. 
         
        [ACPI] "Advanced Configuration and Power Interface 
                Specification", http://www.acpi.info/spec30b.htm 
         

      
      
     <Claise, et. Al>         Expires Mar 12,2013         [Page 66] 
         


     Internet-Draft           <EMAN Framework>        October 2012 
      
        [IEEE1621]  "Standard for User Interface Elements in Power 
                Control of Electronic Devices Employed in 
                Office/Consumer Environments", IEEE 1621, December 
                2004. 
      
        [LLDP]  IEEE Std 802.1AB, "Station and Media Control 
                Connectivity Discovery", 2005. 
      
        [LLDP-MED-MIB]  ANSI/TIA-1057, "The LLDP Management 
                Information Base extension module for TIA-TR41.4 
                media endpoint discovery information", July 2005. 
         
        [EMAN-REQ] Quittek, J., Winter, R., Dietz, T., Claise, B., and 
                M. Chandramouli, "Requirements for Energy 
                Management", draft-ietf-eman-requirements-09, (work 
                in progress), November 2011. 
         
        [EMAN-AWARE-MIB] Parello, J., and B. Claise, "Energy-aware 
                Networks and Devices MIB", draft-ietf-eman-energy-
                aware-mib-07, (work in progress), February 2012. 
         
        [EMAN-MON-MIB] Chandramouli, M.,Schoening, B., Quittek, J., 
                Dietz, T., and B. Claise, "Power and Energy 
                Monitoring MIB", draft-ietf-eman-energy-monitoring-
                mib-03, (work in progress), March 2012. 
         
        [EMAN-BATTERY-MIB] Quittek, J., Winter, R., and T. Dietz, " 
                Definition of Managed Objects for Battery 
                Monitoring", draft-ietf-eman-battery-mib-06, (work in 
                progress), March 2012. 
         
        [EMAN-AS] Schoening, B., Chandramouli, M., and B. Nordman, 
                "Energy Management (EMAN) Applicability Statement", 
                draft-ietf-eman-applicability-statement-02, (work in 
                progress), October 2011 
         
        [EMAN-TERMINOLOGY] J. Parello, "Energy Management 
                Terminology", draft-parello-eman-definitions-06, 
                (work in progress), March 2012 
         
        [ITU-T-M-3400] TMN recommandation on Management Functions 
                (M.3400), 1997 
         
        [NMF] "Network Management Fundamentals", Alexander Clemm, 
                ISBN: 1-58720-137-2, 2007 
         
        [TMN] "TMN Management Functions : Performance Management", 
                ITU-T M.3400 
      
      
     <Claise, et. Al>         Expires Mar 12,2013         [Page 67] 
         


     Internet-Draft           <EMAN Framework>        October 2012 
      
         
        [1037C] US Department of Commerce, Federal Standard 1037C, 
                http://www.its.bldrdoc.gov/fs-1037/fs-1037c.htm 
         
        [IEEE100] "The Authoritative Dictionary of IEEE Standards 
                Terms" 
                http://ieeexplore.ieee.org/xpl/mostRecentIssue.jsp?pu
                number=4116785 
         
        [DASH] "Desktop and mobile Architecture for System Hardware", 
                http://www.dmtf.org/standards/mgmt/dash/ 
         
        [ISO50001] "ISO 50001:2011 Energy management systems - 
                Requirements with guidance for use", 
                http://www.iso.org/  
         
        [IEC60050] International Electrotechnical Vocabulary 
                http://www.electropedia.org/iev/iev.nsf/welcome?openf
                orm 
         
        [SQL] ISO/IEC 9075(1-4,9-11,13,14):2008 
         
        [IEEE-802.3at] IEEE 802.3 Working Group, "IEEE Std 802.3at-
                2009 - IEEE Standard for Information technology - 
                Telecommunications and information exchange between 
                systems - Local and metropolitan area networks - 
                Specific requirements - Part 3: Carrier Sense 
                Multiple Access with Collision Detection (CSMA/CD) 
                Access Method and Physical Layer Specifications - 
                Amendment: Data Terminal Equipment (DTE) -  Power via 
                Media Dependent Interface (MDI) Enhancements", 
                   October 2009. 
      
        [DMTF] "Power State Management Profile DMTF  DSP1027  Version 
                2.0"  December 2009     
                http://www.dmtf.org/sites/default/files/standards/doc
                uments/DSP1027_2.0.0.pdf 
         
        [IPENERGY] R. Aldrich, J. Parello "IP-Enabled Energy 
                Management", 2010, Wiley Publishing 
         
        [X.700]  CCITT Recommendation X.700 (1992), Management 
                framework for Open Systems Interconnection (OSI) for 
                CCITT applications. 
          
        [ASHRAE-201] "ASHRAE Standard Project Committee 201  
                        (SPC 201)Facility Smart Grid Information  

      
      
     <Claise, et. Al>         Expires Mar 12,2013         [Page 68] 
         


     Internet-Draft           <EMAN Framework>        October 2012 
      
                        Model", http://spc201.ashraepcs.org 
         
        [CHEN] "The Entity-Relationship Model: Toward a Unified View 
                of Data",  Peter Pin-shan Chen, ACM Transactions on 
                Database Systems, 1976 
         
      
      
     Authors' Addresses 
      
      Benoit Claise 
      Cisco Systems, Inc. 
      De Kleetlaan 6a b1 
      Diegem 1813 
      BE 
          
      Phone: +32 2 704 5622 
      Email: bclaise@cisco.com 
      
       
      John Parello 
      Cisco Systems, Inc. 
      3550 Cisco Way  
      San Jose, California 95134  
      US 
          
      Phone: +1 408 525 2339 
      Email: jparello@cisco.com 
       
       
      Brad Schoening 
      44 Rivers Edge Drive 
      Little Silver, NJ 07739 
      US 
       
      Phone:  
      Email: brad.schoening@verizon.net 
      
       
     Juergen Quittek 
     NEC Europe Ltd.  
     Network Laboratories 
     Kurfuersten-Anlage 36 
     69115 Heidelberg 
     Germany 
      

      
      
     <Claise, et. Al>         Expires Mar 12,2013         [Page 69] 
         


     Internet-Draft           <EMAN Framework>        October 2012 
      
     Phone: +49 6221 90511 15 
     EMail: quittek@netlab.nec.de 
      
      
     Bruce Nordman 
     Lawrence Berkeley National Laboratory 
     1 Cyclotron Road 
     Berkeley  94720 
     US 
      
     Phone: +1 510 486 7089 
     Email: bnordman@lbl.gov 
      
      
       
       
       
       

      
      
     <Claise, et. Al>         Expires Mar 12,2013         [Page 70]